06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

This may be more useful when operating a CT at higher ambient, where there is a need for the<br />

maximum rating factor. For example, if the CT has an actual rating of 2.67 based on temperature-rise<br />

data but is only rated 2.0, and if it is desired to use the CT at 50C ambient with the stated rating factor<br />

2.0, then this unit should work within its insulation rating and within its stated accuracy class.<br />

If a higher-temperature-class insulation system is provided, then the rise must be in compliance with<br />

that class per Table 2.6.8. In some cases, the temperature class is selected for the environment rather than<br />

the actual temperature rise of the CT.<br />

2.6.4.3 Open-Circuit Conditions<br />

The CT functions best with the minimum burden possible, which would be its own internal impedance.<br />

This can only be accomplished by applying a short circuit across the secondary terminals. Since the core<br />

mmf acts like a shunt, with no load connected to its secondary, the mmf becomes the primary current,<br />

thus driving the CT into hard saturation. With no load on the secondary to control the voltage, the<br />

winding develops an extremely high peak voltage. This voltage can be in the thousands, or even tens of<br />

thousands, of volts. This situation puts the winding under incredible stress, ultimately leading to failure.<br />

This could result in damage to other equipment or present a hazard to personnel. It is for this reason<br />

that the secondary circuit should never be open. It must always have a load connected. If it is installed<br />

to the primary but not in use, then the terminals should be shorted until it is to be used. Most manufacturers<br />

ship CTs with a shorting strap or wire across the secondary terminals. The CT winding must<br />

be able to withstand 3500 V peak for 1 min under open-circuit conditions. If the voltage can exceed this<br />

level, then it is recommended that overvoltage protection be used.<br />

2.6.4.4 Overvoltage Protection<br />

Under load, the CT voltage is limited. The level of this voltage depends on the turns and core crosssectional<br />

area. The user must evaluate the limits of the burdens connected to ensure equipment safety.<br />

Sometimes protective devices are used on the secondary side to maintain safe levels of voltage. These<br />

devices are also incorporated to protect the CT during an open-circuit condition. In metering applications,<br />

it is possible for such a device to introduce a direct current (dc) across the winding that could<br />

saturate the core or leave it in some state of residual flux. In high-voltage equipment, arrestors may be<br />

used to protect the primary winding from high voltage-spikes produced by switching transients or<br />

lightning.<br />

2.6.4.5 Residual Magnetism<br />

Residual magnetism, residual flux, or remanence refers to the amount of stored, or trapped, flux in the<br />

core. This can be introduced during heavy saturation or with the presence of some dc component. Figure<br />

2.6.16 shows a typical B-H curve for silicon-iron driven into hard saturation. The point at which the<br />

curve crosses zero force, identified by +B res , represents the residual flux. If at some point the CT is<br />

disconnected from the source, this flux will remain in the magnetic core until another source becomes<br />

present. If a fault current drove the CT into saturation, when the supply current resumed normal levels,<br />

the core would contain some residual component. Residual flux does not gradually decay but remains<br />

constant once steady-state equilibrium has been reached. Under normal conditions, the minor B-H loop<br />

must be high enough to remove the residual component. If it is not, then it will remain present until<br />

another fault occurrence takes place. The effective result could be a reduction of the saturation flux.<br />

However, if a transient of opposite polarity occurs, saturation is reduced with the assistance of the residual.<br />

Conversely, the magnitude of residual is also based on the polarity of the transient and the phase<br />

relationship of the flux and current. Whatever the outcome, the result could cause a delayed response to<br />

the connected relay.<br />

It has been observed that in a tape-wound toroidal core, as much as 85% of saturation flux could be<br />

left in the core as residual component. The best way to remove residual flux is to demagnetize the core.<br />

This is not always practical. The user could select a CT with a relay class that is twice that required. This<br />

may not eliminate residual flux, but it will certainly reduce the magnitude. The use of hot-rolled steel<br />

may inherently reduce the residual component to 40 to 50% of saturation flux. Another way of reducing<br />

residual magnetism is to use an air-gapped core. Normally, the introduction of a gap that is, say, 0.01%<br />

of core circumference could limit the residual flux to about 10% of the saturation flux. Referring to<br />

Figure 2.6.16, a typical B-H loop for an air-gapped core is shown. The drawback is significantly higher<br />

exciting current and lower saturation levels, as can be seen in Figure 2.6.3. To overcome the high exciting<br />

current, the core would be made larger. That — coupled with the gap — would increase its overall cost.<br />

This type of core construction is often referred to as a linearized core.<br />

2.6.4.6 CT Connections<br />

As previously mentioned, some devices are sensitive to the direction of current flow. It is often critical<br />

in three-phase schemes to maintain proper phase shifting. Residually connected CTs in three-phase<br />

ground-fault scheme (Figure 2.6.17A) sum to zero when the phases are balanced. Reversed polarity<br />

of a CT could cause a ground-fault relay to trip under a normal balanced condition. Another scheme<br />

to detect zero-sequence faults uses one CT to simultaneously monitor all leads and neutral (Figure<br />

2.6.17C). In differential protection schemes (Figure 2.6.17B), current-source phase and magnitude<br />

are compared. Reverse polarity of a CT could effectively double the phase current flowing into the<br />

relay, thus causing a nuisance tripping of a relay. When two CTs are driving a three-phase ammeter<br />

through a switch, a reversed CT could show 1.73 times the monitored current flowing in the<br />

unmonitored circuit.<br />

FIGURE 2.6.16 Typical B-H curve for Si-Fe steel.<br />

FIGURE 2.6.17 (a) Overcurrent and ground-fault protection scheme. (b) Differential protection scheme.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!