[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
FIGURE 3.6.18 Current, voltage, and apparent resistance with time.<br />
some low-current distribution transformer windings where the dc current can be significant compared<br />
with the rated current. It is more likely that errors will occur because of meter readings taken before core<br />
saturation is achieved. The process involved in core saturation is described below.<br />
Compared with the exponential current-vs.-time relationship for the R-L circuit with constant R and<br />
constant L, the current in a transformer winding, when a dc voltage is first applied, rises slowly. The slow<br />
rate of rise comes about because of the high initial impedance of the winding. The initially high impedance<br />
results from the large effective inductance of the winding with its iron core. As the current slowly increases,<br />
the flux density in the core slowly rises until the core begins to saturate. At this point, the winding no<br />
longer behaves like an iron-core coil and instead behaves like an air-core coil, with relatively low inductance.<br />
The rate of rise of the current increases for a period as the core saturates; then the current levels<br />
off at a steady-state value. Typical shapes for the voltage, current, and apparent resistance are shown in<br />
Figure 3.6.18. The magnitude of the dc voltage affects the rate at which flux builds up in the core, since<br />
V = N(d/dt). The higher the magnitude of the dc voltage, the shorter is the time to saturation because<br />
of a higher value for d/dt. At the same time, though, the coil must be able to provide the required<br />
magnetomotive force in ampere turns, N I, needed to force the core into saturation, which leads to a<br />
minimum value for the dc current. Of course, there is an upper limit to the value for dc current, namely<br />
the point at which conductor heating would disturb the resistance measurement.<br />
Note the time scale of the graph in Figure 3.6.18. It is very important that the steady-state dc current<br />
be attained before meter readings are taken. If this is not done, errors in excess of 20% are easily realized.<br />
3.6.6.3.5 Winding Resistance and Average Winding Temperature<br />
Two of the three purposes listed above for measuring the dc resistance of a transformer winding inherently<br />
involve a concomitant measurement of temperature. When measuring resistance for the purpose of<br />
calculating I 2 R at a given temperature, the I 2 R value obtained will be used to determine the load-loss<br />
value at a different temperature. When the winding resistance is measured before and during a heat run,<br />
the determination of average winding temperature at the end of a heat run test requires knowledge of<br />
winding resistance at two temperatures.<br />
The winding dc resistance at two temperatures, T1 and T2, will have values of R1 and R2, respectively,<br />
at the two temperatures. The functional relationship between winding resistance and average temperature<br />
is shown in Equation 3.6.4:<br />
R1<br />
T1<br />
Tk<br />
<br />
R2<br />
T2<br />
T<br />
k<br />
(3.6.4)<br />
where<br />
R1 is the value of winding resistance, corresponding to average winding temperature of T1<br />
R2 is the value of winding resistance, corresponding to average winding temperature of T2<br />
T k is 234.5C for copper, 225C for aluminum<br />
Correction of load loss for temperature is covered in section 3.6.6.2. Determination of average winding<br />
temperature in a heat run test is covered in section 3.6.6.4.<br />
3.6.6.4 Heat Run Tests<br />
3.6.6.4.1 Purpose of Heat Run Tests<br />
The maximum allowable average and hottest-spot temperature rises of the windings over ambient<br />
temperature and the maximum allowable temperature rise of the top oil of the transformer are specified<br />
by ANSI and IEEE standards and are guaranteed by the manufacturer. The purpose of temperature-rise<br />
tests is to demonstrate that the transformer will deliver rated load without exceeding the guaranteed<br />
values of the temperature rises of the windings and oil. According to the ANSI and IEEE standards, these<br />
tests are performed at the minimum and maximum load ratings of a transformer.<br />
3.6.6.4.2 Test Methods<br />
For factory testing, it is not practical to connect the transformer to a load impedance with full rated<br />
secondary voltage applied to the simulated load. Although this would most directly simulate service<br />
conditions, most of the total test input power would dissipate in the load impedance. The load power,<br />
which equals the load rating of the transformer, is much larger than the sum of no-load and load losses<br />
that dissipate in the transformer. The electrical heating of the load would not contribute to transformer<br />
heating. <strong>Electric</strong> power consumption for the test would be excessive, and the test would not be practical<br />
for routine testing.<br />
In factory tests according to methods specified in the ANSI and IEEE standards, several artificial loading<br />
schemes can be used to simulate heat dissipation caused by the load and no-load losses of the transformer.<br />
The back-to-back loading method, described in the IEEE test code [2], requires two identical transformers<br />
and is often used for heat runs of distribution transformers. For power transformers, it is most common<br />
to use the short-circuit loading method, as specified in the IEEE test code [2]. The test setup is similar<br />
to that used for measurement of load loss and impedance voltage. One winding is connected to a short<br />
circuit, and sufficient voltage is applied to the other winding to result in currents in both windings that<br />
generate the required power loss to heat the oil and windings.<br />
3.6.6.4.3 Determination of the Top, Bottom, and Average Oil Rises<br />
This discussion applies to the short-circuit loading method. Initially, the test current is adjusted to provide<br />
an input power loss equal to the no-load loss plus the load loss. This can be called the total loss. The<br />
total loss is corrected to the guaranteed temperature rise plus ambient temperature. During this portion<br />
of the heat run, the windings provide a heat source for the oil and the oil cooling system. The winding<br />
temperatures will be higher than expected because higher-than-rated currents are applied to the windings,<br />
but here only the oil temperature rises are being determined. For an oil-filled power transformer, the<br />
total power loss for a given rating is maintained until the top-oil temperature rise is stabilized. Stabilization<br />
is defined as no more than 1C change in three consecutive 1-h periods.<br />
After stabilization is achieved, the top- and bottom-oil readings are used to determine the top, bottom,<br />
and average oil temperature rises over ambient at the specified load.<br />
3.6.6.4.4 Determination of the Average Winding-Temperature Rise<br />
After the top, bottom, and average oil temperature rises are determined, the currents in the windings are<br />
reduced to rated value for a period of 1 h. Immediately following this 1-h period, the ac power leads are<br />
disconnected, and resistance measurements are carried out on both windings. The total time from<br />
disconnection of power and the first resistance readings should be as short as possible, typically less than<br />
2 min — certainly not more than 4 min. Repeated measurements of winding resistance are carried out<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC