06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

where cos is again the power factor of the load, therefore kVA · cos is real energy delivered to the<br />

load. NL is the no-load loss, and LL is the load loss of the transformer. Most distribution transformers<br />

serving residential or light industrial loads are not fully loaded all the time. It is assumed that such<br />

transformers are loaded to about 50% of nameplate rating on the average. Thus efficiency is often<br />

calculated at L = 0.5, where the load loss is about 25% of the value at full load. Since a typical transformer<br />

will have no-load loss of around 25% of load loss at 100% load, then at L = 0.5, the no-load loss will<br />

equal the load loss and the efficiency will be at a maximum.<br />

2.2.11 <strong>Transformer</strong> Loading<br />

2.2.11.1 Temperature Limits<br />

According to ANSI standards, modern distribution transformers are to operate at a maximum 65˚C<br />

average winding rise over a 30˚C ambient air temperature at rated kVA. One exception to this is submersible<br />

or vault-type distribution transformers, where a 55˚C rise over a 40˚C ambient is specified. The<br />

bulk oil temperature near the top of the tank is called the “top oil temperature,” which cannot be more<br />

than 65˚C over ambient and will typically be about 55˚C over ambient, 10˚C less than the average winding<br />

rise.<br />

2.2.11.2 Hottest-Spot Rise<br />

The location in the transformer windings that has the highest temperature is called the “hottest spot.”<br />

Standards require that the hottest-spot temperature not exceed 80˚C rise over a 30˚C ambient, or 110˚C.<br />

These are steady-state temperatures at rated kVA. The hottest spot is of great interest because, presumably,<br />

this is where the greatest thermal degradation of the transformer’s insulation system will take place. For<br />

calculation of thermal transients, the top-oil rise over ambient air and the hottest-spot rise over top oil<br />

are the parameters used.<br />

2.2.11.3 Load Cycles<br />

If all distribution loads were constant, then determining the proper loading of transformers would be a<br />

simple task. Loads on transformers, however, vary through the hours of a day, the days of a week, and<br />

through the seasons of the year. Insulation aging is a highly nonlinear function of temperature that<br />

accumulates over time. The best use of a transformer, then, is to balance brief periods of hottest-spot<br />

temperatures slightly above 110C with extended periods at hottest spots well below 110˚C. Methods for<br />

calculating the transformer loss-of-life for a given daily cycle are found in the ANSI Guide for Loading<br />

(IEEE, 1995). Parameters needed to make this calculation are the no-load and load losses, the top-oil<br />

rise, the hottest-spot rise, and the thermal time constant.<br />

2.2.11.4 Thermal Time Constant<br />

Liquid-filled distribution transformers can sustain substantial short-time overloads because the mass of<br />

oil, steel, and conductor takes time to come up to a steady-state operating temperature. Time constant<br />

values can vary from two to six hours, mainly due to the differences in oil volume vs. tank surface for<br />

different products.<br />

2.2.11.5 Loading Distribution <strong>Transformer</strong>s<br />

Utilities often assign loading limits to distribution transformers that are different from the transformer’s<br />

nameplate kVA. This is based on three factors: the actual ambient temperature, the shape of the load<br />

curve, and the available air for cooling. For example, one utility divides its service territory into three<br />

temperature situations for different ambient temperatures: summer interior, summer coastal, and winter.<br />

The transformer installations are divided into three applications for the available air cooling: overhead<br />

or pad-mounted, surface operable, and vault. The load shape is expressed by the peak-day load factor,<br />

which is defined as the season’s peak kVA divided by the average kVA and then expressed as a percentage.<br />

Table 2.2.1 shows the assigned capabilities for a 100-kVA transformer. Thus this utility would assign the<br />

TABLE 2.2.1 Assigned Capabilities for a 100-kVA <strong>Transformer</strong><br />

Location<br />

Overhead or<br />

pad-mounted<br />

Surface<br />

operable<br />

Vault<br />

<strong>Transformer</strong><br />

Peak-Day Load Factor<br />

Temperature<br />

District kVA 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%<br />

Summer 100 205 196 187 177 168 159 149 140 131 122<br />

interior<br />

Summer coastal 100 216 206 196 186 176 166 156 146 136 126<br />

Winter 100 249 236 224 211 198 186 173 160 148 135<br />

Summer 100 147 140 133 127 120 113 107 100 93 87<br />

interior<br />

Summer coastal 100 154 147 140 133 126 119 111 104 97 90<br />

Winter 100 178 169 160 151 142 133 124 115 105 96<br />

Summer 100 173 164 156 147 139 130 122 113 105 96<br />

interior<br />

Summer coastal 100 182 173 164 155 146 137 127 118 109 100<br />

Winter 100 185 176 166 157 147 138 128 119 110 100<br />

same 100-kVA transformer a peak capability of 87 to 249 kVA depending on its location, the season, and<br />

the load-shape.<br />

2.2.12 <strong>Transformer</strong> Testing<br />

2.2.12.1 Design Tests<br />

Tests that manufacturers perform on prototypes or production samples are referred to as “design tests.”<br />

These tests may include sound-level tests, temperature-rise tests, and short-circuit-current withstand<br />

tests. The purpose of a design test is to establish a design limit that can be applied by calculation to every<br />

transformer built. In particular, short-circuit tests are destructive and may result in some invisible damage<br />

to the sample, even if the test is passed successfully. The ANSI standard calls for a transformer to sustain<br />

six tests, four with symmetrical fault currents and two with asymmetrical currents. One of the symmetrical<br />

shots is to be of long duration, up to 2 s, depending on the impedance for lower ratings. The<br />

remaining five shots are to be 0.25 s in duration. The long-shot duration for distribution transformers<br />

750 kVA and above is 1 s. The design passes the short-circuit test if the transformer sustains no internal<br />

or external damage (as determined by visual inspection) and minimal impedance changes. The tested<br />

transformer also has to pass production dielectric tests and experience no more than a 25% change in<br />

exciting current (Bean et al., 1959).<br />

2.2.12.2 Production Tests<br />

Production tests are given to and passed by each transformer made. Tests to determine ratio, polarity or<br />

phase-displacement, iron loss, load loss, and impedance are done to verify that the nameplate information<br />

is correct. Dielectric tests specified by industry standards are intended to prove that the transformer is<br />

capable of sustaining unusual but anticipated electrical stresses that may be encountered in service.<br />

Production dielectric tests may include applied-voltage, induced-voltage, and impulse tests.<br />

2.2.12.2.1 Applied-Voltage Test<br />

Standards require application of a voltage of (very roughly) twice the normal line-to-line voltage to each<br />

entire winding for one minute. This checks the ability of one phase to withstand voltage it may encounter<br />

when another phase is faulted to ground and transients are reflected and doubled.<br />

2.2.12.2.2 Induced-Voltage Test<br />

The original applied-voltage test is now supplemented with an induced-voltage test. Voltage at higher<br />

frequency (usually 400 Hz) is applied at twice the rated value of the winding. This induces the higher<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!