06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

2.3.8.1.2 Series Connection<br />

• The throughput power of a single unit is equal to the total throughput power.<br />

• The phase-shift angle of a single unit is equal to 1/n of the total phase-shift angle.<br />

• The impedance of a single unit in ohms is 1/n of the total impedance.<br />

• The impedance of a single unit in percent, referred to the throughput power, is 1/n of the total<br />

impedance in percent.<br />

• When one unit is lost or bypassed, the throughput power remains constant, and the total phaseshift<br />

angle and the total impedance in ohms and in percent are reduced by (n – 1)/n.<br />

2.3.8.2 Tests<br />

In case of a two-tank design, the PST should be completely assembled with the two units connected<br />

together, as in service.<br />

Auxiliary bushings may be necessary to make inner windings accessible for measurements of resistances,<br />

losses, and temperatures or to allow dielectric tests.<br />

2.3.8.2.1 Special Dielectric Tests<br />

When bypassing of the unit is a specified operating condition, a special lightning impulse and a special<br />

switching impulse has to be performed with both terminals of the series winding connected.<br />

2.3.8.2.2 No-Load Phase-Shift Angle<br />

From Figure 2.3.5, the phase shift angle can be calculated as<br />

(2.3.41)<br />

with V S , V L , and V S–L being the absolute values of the voltages of corresponding source and load terminals<br />

to ground and between them, respectively.<br />

To differentiate between advanced and retard angle, the following criteria can be used:<br />

advanced phase-shift angle:<br />

retard phase-shift angle:<br />

V S1 – V S2 > V S1 – V L2<br />

V S1 – V S2 < V S1 – V L2<br />

The tolerance depends on the accuracy of the voltages. ANSI/IEEE C57.135 recommends that this be<br />

1%. This considers the worst case, when V S and V L are at the upper tolerance limit (1.005) and V S–L is<br />

at the lower limit (0.995).<br />

References<br />

V V V<br />

arccos <br />

2 * V * V<br />

2 2 2<br />

S L S L<br />

S L<br />

ANSI/IEEE, Guide for the Application, Specification and Testing of Phase-Shifting <strong>Transformer</strong>s, ANSI/<br />

IEEE C57.135-2001, Institute of <strong>Electric</strong>al and Electronics <strong>Engin</strong>eers, Piscataway, NJ, 2001.<br />

Brown, F.B., Lundquist, T.G. et al., The First 525 kV Phase Shifting <strong>Transformer</strong> — Conception to Service,<br />

presented at 64th Annual Conference of Doble Clients, 1997.<br />

Krämer, A., On-Load Tap-Changers for <strong>Power</strong> <strong>Transformer</strong>s, Maschinenfabrik Reinhausen, Regensburg,<br />

Germany, 2000.<br />

Seitlinger, W., Phase Shifting <strong>Transformer</strong>s — Discussion of Specific Characteristics, CIGRE Paper 12-<br />

306, CIGRE, Paris, 1998.<br />

2.4 Rectifier <strong>Transformer</strong>s<br />

Sheldon P. Kennedy<br />

<strong>Power</strong> electronic circuits can convert alternating current (ac) to direct current (dc). These are called<br />

rectifier circuits. <strong>Power</strong> electronic circuits can also convert direct current to alternating current. These<br />

are called inverter circuits. Both of these circuits are considered to be converters. A transformer that has<br />

one of its windings connected to one of these circuits, as a dedicated transformer, is a converter transformer,<br />

or rectifier transformer. IEC standards refer to these transformers as converter transformers,<br />

while IEEE standards refer to these transformers as rectifier transformers. Because it is IEEE practice to<br />

refer to these transformers as rectifier transformers, that same term is used throughout this discussion.<br />

<strong>Transformer</strong>s connected to circuits with a variety of loads, but which may contain some electronic<br />

circuits that produce harmonics, are not considered to be rectifier transformers. However, they may have<br />

harmonic heating effects similar to rectifier transformers. Those transformers are covered under IEEE<br />

Recommended Practice for Establishing <strong>Transformer</strong> Capability when Supplying Non-Sinusoidal Load<br />

Currents, ANSI/IEEE C57.110.<br />

Electronic circuits provide many types of control today, and their use is proliferating. These circuits<br />

are generally more efficient than previous types of control, and they are applied in many types of everyday<br />

use. Rectifier circuits are used to provide high-current dc for electrochemical processes like chlorine<br />

production as well as copper and aluminum production. They are also used in variable-speed-drive motor<br />

controls, transit traction applications, mining applications, electric furnace applications, higher-voltage<br />

laboratory-type experiments, high-voltage direct-current power transmission (HVDC), static precipitators,<br />

and others. While HVDC transmission and static precipitators are not directly covered in this<br />

chapter, much of the basic information still applies.<br />

2.4.1 Background and Historical Perspective<br />

Rectifier transformers can be liquid-immersed, dry-type, or cast-coil technology. Dry-type transformers<br />

were primarily used in distribution-voltage classes. Impregnation systems have improved with the development<br />

of vacuum pressure impregnation (VPI) technology. These types of transformers have been<br />

developed to 34-kV and 46-kV classes, although basic-impulse-insulation levels (BIL) are often less than<br />

in liquid-immersed transformers. Cast-coil technology has developed as a more rugged, nonliquid-filled<br />

technology. Both of these types of transformers — dry type and cast coil — are limited by voltage and<br />

kVA size. They have advantages over liquid-filled transformers for fire protection, since they have no<br />

liquids to ignite. However, liquid-immersed transformers can be built to all voltage levels and current<br />

levels. High-fire-point fluids can be used for fire-protection considerations. Auxiliary cooling can be<br />

utilized to cool larger levels of power loss developed in higher-current applications.<br />

The early rectifiers were pool-cathode mercury rectifiers. These had high levels of short-circuit failures<br />

on transformers and suffered from arc-backs. When one phase faulted, all phases would dump through<br />

the faulted phase. So on a six-phase transformer with 10% impedance, instead of 10 times rated current<br />

during a fault, it could develop up to 60 times rated current. Usually the fault would not be this high,<br />

but it could still be in the area of 40 times rated current. This is an extremely high fault current for a<br />

transformer to withstand. <strong>Transformer</strong>s had to be built very ruggedly and were extremely heavy compared<br />

with most transformers, which greatly increased the cost of these systems. They also had the disadvantage<br />

of the environmental problems associated with mercury. These transformers were built to comply with<br />

ANSI/IEEE C57.18-1964, Pool Cathode Mercury-Arc Rectifier <strong>Transformer</strong>. The latest revision of this<br />

standard was 1964, but it was reaffirmed later.<br />

Semiconductor rectifiers advanced higher in voltage and current capability, and finally semiconductor<br />

technology developed to the point that pool-cathode mercury-arc rectifiers were replaced. Semiconductor<br />

rectifiers also brought the ability of control with thyristors in addition to diodes, without the use of<br />

magnetic devices such as the saturable core reactors and amplistats that had been used for this purpose.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!