FIGURE 3.8.30 DC content of the differential current for Case 3.<br />

TABLE 3.8.3 Inrush Detection Methods Performance during Inrush Conditions<br />

Method Case 1 Case 2 Case 3<br />

<br />

<br />

Low even-harmonic Second-harmonic setting<br />

content<br />

6%<br />

8%<br />

Second- and fourthharmonic<br />

blocking<br />

All-harmonic restraint<br />

Low-current detection<br />

Even-harmonic restraint<br />

DC-ratio blocking<br />

4. An improved approach for transformer protection that combines harmonic-restraint and -blocking<br />

methods with a waveshape-recognition technique provides added security to the independent<br />

harmonic-restraint element without sacrificing dependability. This new method uses even harmonics<br />

for restraint, plus dc component and fifth harmonic for blocking.<br />

5. Using even-harmonic restraint ensures security for inrush currents with low second-harmonic<br />

content and maintains dependability for internal faults with CT saturation. The use of fifthharmonic<br />

blocking guarantees an invariant relay response to overexcitation. Using dc-offset blocking<br />

ensures security for inrush conditions with very low total harmonic distortion.<br />

References<br />

Percentage<br />

100<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

0 1 2 3 4 5 6 7<br />

Cycles<br />

<br />

High third-harmonic<br />

content<br />

<br />

Low-current interval = 1 / 4<br />

cycle<br />

<br />

Low even-harmonic<br />

content<br />

<br />

DC ratio = zero<br />

Note: = Correct operation; = Misoperation.<br />

<br />

Even-harmonic content<br />

<br />

Low-current interval > 1 / 4<br />

cycle<br />

<br />

Even-harmonic content<br />

<br />

DC ratio > 0.1 after 1 cycle<br />

<br />

Second-harmonic setting<br />

<br />

Harmonic content<br />

<br />

Low-current interval < 1 / 4<br />

cycle<br />

<br />

Even-harmonic content<br />

<br />

DC ratio = zero<br />

1. Klingshirn, E.A., Moore, H.R., and Wentz, E.C., Detection of faults in power transformers, AIEE<br />

Trans., 76, 87–95, 1957.<br />

2. Madill, J.T., Typical transformer faults and gas detector relay protection, AIEE Trans., 66,<br />

1052–1060, 1947.<br />

3. Bean, R.L. and Cole, H.L., A sudden gas pressure relay for transformer protection, AIEE Trans.,<br />

72, 480–483, 1953.<br />

4. Monseth, I.T. and Robinson, P.H., Relay Systems: Theory and Applications, McGraw Hill, New York,<br />

1935.<br />

5. Sleeper, H.P., Ratio differential relay protection, <strong>Electric</strong>al World, 827831, October 1927.<br />

6. Cordray, R.E., Percentage differential transformer protection, <strong>Electric</strong>al Eng., 50, 361–363, 1931.<br />

7. Cordray, R.E., Preventing false operation of differential relays, <strong>Electric</strong>al World, 160–161, July 25,<br />

1931.<br />

8. Harder, E.L. and Marter, W.E., Principles and practices of relaying in the United States, AIEE Trans.,<br />

67, 1005–1023, 1948.<br />

9. Kennedy, L.F., and Hayward, C.D., Harmonic-current-restrained relays for differential protection,<br />

AIEE Trans., 57, 262–266, 1938.<br />

10. Hayward, C.D., Harmonic-current-restrained relays for transformer differential protection, AIEE<br />

Trans., 60, 377–382, 1941.<br />

11. Mathews, C.A., An improved transformer differential relay, AIEE Trans., 73, 645–650, 1954.<br />

12. Sharp, R.L. and Glassburn, W.E., A transformer differential relay with second-harmonic restraint,<br />

AIEE Trans., 77, 913–918, 1958.<br />

13. Einval, C.H. and Linders, J.R., A three-phase differential relay for transformer protection, IEEE<br />

Trans., PAS-94, 1971–1980, 1975.<br />

14. Dmitrenko, A.M., Semiconductor pulse-duration differential restraint relay, Izv. Vysshikh Uchebnykh<br />

Zavedenii, Elektromekhanika, No. 3, 335–339, March 1970 (in Russian).<br />

15. Atabekov, G.I., The Relay Protection of High Voltage Networks, Pergamon Press, London, 1960.<br />

16. Rockefeller, G.D., Fault protection with a digital computer, IEEE Trans., PAS-98, 438464, 1969.<br />

17. Wilkinson, S.B., <strong>Transformer</strong> Differential Relay, U.S. Patent 5,627,712, May 6, 1997.<br />

18. Hayward, C.D., Prolonged inrush currents with parallel transformers affect differential relaying,<br />

AIEE Trans., 60, 10961101, 1941.<br />

19. Blume, L.F., Camilli, G., Farnham, S.B., and Peterson, H.A., <strong>Transformer</strong> magnetizing inrush<br />

currents and influence on system operation, AIEE Trans., 63, 366375, 1944.<br />

20. Specht, T.R., <strong>Transformer</strong> magnetizing inrush current, AIEE Trans., 70, 323328, 1951.<br />

21. AIEE Committee Report, Report on transformer magnetizing current and its effect on relaying<br />

and air switch operation, AIEE Trans., 70, 17331740, 1951.<br />

22. Sonnemann, W.K., Wagner, C.L., and Rockefeller, G.D., Magnetizing inrush phenomena in transformer<br />

banks, AIEE Trans., 77, 884892, 1958.<br />

23. Berdy, J., Kaufman, W., and Winick, K., A Dissertation on <strong>Power</strong> <strong>Transformer</strong> Excitation and<br />

Inrush Characteristics, presented at Symposium on <strong>Transformer</strong> Excitation and Inrush Characteristics<br />

and Their Relationship to <strong>Transformer</strong> Protective Relaying, Houston, TX, 1976.<br />

24. Zocholl, S.E., Guzmán, A., and Hou, D., <strong>Transformer</strong> Modeling as Applied to Differential Protection,<br />

presented at 22nd Annual Western Protective Relay Conference, Spokane, WA, 1995.<br />

25. Cooper <strong>Power</strong> Systems, <strong>Electric</strong> <strong>Power</strong> System Harmonics: Design Guide, Cooper <strong>Power</strong> Systems,<br />

Bulletin 87011, Franksville, WI, 1990.<br />

26. Waldron, J.E. and Zocholl, S.E., Design Considerations for a New Solid-State <strong>Transformer</strong> Differential<br />

Relay with Harmonic Restraint, presented at Fifth Annual Western Protective Relay Conference,<br />

Sacramento, CA, 1978.<br />

27. Marshall, D.E. and Langguth, P.O., Current transformer excitation under transient conditions,<br />

AIEE Trans., 48, 14641474, 1929.<br />

28. Wentz, E.C. and Sonnemann, W.K., Current transformers and relays for high-speed differential<br />

protection with particular reference to offset transient currents, AIEE Trans., 59, 481488, 1940.<br />

© 2004 by CRC Press LLC<br />