06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Records of relay operation must be analyzed to determine the sequence of events. A failure of a<br />

transformer due to a through fault, if uncorrected, can lead to the failure of a replacement unit. This<br />

can be a very expensive oversight.<br />

Based on initial observations and recordings, a preliminary cause may be determined. Subsequent<br />

tests should focus on confirming or refuting this cause.<br />

3.12.2.4 Operational History<br />

3.12.2.4.1 Diagnostic Testing<br />

The operation records of the transformer should be examined in detail. Records of field tests such as<br />

insulation resistance and power factor, gas-in-oil analyses, oil test data, and bushing tests should be<br />

studied. Any trends from normal such as increasing power factor, water in oil, or deterioration of oil<br />

properties should be noted. Any internal inspections that may have been performed, changes in oil, and<br />

any repairs or modifications are of interest. Maintenance records should be examined for evidence of<br />

either good or poor maintenance practices. Proper application of arresters and other protective schemes<br />

should be verified.<br />

3.12.2.4.2 Severe Duty<br />

Operational history such as switching events, numbers and type of system short circuits, known lightning<br />

strikes, overloads, etc., should be recorded.<br />

3.12.2.4.2.1 Overloads — The effect of loading a transformer beyond nameplate is not apparent without<br />

disassembly. The history of transformer operation will be the first indication of damage from overloads.<br />

The transformer may have some inherent capability to handle loading in excess of nameplate rating.<br />

However, the result of loading beyond nameplate can result in accelerated loss of life. This loss of life is<br />

cumulative and cannot be restored. Loading recommendations are more fully described in IEEE C57.91-<br />

1995, Guide for Loading Mineral-Oil-Immersed <strong>Transformer</strong>s, and in IEEE C57.96-1999, Guide for<br />

Loading Dry-Type Distribution and <strong>Power</strong> <strong>Transformer</strong>s.<br />

3.12.2.4.2.2 Overvoltages — Maximum continuous transformer operating voltage should not exceed the<br />

levels specified in ANSI C84.1-1995. Overexcitation will result in core heating and subsequent damage.<br />

The results of core heating may not be readily discerned until a transformer is untanked. Examination<br />

of the operating records may provide insight into this as a cause of damage.<br />

3.12.2.4.2.3 Short Circuits — IEEE C57.12.00-2000, IEEE Standard General Requirements for Liquid-<br />

Immersed Distribution, <strong>Power</strong>, and Regulating <strong>Transformer</strong>s, and IEEE C57.12.01, IEEE Standard General<br />

Requirements for Dry-Type Distribution and <strong>Power</strong> <strong>Transformer</strong>s Including Those with Solid-Cast<br />

and/or Resin-Encapsulated Windings, state limits for short-circuit durations and magnitude. Not all<br />

short-circuits reach the magnitude of those limits. However, like overloads, the effect can be cumulative.<br />

This effect is further expanded in IEEE C57.109-1993, IEEE Guide for Liquid-Immersed <strong>Transformer</strong><br />

Through-Fault-Current Duration. The effect is described as an “extremely inverse time-current characteristic”<br />

upon which the overcurrent protection of the transformer should be based.<br />

3.12.3 Problem Analysis where No Failure Is Involved<br />

3.12.3.1 <strong>Transformer</strong> Components<br />

Component failures can lead to major failures if left uncorrected. All of these should be corrected as soon<br />

as identified to avoid letting them develop into problems that are more serious.<br />

3.12.3.1.1 <strong>Transformer</strong> Tank<br />

<strong>Transformer</strong> tank welds can crack after thermal cycling or even after withstanding the stresses of throughfaults.<br />

Bushing and radiator gaskets can deteriorate over time, leading to leaks. Left unattended, these<br />

leaks can result in moisture entering the transformer insulation.<br />

3.12.3.1.2 <strong>Transformer</strong> Radiators and Coolers<br />

Radiators can leak, leading to ingress of moisture, or they can clog, reducing their cooling efficiency. Fan<br />

motors can fail, resulting in a loss of cooling. Today’s modern low-loss transformer designs can have a<br />

dual rating ONAN/ONAF with as few as one or two cooling fans. Loss of a large percentage of the fans<br />

necessitates using the ONAN rating for transformer capacity. (See Section 2.1.2.3, Cooling Classes, for<br />

a discussion of cooling-class terminology.)<br />

3.12.3.1.3 <strong>Transformer</strong> Bushings<br />

Bushings occasionally develop problems such as leaks or high power factor and thermal problems.<br />

Problems detected during periodic diagnostic testing should be remedied as quickly as possible.<br />

3.12.3.1.4 <strong>Transformer</strong> Gauges<br />

Gauges and indicating devices should be repaired or replaced as soon as it is suspected that they are<br />

giving false indication. Confirm that the abnormal indication is false and replace the device. Letting a<br />

false indication continue may disguise the development of a more severe problem.<br />

3.12.3.2 Severe Duty Investigations<br />

It is advisable to make some investigations after severe operating events such as direct lightning strikes<br />

(if known), high-magnitude short-circuit faults, and inadvertent high-magnitude overloads. Problem<br />

investigations are sometimes more difficult than failure analyses because some of the internal parts<br />

cannot be seen without dismantling the transformer. The same data-collection process is recommended<br />

for problems as for failures. It is recommended that a plan be prepared when the investigation<br />

is initiated, including a checklist to guide the study and to ensure that no important steps are omitted.<br />

A recommended checklist is in ANSI/IEEE C57.125. Specific steps that are recommended are as<br />

follows:<br />

3.12.3.2.1 Communication with Persons Involved or Site Visit<br />

• Obtain the background of the events indicating a problem.<br />

• If there is any external evidence such as loss of oil, overheated parts, or other external indications,<br />

a site visit may be advisable to get first-hand information and to discuss the events with persons<br />

who operated the transformer.<br />

• Determine if there have been any unusual events such as short circuits, overvoltages, or overloads.<br />

3.12.3.2.2 Diagnostic Testing<br />

If the utility has a comprehensive field-testing program, obtain and study the following data. If the data<br />

are not available, arrange for tests to be made.<br />

3.12.3.2.2.1 Gas-in-Oil Analyses — Obtain test results for several years prior to the event, if possible.<br />

Many good papers and texts have discussed the interpretation of dissolved gas-in-oil analysis (DGA)<br />

results. One must also remember that once an internal failure has occurred, the initiating cause may be<br />

masked by the resulting fault gases. IEEE C57.104-1991, IEEE Guide for Interpretation of Gases Generated<br />

in Oil-Immersed <strong>Transformer</strong>s, can provide the latest interpretation of DGA results.<br />

3.12.3.2.2.2 Oil Test Data — Dielectric strength in accordance with ASTM D 1816<br />

• Water in oil<br />

• <strong>Power</strong> factor at 25 and 100˚C, if available<br />

• General characteristics such as color, inter-facial tension (IFT), etc.<br />

3.12.3.2.2.3 Turns Ratio — This test should match the factory results and be within the standard 0.5%<br />

of calculated value (except as noted in Clause 9.1 of IEEE C57.12.00-2000). Any deviation indicates a<br />

partially shorted turn.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!