[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Records of relay operation must be analyzed to determine the sequence of events. A failure of a<br />
transformer due to a through fault, if uncorrected, can lead to the failure of a replacement unit. This<br />
can be a very expensive oversight.<br />
Based on initial observations and recordings, a preliminary cause may be determined. Subsequent<br />
tests should focus on confirming or refuting this cause.<br />
3.12.2.4 Operational History<br />
3.12.2.4.1 Diagnostic Testing<br />
The operation records of the transformer should be examined in detail. Records of field tests such as<br />
insulation resistance and power factor, gas-in-oil analyses, oil test data, and bushing tests should be<br />
studied. Any trends from normal such as increasing power factor, water in oil, or deterioration of oil<br />
properties should be noted. Any internal inspections that may have been performed, changes in oil, and<br />
any repairs or modifications are of interest. Maintenance records should be examined for evidence of<br />
either good or poor maintenance practices. Proper application of arresters and other protective schemes<br />
should be verified.<br />
3.12.2.4.2 Severe Duty<br />
Operational history such as switching events, numbers and type of system short circuits, known lightning<br />
strikes, overloads, etc., should be recorded.<br />
3.12.2.4.2.1 Overloads — The effect of loading a transformer beyond nameplate is not apparent without<br />
disassembly. The history of transformer operation will be the first indication of damage from overloads.<br />
The transformer may have some inherent capability to handle loading in excess of nameplate rating.<br />
However, the result of loading beyond nameplate can result in accelerated loss of life. This loss of life is<br />
cumulative and cannot be restored. Loading recommendations are more fully described in IEEE C57.91-<br />
1995, Guide for Loading Mineral-Oil-Immersed <strong>Transformer</strong>s, and in IEEE C57.96-1999, Guide for<br />
Loading Dry-Type Distribution and <strong>Power</strong> <strong>Transformer</strong>s.<br />
3.12.2.4.2.2 Overvoltages — Maximum continuous transformer operating voltage should not exceed the<br />
levels specified in ANSI C84.1-1995. Overexcitation will result in core heating and subsequent damage.<br />
The results of core heating may not be readily discerned until a transformer is untanked. Examination<br />
of the operating records may provide insight into this as a cause of damage.<br />
3.12.2.4.2.3 Short Circuits — IEEE C57.12.00-2000, IEEE Standard General Requirements for Liquid-<br />
Immersed Distribution, <strong>Power</strong>, and Regulating <strong>Transformer</strong>s, and IEEE C57.12.01, IEEE Standard General<br />
Requirements for Dry-Type Distribution and <strong>Power</strong> <strong>Transformer</strong>s Including Those with Solid-Cast<br />
and/or Resin-Encapsulated Windings, state limits for short-circuit durations and magnitude. Not all<br />
short-circuits reach the magnitude of those limits. However, like overloads, the effect can be cumulative.<br />
This effect is further expanded in IEEE C57.109-1993, IEEE Guide for Liquid-Immersed <strong>Transformer</strong><br />
Through-Fault-Current Duration. The effect is described as an “extremely inverse time-current characteristic”<br />
upon which the overcurrent protection of the transformer should be based.<br />
3.12.3 Problem Analysis where No Failure Is Involved<br />
3.12.3.1 <strong>Transformer</strong> Components<br />
Component failures can lead to major failures if left uncorrected. All of these should be corrected as soon<br />
as identified to avoid letting them develop into problems that are more serious.<br />
3.12.3.1.1 <strong>Transformer</strong> Tank<br />
<strong>Transformer</strong> tank welds can crack after thermal cycling or even after withstanding the stresses of throughfaults.<br />
Bushing and radiator gaskets can deteriorate over time, leading to leaks. Left unattended, these<br />
leaks can result in moisture entering the transformer insulation.<br />
3.12.3.1.2 <strong>Transformer</strong> Radiators and Coolers<br />
Radiators can leak, leading to ingress of moisture, or they can clog, reducing their cooling efficiency. Fan<br />
motors can fail, resulting in a loss of cooling. Today’s modern low-loss transformer designs can have a<br />
dual rating ONAN/ONAF with as few as one or two cooling fans. Loss of a large percentage of the fans<br />
necessitates using the ONAN rating for transformer capacity. (See Section 2.1.2.3, Cooling Classes, for<br />
a discussion of cooling-class terminology.)<br />
3.12.3.1.3 <strong>Transformer</strong> Bushings<br />
Bushings occasionally develop problems such as leaks or high power factor and thermal problems.<br />
Problems detected during periodic diagnostic testing should be remedied as quickly as possible.<br />
3.12.3.1.4 <strong>Transformer</strong> Gauges<br />
Gauges and indicating devices should be repaired or replaced as soon as it is suspected that they are<br />
giving false indication. Confirm that the abnormal indication is false and replace the device. Letting a<br />
false indication continue may disguise the development of a more severe problem.<br />
3.12.3.2 Severe Duty Investigations<br />
It is advisable to make some investigations after severe operating events such as direct lightning strikes<br />
(if known), high-magnitude short-circuit faults, and inadvertent high-magnitude overloads. Problem<br />
investigations are sometimes more difficult than failure analyses because some of the internal parts<br />
cannot be seen without dismantling the transformer. The same data-collection process is recommended<br />
for problems as for failures. It is recommended that a plan be prepared when the investigation<br />
is initiated, including a checklist to guide the study and to ensure that no important steps are omitted.<br />
A recommended checklist is in ANSI/IEEE C57.125. Specific steps that are recommended are as<br />
follows:<br />
3.12.3.2.1 Communication with Persons Involved or Site Visit<br />
• Obtain the background of the events indicating a problem.<br />
• If there is any external evidence such as loss of oil, overheated parts, or other external indications,<br />
a site visit may be advisable to get first-hand information and to discuss the events with persons<br />
who operated the transformer.<br />
• Determine if there have been any unusual events such as short circuits, overvoltages, or overloads.<br />
3.12.3.2.2 Diagnostic Testing<br />
If the utility has a comprehensive field-testing program, obtain and study the following data. If the data<br />
are not available, arrange for tests to be made.<br />
3.12.3.2.2.1 Gas-in-Oil Analyses — Obtain test results for several years prior to the event, if possible.<br />
Many good papers and texts have discussed the interpretation of dissolved gas-in-oil analysis (DGA)<br />
results. One must also remember that once an internal failure has occurred, the initiating cause may be<br />
masked by the resulting fault gases. IEEE C57.104-1991, IEEE Guide for Interpretation of Gases Generated<br />
in Oil-Immersed <strong>Transformer</strong>s, can provide the latest interpretation of DGA results.<br />
3.12.3.2.2.2 Oil Test Data — Dielectric strength in accordance with ASTM D 1816<br />
• Water in oil<br />
• <strong>Power</strong> factor at 25 and 100˚C, if available<br />
• General characteristics such as color, inter-facial tension (IFT), etc.<br />
3.12.3.2.2.3 Turns Ratio — This test should match the factory results and be within the standard 0.5%<br />
of calculated value (except as noted in Clause 9.1 of IEEE C57.12.00-2000). Any deviation indicates a<br />
partially shorted turn.<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC