S1 S2 S3 L1 L2 L3 Series Unit Main Unit FIGURE 2.3.12 Two-core PST. FIGURE 2.3.14 Quadrature booster set (300 MVA, 50 Hz, 40012*1.25%/11512*1.45˚ kV). L , , L a) b) S c) FIGURE 2.3.15 Winding arrangements. , L Y Y FIGURE 2.3.13 Quadrature booster — simplified connection diagram. 2.3.6 Details of <strong>Transformer</strong> Design In general, the design characteristics of PSTs do not differ from ordinary power transformers. In the symmetrical case, however, the phase-angle difference of the currents flowing through the two parts of the series winding has to be recognized. The additional magnetic field excited by the self-compensating components in the series winding influences mechanical forces, additional losses, and the short-circuit impedance. Figure 2.3.15 shows schematically variations of the physical winding arrangements in PSTs. In Figure 2.3.15a, a double concentric design of a single-phase PST is shown. This arrangement does not offer any problems with respect to the phase lag between currents and is a standard winding arrangement in shell-type transformers. In core types, the arrangement of the connecting leads from the innermost regulating winding need some attention, but this does not present a real obstacle to the use © 2004 by CRC Press LLC © 2004 by CRC Press LLC
150 V(%) 100 50 0 -50 40 80 T(s) 120 FIGURE 2.3.16 Lightning impulse response (bypassed PST). of this design. On the other hand, the axial arrangement of the regulating winding in core-type transformers, as shown in Figure 2.3.15b, offers the advantage of direct access and saves space. But because the pattern of the stray field is more complicated, thorough field calculations have to be performed using the appropriate computer programs. It is possible that a client may operate the PST in a bypassed condition. In this case, the source and load terminals are directly connected phasewise. In this state, a lightning impulse would penetrate the series winding from both ends at the same time. Two traveling waves would meet in the middle of the winding and would theoretically be reflected to double the amplitude (Figure 2.3.16). Therefore the series winding must either be designed with a high internal capacitance or be protected by external or internal surge arresters. A high internal capacitance can be obtained using any of the measures that are used to improve the lightning-impulse voltage distribution along the winding, e.g., interleaving or shielding. Again, the axial arrangement is more advantageous and easier to make self-protecting. Figure 2.3.15c shows the arrangement of a two-core design with two coarse and one fine tap winding, which is a variation of the circuit drawn in Figure 2.3.12 (see also Section 2.3.7, Details of On-Load Tap- Changer Application). If a two-tank solution has to be used, the connection between the main and series unit requires an additional set of six high-voltage bushings, which means that a total of nine high-voltage bushings would have to be arranged on the series unit. Because a short circuit between the main and series units could destroy the regulating winding, a direct and encapsulated connection between the two tanks is preferred. This requires a high degree of accuracy in the mechanical dimensions and the need for experienced field engineers to assemble both units on site. If required, special oil-tight insulation systems allow the separation of the two tanks without the need to drain the oil in one or both units. In the latter case, an extra oil-expansion system is needed for the connecting tubes. Figure 2.3.17 shows a double-tank PST design at a testing site. 2.3.7 Details of On-Load Tap-Changer Application OLTCs are subject to numerous limits. The most essential limit is, of course, the current-interrupting or current-breaking capability. In addition to this limit, the voltage per step and the continuous current are also limited. The product of these two limits is generally higher than the capability limit, so the maximum voltage per step and the maximum current cannot be utilized at the same time. Table 2.3.1, Table 2.3.2, and Table 2.3.3 show examples for design power, voltage per step, and system current as functions of phase-shift angle, throughput power, system voltage, and number of voltage steps. These limits (e.g., 4000 V/step, 2000 A) determine the type of regulation (the need for only a fine tap winding or a combination of fine and coarse tap windings) and the number of parallel branches. But it must be noted that the mutual induction resulting from the use of a coarse/fine-tap winding configuration also has to be taken into account and may influence the decision. FIGURE 2.3.17 Two-tank PST at a test site (coolers not assembled) (650 MVA, 60 Hz, 525/52520*1.2˚ kV). TABLE 2.3.1 Design <strong>Power</strong> of PSTs as a Function of Throughput <strong>Power</strong> and Phase-Shift Angle, MVA Throughput <strong>Power</strong>, MVA Design <strong>Power</strong>, MVA Phase-Shift Angle ˚ 10 20 30 40 50 100 17.4 34.7 51.8 68.4 84.5 250 43.6 86.8 129.4 171.0 211.3 500 87.2 173.6 258.8 342.5 422.6 750 130.7 260.5 388.2 513.0 633.9 1000 174.3 347.3 517.6 684.0 845.2 TABLE 2.3.2 Step Voltage as a Function of System Voltage and Phase-Shift Angle for a 16-Step OLTC, V System Voltage, kV Step Voltage, V Phase-Shift Angle ˚ Steps:16 10 20 30 40 50 69.0 434 865 1,289 1,703 2,104 115.0 723 1,441 2,148 2,839 3,507 138.0 868 1,729 2,578 3,406 4,209 161.0 1,013 2,018 3,007 3,974 4,910 230.0 1,447 2,882 4,296 5,677 7,015 345.0 2,170 4,324 6,444 8,516 10,522 500.0 3,145 6,266 9,339 12,342 15,250 765.0 4,812 9,587 14,289 18,883 23,332 Another problem that also is not specific to PSTs, but may be more significant, is the possible altering of the potential of the regulating winding when the changeover selector is operated. In this moment, the tap selector is positioned at tap “K” (see Figure 2.3.18), and the regulating winding is no longer fixed to the potential of the excitation winding. The new potential is determined by the ratio of the capacitances © 2004 by CRC Press LLC © 2004 by CRC Press LLC
- Page 1 and 2: ELECTRIC POWER TRANSFORMER ENGINEER
- Page 3 and 4: I wish to recognize the interest of
- Page 5 and 6: Contents 1 Theory and Principles Ch
- Page 7 and 8: 1.3 Equivalent Circuit of an Iron-C
- Page 9 and 10: designer starts to make a design fo
- Page 11 and 12: • Transient voltages generated du
- Page 13 and 14: the transformer’s bushings and, m
- Page 15 and 16: % regulation = [(V NL - V FL )/V FL
- Page 17 and 18: In core-form transformers, the wind
- Page 19 and 20: FIGURE 2.1.14 Layer windings (singl
- Page 21 and 22: the transformer design, which may b
- Page 23 and 24: consumer’s service circuit is a d
- Page 25 and 26: FIGURE 2.2.3 Single-phase transform
- Page 27 and 28: is installed so that the tank never
- Page 29 and 30: above which persons might be burned
- Page 31 and 32: FIGURE 2.2.16 Two-bushing subway. (
- Page 33 and 34: carbon steel or the very expensive
- Page 35 and 36: FIGURE 2.2.31 Radial-style dead fro
- Page 37 and 38: FIGURE 2.2.36 Complete transformer
- Page 39 and 40: voltage in each winding simultaneou
- Page 41 and 42: mounted transformers can have arres
- Page 43 and 44: V S + V S I V L Z=R+jX a) V L V S V
- Page 45 and 46: Z = jX (2.3.19) 0.7 Then the curren
- Page 47: X1 L* X1 S =X1 L X2 L* X3 L* a) S L
- Page 51 and 52: 2.3.8.1.2 Series Connection • The
- Page 53 and 54: A six-pulse single-way transformer
- Page 55 and 56: The degree of coupling also influen
- Page 57 and 58: where I h = current for the hth har
- Page 59 and 60: In the case of liquid-filled transf
- Page 61 and 62: FIGURE 2.4.21 A 36-pulse system mad
- Page 63 and 64: Vacuum-pressure encaps ulated — T
- Page 65 and 66: FIGURE 2.6.1 Typical wiring and sin
- Page 67 and 68: a) H1 b) Ip X2 FLUX H2 LEAKAGE FLUX
- Page 69 and 70: and for CTs is TCF = RCF - (PA/2600
- Page 71 and 72: RCF x Bx Bt RCF t - RCF 0 co
- Page 73 and 74: 2000 1000 5% Vex BANDWITH FROM NOMI
- Page 75 and 76: This may be more useful when operat
- Page 77 and 78: also some uncertainty in repeatabil
- Page 79 and 80: FIGURE 2.6.25 Standard two-element
- Page 81 and 82: 2.7 Step-Voltage Regulators Craig A
- Page 83 and 84: Source Bypass Switch Source Bypass
- Page 85 and 86: 2.7.4 Theory A step-voltage regulat
- Page 87 and 88: FIGURE 2.7.22 Equalizer winding inc
- Page 89 and 90: TABLE 2.7.4 Increase in Ampere Load
