06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

• Vault-type transformers are suitable for occasional submerged operation.<br />

• Subway transformers are suitable for frequent or continuous submerged operation.<br />

From the definitions, the vault type should only be used when a sump pump is installed, while the<br />

subway-type could be installed without a sump pump. The principal distinction between vault and subway<br />

is their corrosion resistance. For example, the 1994 version of the network standard, C57.12.40, required<br />

the auxiliary coolers to have a corrosion-resistance equivalence of not less than 5/16 in. of copper-bearing<br />

steel for subway transformers but only 3/32 in. for vault-type transformers. In utility application, vault<br />

and subway types may be installed in the same type of enclosure, and the use of a sump pump is predicated<br />

more on the need for quick access for operations than it is on whether the transformer is a vault or<br />

subway type.<br />

2.2.7.1.1 <strong>Transformer</strong>s for Vault Installation<br />

2.2.7.1.1.1 Network <strong>Transformer</strong>s — As defined in IEEE C57.12.80 (IEEE, 2002b), network transformers<br />

(see Figure 2.2.13) are designed for use in vaults to feed a variable-capacity system of interconnected<br />

secondaries. They are three-phase transformers that are designed to connect through a network protector<br />

to a secondary network system. Network transformers are typically applied to serve loads in the downtown<br />

areas of major cities. National standard C57.12.40 (ANSI, 2000a) details network transformers. The<br />

standard kVA ratings are 300, 500, 750, 1000, 1500, 2000, and 2500 kVA. The primary voltages range<br />

from 2,400 to 34,500 V. The secondary voltages are 216Y/125 or 480Y/277.<br />

Network transformers are built as either vault type or subway type. They incorporate a primary switch<br />

with open, closed, and ground positions. Primary cable entrances are made by one of the following<br />

methods:<br />

FIGURE 2.2.14 Single-phase subway. (By permission of Pacific Gas & <strong>Electric</strong> Company, San Francisco, CA.)<br />

• Wiping sleeves or entrance fittings for connecting to lead cables — either one three-conductor or<br />

three single-conductor fittings or sleeves<br />

• Bushing wells or integral bushings for connecting to plastic cables — three wells or three bushings<br />

2.2.7.1.1.2 Network Protectors — Although not a transformer, the network protector is associated with<br />

the network transformer. The protector is an automatic switch that connects and disconnects the<br />

transformer from the secondary network being served. The protector connects the transformer when<br />

power flows from the primary circuit into the secondary network, and it disconnects upon reverse<br />

power flow from the secondary to the primary. The protector is described in C57.12.44 (IEEE, 2000c).<br />

The protector is typically mounted on the secondary throat of the network transformer, as shown in<br />

Figure 2.2.13.<br />

FIGURE 2.2.13 Network transformer with protector. (By permission of Pacific Gas & <strong>Electric</strong> Company, San<br />

Francisco, CA.)<br />

FIGURE 2.2.15 Three-bushing subway. (By permission of Pacific Gas & <strong>Electric</strong> Company, San Francisco, CA.)<br />

2.2.7.1.1.3 Single-Phase Subway or Vault Types — These are round single-phase transformers designed to<br />

be installed in a vault and capable of being banked together to provide three-phase service (Figure 2.2.14).<br />

These can be manufactured as either subway-type or vault-type transformers. They are typically applied<br />

to serve small- to medium-sized commercial three-phase loads. The standard kVA ratings are 25, 37.5,<br />

50, 75, 100, 167, and 250 kVA. Primary voltages range from 2,400 to 34,500 V, with the secondary voltage<br />

usually being 120/240. Four secondary bushings allow the secondary windings to be connected in parallel<br />

for wye connections or in series for delta connections. The secondary can be either insulated cables or<br />

spades. The units are designed to fit through a standard 36-in.-diameter manhole. They are not specifically<br />

covered by a national standard, however they are very similar to the units in IEEE C57.12.23 (IEEE,<br />

2002c). Units with three primary bushings or wells, and with an internal primary fuse (Figure 2.2.15),<br />

allow for connection in closed-delta, wye, or open-wye banks. They can also be used for single-phase<br />

phase-to-ground connections.<br />

Units with two primary bushings or wells, and with two internal primary fuses (Figure 2.2.16) allow<br />

for connection in an open-delta or an open-wye bank. This construction also allows for single-phase<br />

line-to-line connection.<br />

2.2.7.1.1.4 Three-Phase Subway or Vault Types — These are rectangular-shaped three-phase transformers<br />

that can be manufactured as either subway-type or vault-type. Figure 2.2.17 depicts a three-phase vault.<br />

These are used to supply large three-phase commercial loads. Typically they have primary-bushing well<br />

terminations on one of the small sides and the secondary bushings with spades on the opposite end.<br />

These are also designed for radial installation and require external fusing. They can be manufactured in<br />

any of the standard three-phase kVA sizes and voltages. They are not detailed in a national standard.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!