06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

and for CTs is<br />

TCF = RCF – (PA/2600) (2.6.8)<br />

The TCF is mainly applied when the instrument transformer is being used to measure energy usage.<br />

From Table 2.6.5, the limits of TCF are also the same as RCF. A negative RE will yield an RCF > 1, while<br />

a positive RE will yield an RCF < 1. The “adopted” class in Table 2.6.5 is extrapolated from these<br />

relationships and is recognized in industry.<br />

The accuracy-class limits of the CT apply to the errors at 100% of rated current up through the rating<br />

factor of the CT. At 10% of rated current, the error limits permitted are twice that of the 100% class.<br />

There is no defined requirement for the current range between 10% and 100%, nor is there any requirement<br />

below 10%. There are certain instances in which the user is concerned about the errors at 5% and<br />

will rely on the manufacturer’s guidance. Because of the nonlinearity in the core and the ankle region,<br />

the errors at low flux densities are exponential. As the current and flux density increase, the errors become<br />

linear up until the core is driven into saturation, at which point the errors increase at a tremendous rate<br />

(see Figure 2.6.9).<br />

Trends today are driving accuracy classes to 0.15%. Although not yet recognized by IEEE C57.13,<br />

manufacturers and utilities are establishing acceptable guidelines that may soon become part of the<br />

standard. With much cogeneration, the need to meter at extremely low currents with the same CT used<br />

TABLE 2.6.5 Accuracy Classes<br />

Accuracy Class RCF Range Phase Range, min TCF Range<br />

New 0.15<br />

1.0015–0.9985 ± 7.8 1.0015–0.9985<br />

IEEE C57.13 0.3<br />

1.003–0.997 ± 15.6 1.003–0.997<br />

IEEE C57.13 0.6<br />

1.006–0.994 ± 31.2 1.006–0.994<br />

IEEE C57.13 1.2<br />

1.012–0.988 ± 62.4 1.012–0.988<br />

IEEE C57.13 2.4<br />

1.024–0.976 ± 124.8 1.024–0.976<br />

Adopted 4.8<br />

1.048–0.952 ± 249.6 1.048–0.952<br />

for regular loads has forced extended-range performance to be constant from rating factor down to 1%<br />

of rated current. This is quite a deviation from the traditional class.<br />

In the case of the VT, the accuracy-class range is between 90% and 110% of rated voltage for each<br />

designated burden. Unlike the CT, the accuracy class is maintained throughout the entire range. The<br />

manufacturer will provide test data at 100% rated voltage, but it can furnish test data at other levels if<br />

required by the end user. The response is somewhat linear over a long range below 90%. Since the normal<br />

operating flux densities are much higher than in the CT, saturation will occur much sooner at voltages<br />

above 110%, depending on the overvoltage rating.<br />

Protection, or relay class, is based on the instrument transformer’s performance at some defined fault<br />

level. In VTs it may also be associated with an under- and overvoltage condition. In this case, the VT<br />

may have errors as high as 5% at levels as low as 5% of rated voltage and at the VT overvoltage rating.<br />

In CTs, the accuracy is based on a terminal voltage developed at 20 times nominal rated current. The<br />

limits of RCF are 0.90 to 1.10, or 10% RE from nominal through 20 times nominal. This applies to rated<br />

burden or any burden less than rated burden.<br />

2.6.2.6 Insulation Systems<br />

The insulation system is one of the most important features of the instrument transformer, establishing<br />

its construction, the insulation medium, and the unit’s overall physical size. The insulation system is<br />

determined by three major criteria: dielectric requirements, thermal requirements, and environmental<br />

requirements.<br />

Dielectric requirements are based on the source voltage to which the instrument transformer will be<br />

connected. This source will define voltage-withstand levels and basic impulse-insulation levels (BIL). In<br />

some cases, the instrument transformer may have to satisfy higher levels, depending on the equipment<br />

with which they are used. Equipment such as power switchgear and isolated-phase bus, for instance, use<br />

instrument transformers within their assembly, but they have test requirements that differ from the<br />

instrument-transformer standard. It is not uncommon to require a higher BIL class for use in a highly<br />

polluted environment. See Table 2.6.6A and Table 2.6.6B. <br />

TABLE 2.6.6A Low- and Medium-Voltage Dielectric Requirements<br />

Class, kV Instrument <strong>Transformer</strong>s (IEEE C57.13) Other Equipment Standards a<br />

BIL, kV Withstand Voltage, kV BIL, kV Withstand Voltage, kV<br />

0.6 10 4 — 2.2<br />

1.2 30 10 — —<br />

2.4 45 15 — —<br />

5.0 60 19 60 19<br />

8.7 75 26 75/95 26/36<br />

15.0 95/110 34 95/110 36/50<br />

25.0 125/150 40/50 125/150 60<br />

34.5 200 70 150 80<br />

46 250 95 — —<br />

69 350 140 350 160<br />

a<br />

IEEE C37.06, C37.20.1, C37.20.2,C37.20.3, C37.23.<br />

TABLE 2.6.6B High-Voltage Dielectric Requirements<br />

FIGURE 2.6.9 CT RCF characteristic curve.<br />

Class, kV Instrument <strong>Transformer</strong>s (IEEE C57.13) Other Equipment Standards (IEEE C37.06)<br />

BIL, kV Withstand Voltage, kV BIL, kV Withstand Voltage, kV<br />

115 450/550 185/230 550 215/260<br />

138 650 275 650 310<br />

161 750 325 750 365<br />

230 900/1050 395/460 900 425<br />

345 1300 575 1300 555<br />

500 1675/1800 750/800 1800 860<br />

765 2050 920 2050 960<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!