- Page 91 and 92: References IEEE, Standard Requireme
- Page 93 and 94: 300% FIGURE 2.8.4 Schematic of a co
- Page 95 and 96: TABLE 2.8.1 Typical Sizing Workshee
- Page 97 and 98: Input with Interruption Ferro Outpu
- Page 99 and 100:
FIGURE 2.8.20A Performance of a rid
- Page 101 and 102:
• Input frequency or frequency ra
- Page 103 and 104:
References 1. Sola/Hevi-Duty Corp.,
- Page 105 and 106:
FIGURE 2.9.5 Typical phase-reactor
- Page 107 and 108:
FIGURE 2.9.10 Two generator arrange
- Page 109 and 110:
• Overloading of lines • Increa
- Page 111 and 112:
FIGURE 2.9.23 34-kV, 25-MVAR (per p
- Page 113 and 114:
V 90 ( X X ) s T (2.9.10a) where,
- Page 115 and 116:
Therefore, Line reactive losses = (
- Page 117 and 118:
ate of rise of transient-recovery v
- Page 119 and 120:
the LLCR is provided in IEEE Std. C
- Page 121 and 122:
aluminum shielding, i.e., an oil-im
- Page 123 and 124:
Leo J. Savio ADAPT Corporation Ted
- Page 125 and 126:
3.1.2.2.2 Heat Dissipation A second
- Page 127 and 128:
FIGURE 3.2.1 Solid-type bushing. ma
- Page 129 and 130:
1.6 cm. This means that most of the
- Page 131 and 132:
where HS = steady-state bushing ho
- Page 133 and 134:
the conductivity of the water-solub
- Page 135 and 136:
of 178 ohm-m, and a test duration o
- Page 137 and 138:
2. Easley, J.K. and Stockum, F.R.,
- Page 139 and 140:
FIGURE 3.3.5 Reactance-type LTC, in
- Page 141 and 142:
FIGURE 3.3.10 LTC with delta connec
- Page 143 and 144:
3.3.5 Selection of Load Tap Changer
- Page 145 and 146:
FIGURE 3.3.19 Effect of the leakage
- Page 147 and 148:
References Goosen, P.V. , Transform
- Page 149 and 150:
If i 1 is the full-load current rat
- Page 151 and 152:
TABLE 3.4.1 Loading Recommendations
- Page 153 and 154:
3.5.4 Three-Phase Transformer Conne
- Page 155 and 156:
FIGURE 3.5.4 Interconnected star-gr
- Page 157 and 158:
3.6.1.1 Standards ANSI standards fo
- Page 159 and 160:
ANSI standards. LTC control setting
- Page 161 and 162:
FIGURE 3.6.7 Discharging the capaci
- Page 163 and 164:
FIGURE 3.6.10 Standard switching-im
- Page 165 and 166:
voltage of the excited winding, rea
- Page 167 and 168:
FIGURE 3.6.18 Current, voltage, and
- Page 169 and 170:
TABLE 3.6.3 Transformer Short-Circu
- Page 171 and 172:
FIGURE 3.7.3 Control for voltage re
- Page 173 and 174:
FIGURE 3.7.6A Feeder with power-fac
- Page 175 and 176:
3. Circulating current (current bal
- Page 177 and 178:
FIGURE 3.7.10 Control block diagram
- Page 179 and 180:
Primary Current (Amps) 60 40 20 0 -
- Page 181 and 182:
current transformer having two prim
- Page 183 and 184:
87R1 87BL1 (A) Independent Harmonic
- Page 185 and 186:
Winding 1 Secondary Currents Data A
- Page 187 and 188:
Y Y 20 18 3 rd Harmonic CTR1=40 CTR
- Page 189 and 190:
230 kV 3 180 MVA 138 kV 5 CTR1 = 2
- Page 191 and 192:
29. Concordia, C. and Rothe, F.S.,
- Page 193 and 194:
FIGURE 3.9.1 Measurement of pressur
- Page 195 and 196:
H 2m 1. Vertical Forced Air 2. Prin
- Page 197 and 198:
Gade, S., Sound Intensity Instrumen
- Page 199 and 200:
nected. This steady-state voltage d
- Page 201 and 202:
where [A] = state matrix [B] = inpu
- Page 203 and 204:
where C = capacitance between the t
- Page 205 and 206:
L ijo = N i N j ijo (3.10.31) 1.4
- Page 207 and 208:
% VOLTAGE % VOLTAGE 100 BIL 90 50 3
- Page 209 and 210:
29. Degeneff, R.C., Reducing Storag
- Page 211 and 212:
All connections should be cleaned a
- Page 213 and 214:
6. Costs to set up and use a mobile
- Page 215 and 216:
Records of relay operation must be
- Page 217 and 218:
• Has heating occurred as the res
- Page 219 and 220:
a reference value) of the currents
- Page 221 and 222:
The next data-processing step is to
- Page 223 and 224:
temperature. As the transformer coo
- Page 225 and 226:
3.13.3.2 Instrument Transformers Th
- Page 227 and 228:
FIGURE 3.13.5 Analysis of bushing s
- Page 229 and 230:
temperature. Under abnormal conditi
- Page 231 and 232:
3.14.1.2 Accredited Standards Commi
- Page 233 and 234:
FIGURE 3.14.4 IEC technical-committ
- Page 235 and 236:
TABLE 3.14.2 Relevant Documents for
- Page 237 and 238:
TABLE 3.14.5 Relevant Documents for
- Page 239 and 240:
TABLE 3.14.9 Relevant Documents for
- Page 241:
TABLE 3.14.13 Relevant Documents fo