06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Primary Current (Amps)<br />

60<br />

40<br />

20<br />

0<br />

-20<br />

TABLE 3.8.1 Harmonic Content of the Current Signal Shown in Figure 3.8.3<br />

Frequency Component Magnitude (primary amps) Percentage of Fundamental<br />

Fundamental 22.5 100.0<br />

Third 11.1 49.2<br />

Fifth 4.9 21.7<br />

Seventh 1.8 8.1<br />

<br />

<br />

<br />

<br />

<br />

-40<br />

-60<br />

0.5 1 1.5 2 2.5<br />

Cycles<br />

FIGURE 3.8.3 Exciting current of an overexcited transformer; overvoltage of 150% applied to a 5-KVA, 230/115-<br />

V single-phase transformer.<br />

• Second harmonics are added at 120.<br />

• Third harmonics are added at 180 (they cancel out), etc.<br />

Sonnemann et al. initially claimed that the second-harmonic content of the inrush current was never<br />

less than 16 to 17% of the fundamental [22]. However, transformer energization with reduced voltages<br />

can generate inrush currents with second-harmonic content less than 10%, as will be discussed later in<br />

this section.<br />

3.8.3.2 <strong>Transformer</strong> Overexcitation<br />

The magnetic flux inside the transformer core is directly proportional to the applied voltage and inversely<br />

proportional to the system frequency. Overvoltage and/or underfrequency conditions can produce flux<br />

levels that saturate the transformer core. These abnormal operating conditions can exist in any part of<br />

the power system, so any transformer can be exposed to overexcitation.<br />

<strong>Transformer</strong> overexcitation causes transformer heating and increases exciting current, noise, and<br />

vibration. A severely overexcited transformer should be disconnected to avoid transformer damage.<br />

Because it is difficult, with differential protection, to control the amount of overexcitation that a transformer<br />

can tolerate, transformer differential protection tripping for an overexcitation condition is not<br />

desirable. Instead, use separate transformer overexcitation protection, and the differential element should<br />

not trip for these conditions. One alternative is a V/Hz relay that responds to the voltage/frequency ratio.<br />

Overexcitation of a power transformer is a typical case of ac saturation of the core that produces odd<br />

harmonics in the exciting current. Figure 3.8.3 shows the exciting current recorded during a real test of<br />

a 5-kVA, 230/115-V, single-phase laboratory transformer [24]. The current corresponds to an overvoltage<br />

condition of 150% at nominal frequency. For comparison purposes, the peak value of the transformer<br />

nominal current is 61.5 A, and the peak value of the exciting current is 57.3 A.<br />

Table 3.8.1 shows the most significant harmonics of the current signal depicted in Figure 3.8.3.<br />

Harmonics are expressed as a percentage of the fundamental component. The third harmonic is the most<br />

suitable for detecting overexcitation conditions, but either the delta connection of the CTs or the deltaconnection<br />

compensation of the differential relay filters out this harmonic. The fifth harmonic, however,<br />

is still a reliable quantity for detecting overexcitation conditions.<br />

3<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

FIGURE 3.8.4 Harmonic content of transformer exciting current as a function of the applied voltage. (From Cooper<br />

<strong>Power</strong> Systems, <strong>Electric</strong> <strong>Power</strong> System Harmonics: Design Guide, Cooper <strong>Power</strong> Systems, Bulletin 87011, Franksville,<br />

WI, 1990. With permission.)<br />

Einval and Linders [13] were the first to propose using the fifth harmonic to restrain the transformer<br />

differential relay. They recommended setting this restraint function at 35% of fifth harmonic with respect<br />

to the fundamental. Figure 3.8.4 [25] shows the harmonic content of the excitation current of a power<br />

transformer as a function of the applied voltage. As the voltage increases, saturation and the exciting<br />

current increase. The odd harmonics, expressed as a percentage of the fundamental, first increase and<br />

then begin to decrease at overvoltages on the order of 115 to 120%. Setting the differential-relay fifthharmonic<br />

restraint to 35% ensures security for overvoltage conditions less than 140%. For greater<br />

overvoltages, which could quickly destroy the transformer in a few seconds, it is desirable to have the<br />

differential-relay fast tripping added to that of the transformer-overexcitation relay.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!