[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Electric</strong> supply systems are to be designed and operated so that most service voltages fall within the<br />
range A limits. User systems are to be designed and operated so that, when the service voltages are within<br />
range A, the utilization voltages are within range A. Utilization equipment is to be designed and rated<br />
to give fully satisfactory performance within the range A limits for utilization voltages.<br />
Range B is provided to allow limited excursion of voltage outside the range A limits that necessarily<br />
result from practical design and operating conditions. The supplying utility is expected to take action<br />
within a reasonable time (e.g., 2 or 3 min) to restore utilization voltages to range A limits.<br />
The combination of step-voltage regulators and fixed-ratio power transformers is often used in lieu<br />
of load-tap-changing power transformers in the substation. To obtain constant voltage at some distance<br />
(load center) from the step-voltage regulator bank, a line-drop compensation feature in the control can<br />
be utilized.<br />
Step-voltage regulators — single- and three-phase — are designed, manufactured, and tested in<br />
accordance with IEEE Std. C57.15, IEEE Standard Requirements, Technology, and Test Code for Step-<br />
Voltage Regulators. A step-voltage regulator is defined as “an induction device having one or more<br />
windings in shunt with and excited from the primary circuit, and having one or more windings in series<br />
between the primary circuit and the regulated circuit, all suitably adapted and arranged for the control<br />
of the voltage, or of the phase angle, or of both, of the regulated circuit in steps by means of taps without<br />
interrupting the load.”<br />
The most common step-voltage regulators manufactured today are single-phase, using reactive switching<br />
resulting in 32 5/8% voltage steps (16 boosting and 16 bucking the applied voltage), providing an<br />
overall 10% regulation. They are oil-immersed and typically use ANSI Type II insulating oil in accordance<br />
with ANSI/ASTM D-3487.<br />
Although not required by the IEEE standard, which now recognizes 65C rise, most manufacturers<br />
today design and manufacture step-voltage regulators rated 55C average winding rise over a 30C average<br />
ambient and use a sealed-tank-type construction. The gases generated from arcing in oil, as a result of<br />
normal operation of the load-tap changer, are vented through a pressure-relief device located on the tank<br />
above the oil level. Thermally upgraded paper insulation designed for an average winding rise of 65C,<br />
along with the use of a sealed-tank-type system, allows for a 12% increase in load over the nameplate<br />
55C rise kVA rating.<br />
Many regulators with a continuous-current rating of 668 A and below can be loaded in excess of their<br />
rated ampere load if the range of voltage regulation is limited at a value less than the normal 10% value.<br />
Table 2.7.2 shows the percent increase in ampere load permitted on each single-phase step-voltage<br />
regulator when the percent regulation range is limited to discrete values less than 10%.<br />
Some regulators have limitations in this increased current capacity due to tap-changer ampacity<br />
limitations. In those cases, the maximum tap-changer capacity is shown on the regulator nameplate.<br />
Limiting the percent regulation range is accomplished by setting limit switches in the position indicator<br />
of the regulator to prevent the tap changer from traveling beyond a set position in either raise or lower<br />
directions. It should be recognized, however, that although the regulators can be loaded by these additional<br />
amounts without affecting the regulator’s normal coil-insulation longevity, when the percent<br />
regulation is decreased, the life of the tap-changer contacts will be adversely affected.<br />
TABLE 2.7.2 Increase in Ampere Load Permitted on Single-Phase Step-Voltage<br />
Regulators for Regulation Range