06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

IOP<br />

Operating Region<br />

Slope 2<br />

(SLP2)<br />

2 nd Harmonic<br />

Blocking<br />

4 th Harmonic<br />

Blocking<br />

5HB1<br />

S2<br />

S3<br />

S4<br />

2HB1<br />

S1<br />

87BL1<br />

S5<br />

Slope 1<br />

(SLP1)<br />

60%<br />

DCBL1<br />

FIGURE 3.8.16 Differential-element blocking logic.<br />

O87P=0.3<br />

25%<br />

Restraining Region<br />

(A) IHBL=Y<br />

(B) IHBL=N<br />

IRS1=3<br />

FIGURE 3.8.14 Percentage restraint differential characteristic.<br />

S +<br />

IRT<br />

87R1<br />

87BL1<br />

87R2<br />

87BL2<br />

87R3<br />

87BL3<br />

87R<br />

87R1<br />

87R2<br />

87R3<br />

87BL1<br />

87BL2<br />

87BL3<br />

87R<br />

Min<br />

Max<br />

DCR<br />

_<br />

+<br />

DCBL1<br />

FIGURE 3.8.17 Differential-relay blocking logic.<br />

3.8.7 Differential-Element Performance during Inrush Conditions<br />

Differential Current<br />

S -<br />

0.1<br />

Following is a study of the performance of the differential elements for three field cases of transformer<br />

energization. These cases are special because they cause some of the traditional differential elements to<br />

misoperate.<br />

FIGURE 3.8.15 DC blocking logic.<br />

the maximum of the absolute values of the two one-cycle sums and calculate the dc ratio, DCR, by<br />

dividing the minimum one-cycle sum value by the maximum one-cycle sum value. When DCR is less<br />

than a threshold value of 0.1, the relay issues a blocking signal, DCBL1. Then, the relay blocking condition<br />

is according to Equation 3.8.25.<br />

By defining DCR as the ratio of the minimum to the maximum values of the one-cycle sums, an<br />

accounting is made for differential currents having positive or negative dc-offset components. In addition,<br />

the resulting DCR value is normalized.<br />

Relay tripping requires the fulfillment of Equation 3.8.19 but not Equation 3.8.13 or Equation 3.8.25.<br />

3.8.6.4 Relay Blocking Logic<br />

Figure 3.8.16 depicts the blocking logic of the differential elements. If the even-harmonic restraint is not<br />

in use, switch S1 closes to add even-harmonic blocking to the fifth-harmonic and dc blocking functions.<br />

In this case, the differential elements operate in a blocking-only mode. Switches S2, S3, S4, and S5 permit<br />

enabling or disabling each of the blocking functions. The output (87BL1) of the differential-element<br />

blocking logic asserts when any one of the enabled logic inputs asserts.<br />

Figure 3.8.17 shows the blocking logic of the differential relay. The relay can be set to an independent<br />

blocking mode (IHBL=Y) or a common blocking mode (IHBL=N).<br />

3.8.7.1 Case 1<br />

Figure 3.8.18 shows a transformer energization case while A-phase is faulted and the transformer is not<br />

loaded. The transformer is a three-phase, delta–wye-connected distribution transformer; the CT connections<br />

are wye at both sides of the transformer.<br />

Figure 3.8.19 shows the differential element 1 inrush current; this element uses I AB current. This signal<br />

looks like a typical inrush current. The current signal has low second-harmonic content and high dc<br />

content compared with the fundamental. Another interesting fact is that this signal also has high thirdharmonic<br />

content. Figure 3.8.20 shows the second, third, and fourth harmonic as percentages of fundamental.<br />

Notice that the second harmonic drops below 5%. Figure 3.8.21 shows the dc content as a<br />

percentage of fundamental of the inrush current. The dc content is high during the event; this is useful<br />

information for adding security to the differential relay.<br />

The differential elements operate as follows:<br />

3.8.7.1.1 Second- and Fourth-Harmonic Blocking<br />

The low second- and fourth-harmonic content produces misoperation of the differential element that<br />

uses independent harmonic blocking.<br />

3.8.7.1.2 All-Harmonic Restraint<br />

The harmonic-restraint relay that uses all harmonics maintains its security because of the high thirdharmonic<br />

content of the inrush current.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!