06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

FIGURE 3.7.3 Control for voltage regulation of the bus.<br />

FIGURE 3.7.2 Phasing of voltage and current inputs.<br />

3.7.4 The Need for Voltage Regulation<br />

Referring to the circuits of Figure 3.7.1, note that system conditions will change over time, with the result<br />

that the voltage at the substation bus, and as delivered to the load, will change. From Figure 3.7.1, the<br />

source voltage, the source impedance, and the load conditions will be expected to change with time. The<br />

most notable of these, the load, must be recognized to consist of two factors — the magnitude and the<br />

power factor, or what is the same point, the real (watt) and reactive (var) components.<br />

3.7.4.1 Regulation of the Voltage at the Bus<br />

Many times, the object of the LTC is simply to hold the substation bus voltage at the desired level. If this<br />

is the sole objective, it is sufficient to bring only a VT signal that is representative of the bus voltage into<br />

the control. The secondary of the VT is usually 120 V at the nominal bus voltage, but other VT secondary<br />

voltages, especially 125 V, 115 V and 110 V, are used. Figure 3.7.3 shows the circuit. The figure shows a<br />

motor (M) on the LTC, which is driven in either the raise or lower direction by the appropriate output<br />

(M R or M L ) of the control. This first control, Figure 3.7.3, is provided with only three settings, these being<br />

those required for the objective of regulating the substation secondary-bus voltage:<br />

3.7.4.1.1 Voltage Set Point<br />

The voltage set point on the control voltage base, e.g., 120 V, is the voltage desired to be held at the load.<br />

(The load location for this first case is the substation secondary bus because line-drop compensation is<br />

not yet considered and is therefore zero.) This characteristic is also commonly referred to as “voltage<br />

band center,” this being illustrative of the point that there is a band of acceptable voltage and that this<br />

is the midpoint of that band. If line-drop compensation (LDC, as detailed later) is not used, the set point<br />

will often be somewhat higher than 120 V, perhaps 123 V to 125 V; with use of LDC the setting will be<br />

lower, perhaps 118 V.<br />

3.7.4.1.2 Bandwidth<br />

The bandwidth describes the voltage range, or band, that is considered acceptable, i.e., in which there is<br />

not a need for any LTC corrective action. The bandwidth is defined in the ANSI/IEEE C57.15 standard<br />

as a voltage with one-half of the value above and one-half below the voltage set point. Some other controls<br />

adjust the bandwidth as a percentage of the voltage set point, and the value represents the band on each<br />

side of the band center. The bandwidth voltage selected is basically determined by the LTC voltage change<br />

per step. Consider a transformer where the voltage change per step is nominally 0.75 V (5/8% of 120 V).<br />

Often this is only the average; the actual voltage change per step can differ appreciably at different steps.<br />

Clearly, the bandwidth must be somewhat greater than the maximum step-change voltage, because if the<br />

bandwidth were less than the voltage change per step, the voltage could pass fully across the band with<br />

a single step, causing a severe hunting condition. The minimum suggested bandwidth setting is twice<br />

the nominal step-change voltage, plus 0.5 V, for a 2.0-V minimum setting for the most common 5/8%<br />

systems. Many users choose somewhat higher bandwidths when the voltage is not critical and there is a<br />

desire to reduce the number of daily tap changes.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!