[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Phase Conductor<br />
Model of CT Insulation<br />
Ir<br />
Ic<br />
I total = Ir + Ic<br />
FIGURE 3.13.3 Schematic representation of relative tan delta measurements.<br />
Measurement Impedance<br />
Installation can require factory modifications, depending on the type of sensor that is installed (Boisseau<br />
and Tantin, 1993). Typically, the hydrogen sensor is located in an area where the oil is stagnant, especially<br />
during periods of low ambient temperatures. This arrangement results in poor accuracy for low hydrogenconcentration<br />
levels. For significant hydrogen concentrations (above 300 ppm) in stagnant oil, the<br />
accuracy has been determined to be acceptable (Cummings et al., 1988). These constraints may not apply<br />
to the thermal conductivity detection (TCD) technology. In this case, the sensor is located externally to<br />
the apparatus and utilizes active oil circulation through the monitor while also providing continuous<br />
moisture-level monitoring.<br />
3.13.3.2.2.3 On-Line Partial Discharge Measurements — On-line partial-discharge measurement techniques<br />
that were discussed in the section on power transformers (Section 3.13.3.1) are also applicable to<br />
instrument transformers.<br />
3.13.3.2.2.4 Pressure — Due to partial-discharge activity inside the tank, gases can be formed, which<br />
increases the pressure after the gases saturate the oil. A threshold-pressure switch can be used to perform<br />
this measurement. The operation of this sensor is possible with an inflatable bellows that is placed between<br />
the expansion device and the enclosure. The installation of the device typically requires factory modification.<br />
In some applications, pressure sensors take a considerable amount of time (on the order of<br />
months) to detect any significant pressure change. The sensitivity of this type of measurement is less<br />
than that of hydrogen and partial-discharge sensors (Boisseau and Tantin, 1993). Pressure sensors are<br />
also available that mount on the drain valve (Cummings et al., 1988).<br />
3.13.3.3 Bushings<br />
Bushings are subjected to high dielectric and thermal stresses, and bushing failures are one of the leading<br />
causes of forced outages and transformer failures. The methods of detecting deterioration of the bushing<br />
insulation have been well understood for decades, and conventional off-line diagnostics are very effective<br />
at discovering problems. The challenge facing a maintenance engineer is that some problems have<br />
gestation time (i.e., going from good condition to failure) that is shorter than typical routine test intervals.<br />
Since on-line monitoring of power-factor and capacitance can be performed continuously, and with the<br />
same sensitivity as the off-line measurement, deciding whether to apply an on-line system is reduced to<br />
an economic exercise of weighing the direct and strategic benefits with the cost.<br />
FIGURE 3.13.4 Bushing sum-current measurements.<br />
3.13.3.3.1 Failure Mechanisms Associated with Bushings<br />
The two most common bushing failure mechanisms are moisture contamination and partial discharge.<br />
Moisture usually enters the bushing via deterioration of gasket material or cracks in terminal connections,<br />
resulting in an increase in the dielectric loss and insulation power factor. The presence of tracking over<br />
the surface or burn-through of the condenser core is typically associated with partial discharge. The first<br />
indication of this type of problem is an initial increase in power factor. As the deterioration progresses,<br />
increases in capacitance will be observed.<br />
3.13.3.3.2 On-Line Bushing <strong>Power</strong>-Factor and Capacitance Measurements<br />
Measurement of power factor and capacitance is a useful and reliable diagnostic indicator. The sumcurrent<br />
method is a very sensitive method for obtaining these parameters on-line. The basic principle<br />
of the sum-current method is based on the fact that the sums of the voltage and current phasors are zero<br />
in a symmetrical three-phase system. Therefore, analysis of bushing condition can be performed by<br />
adding the current phasors from the capacitance or power-factor taps, as depicted in Figure 3.13.4. If<br />
the bushings are identical and system voltages are perfectly balanced, the sum current, I S , will equal zero.<br />
In reality, bushings are never identical, and system voltages are never perfectly balanced. As a result,<br />
the sum current is a nonzero value and is unique for each set of bushings. The initial sum current can<br />
be learned, and the condition of the bushings can be determined by evaluating changes in the sumcurrent<br />
phasor. By using software techniques and an expert system to analyze changes to the sum current,<br />
changes in either the capacitance or power factor of any of the bushings being monitored can be detected,<br />
as shown in Figure 3.13.5.<br />
Figure 3.13.5a depicts a change that is purely resistive, i.e., only the in-phase component of current is<br />
changing. It is due to a change in C 1 insulation power factor, and it results in the current phasor change<br />
I A from I 0 A to I A . The change in current is in phase with A-phase line voltage, V A , and it is equal to<br />
I . This is then evidence of a power factor increase for the A-phase bushing.<br />
Figure 3.13.5b depicts a change that is purely capacitive, i.e., only a quadrature component of current<br />
is changing. In this case, the change is due to a change in C 1 insulation capacitance, and it results in the<br />
current phasor change I A from I 0 A to I A . The change in current leads the voltage V A by 90˚, and it is<br />
equal to I .<br />
Expert systems are also used to determine whether the sum-current change is related to actual bushing<br />
deterioration or changes in environmental conditions such as fluctuations in system voltages, changes<br />
in bushing or ambient temperature, and changes in surface conditions (Lachman, 1999).<br />
3.13.3.4 Load Tap Changers<br />
High maintenance costs for load tap changers (LTC) result from several causes. The main reasons include:<br />
misalignment of contacts, poor design of the contacts, high loads, excessive number of tap changes,<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC