06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

FIGURE 3.7.9 Control block diagram, paralleling by usual circulating-current method.<br />

3.7.8.3 Negative Reactance Method<br />

The negative reactance method (<strong>Harlow</strong>, 2002) has a very distinct advantage over all others: it involves<br />

no supplemental apparatus beyond the basic LTC control. It also involves no wiring between controls,<br />

and it is very f<strong>org</strong>iving of mismatched transformers, including the built-in instrument transformers. It<br />

fell from favor about 50 years ago because of an inherent inaccuracy in its operation. The error, in the<br />

all-important voltage-regulation function, is a function of the power factor of the load. If the load power<br />

factor changes from about 1.0 to 0.7 lag, there will be a maximum error of perhaps ±1.5 V (3 V total<br />

swing) in the regulated voltage. This, coupled with the overall inaccuracy of controls of 50 years past<br />

(the standard of the day allowed up to 5% error!), apparently made for an intolerable condition.<br />

Today’s controls are far superior in accuracy, and the power system typically operates at a much<br />

improved and consistent power factor. These two points combine to afford an order-of-magnitude<br />

improvement in the operating accuracy of the technique. The technique is little known in the industry,<br />

perhaps to the detriment of many who would find applications to benefit from the procedure.<br />

3.7.9 Characteristics Important for LTC <strong>Transformer</strong> Paralleling<br />

There are many transformer characteristics that must be known and evaluated when it is planned to<br />

parallel LTC transformers. Some of the more notable follow:<br />

1. Impedance and MVA. “Impedance” as a criterion for paralleling is more correctly stated as the<br />

percent impedance referred to a common MVA base. Two transformers of 10% impedance —one<br />

of 10 MVA and the other of 15 MVA — are not the same. Two other transformers, one 10%<br />

impedance and 10 MVA and another of 15% impedance and 15 MVA, are suitably matched per<br />

this criterion. There is no definitive difference in the impedances that will be the limit of acceptability,<br />

but a difference of no greater than 7.5% is realistic.<br />

2. Voltage rating and turns ratio. It may not be essential that the voltage ratings and turns ratios be<br />

identical. If one transformer is 69–13.8 kV and the other 69–12.47 kV, the difference may be<br />

tolerated by recognizing and accepting a fixed-step tap discrepancy, or it may be that the ratios<br />

can be made more nearly the same using the de-energized tap changers.<br />

3. Winding configuration. The winding configuration, as delta–wye, wye–wye, etc., is critical, yet<br />

transformers of different configurations can be paralleled if care is taken to ensure that the phase<br />

shift through the transformers is the same.<br />

4. Instrument transformers. The transformers must have VTs and CTs that produce in-phase signals<br />

of the correct ratio to the control, and they must be measuring the same phase in the different<br />

transformers.<br />

3.7.10 Paralleling <strong>Transformer</strong>s with Mismatched Impedance<br />

Very often it is desired to use two existing transformers in parallel, even when it is recognized that the<br />

impedance mismatch is greater than that recommended for proper operation. This can usually be<br />

accomplished, although some capacity of one transformer will be sacrificed.<br />

If the impedances of the transformers in parallel are not equal, the current divides inversely with the<br />

impedances so that the same voltage appears across both impedances. The impedances — effectively the<br />

transformer impedance as read from the nameplate — can be taken to be wholly reactive. The problem<br />

when dealing with mismatched transformers in parallel is that while the current divides per the impedances,<br />

the control — if operating using the conventional circulating-current method — is attempting to<br />

match the currents.<br />

Realize that the LTC control and the associated paralleling equipment really have no knowledge of the<br />

actual line current. They know only a current on its scaled base, which could represent anything from<br />

100 to 3000 A. The objective of the special considerations to permit the mismatched-impedance transformers<br />

to be paralleled is to supply equal current signals to the controls when the transformers are<br />

carrying load current in inverse proportion to their impedances.<br />

To illustrate, consider the paralleling of two 20-MVA transformers of 9% and 11% impedance, which<br />

is much more than the 7.5% difference criterion stated earlier. We establish that Z 1 = k Z 2 , so:<br />

And since I 1 = I 2 /k:<br />

k = Z 1 /Z 2 = 9/11 = 0.818<br />

I 1 = I 2 /k = 1.222 I 2<br />

<strong>Transformer</strong> T1 will carry 22.2% more load than transformer T2, even though they are of the same<br />

MVA rating. A resolution is to fool the controls to act as though the current is balanced when, in fact,<br />

it is mismatched by 22%. A solution is found by placing a special ratio auxiliary CT in the control-current<br />

path of T2 that boosts its current by 22%. This will cause both controls to see the same current when,<br />

in fact, T1 is carrying 22% more current. In this way, the controls are fooled into thinking that the load<br />

is balanced when it is actually unbalanced due to the impedance mismatch. <strong>Transformer</strong> T2 has effectively<br />

been derated by 22% in order to have the percent impedances match.<br />

The circulating-current paralleling described here is commonly used in the U.S. Another basis for<br />

implementing circulating-current paralleling is now available. The new scheme does not require the<br />

breakout of the circulating current and the load current from the total transformer current. Rather, the<br />

procedure is to recognize the apparent power factors as seen by the transformers and then act so as to<br />

make the power factors be equal. The control configuration used is that of Figure 3.7.10, where the phasor<br />

diagram, Figure 3.7.11, shows typical loading for mismatched transformers. The fundamental difference<br />

in this manner of circulating-current paralleling is that the principle involves the equalization of the<br />

apparent power factors as seen by the transformers, i.e., the control acts to make 1 2. The benefit<br />

of this subtle difference is that it is more amenable to use where the transformers exhibit mismatched<br />

impedance.<br />

References<br />

American National Standard for <strong>Transformer</strong>s 230 kV and Below 833/958 through 8333/10417 kVA,<br />

Single-Phase; and 750/862 through 60000/80000/100000 kVA, Three-Phase without Load Tap<br />

Changing; and 3750/4687 through 60000/80000/100000 kVA with Load Tap Changing, ANSI<br />

Standard C57.12.10, National <strong>Electric</strong>al Manufacturers Association, Rosslyn, VA, 1998.<br />

Beckwith <strong>Electric</strong> Co., Basic Considerations for the Application of LTC <strong>Transformer</strong>s and Associated<br />

Controls, Application Note 17, Beckwith <strong>Electric</strong>, Largo, FL, 1995.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!