06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

FIGURE 3.6.17 Circuit for measuring winding resistance.<br />

FIGURE 3.6.15 Test circuit for load-loss measurement.<br />

FIGURE 3.6.16 Equivalent circuit and phasor diagram for load-loss test.<br />

recently been developed by a working group of the IEEE PES <strong>Transformer</strong>s Committee. When generally<br />

available, it will provide a complete background and the basis for carrying out measurements and<br />

calibrations to ensure accurate values of reported losses as required by ANSI and IEEE standards [1].<br />

Because the magnitudes of load losses and impedance depend upon the tap positions of the deenergized<br />

tap changer (DETC) and the load tap changer (LTC), if present, load-loss and impedancevoltage<br />

measurements are usually carried out in the rated voltage connection and at the tap extremes. If<br />

the transformer under test has multiple MVA ratings that depend on the type of cooling, the tests are<br />

normally carried out at all ratings.<br />

3.6.6.3 Winding Resistance Measurements<br />

3.6.6.3.1 Purpose of Winding Resistance Measurements<br />

Measurements of dc winding resistance are of fundamental importance because they form the basis for<br />

determining the following:<br />

Resistance measurements, taken at known temperatures, are used in the calculation of winding conductor<br />

I 2 R losses. The I 2 R losses at known temperatures are used to correct the measured load<br />

losses to a standard reference temperature. Correction of load losses is discussed in section 3.6.6.2.<br />

Resistance measurements, taken at known temperatures, provide the basis to determine the temperature<br />

of the same winding at a later time by measuring the resistance again. From the change in<br />

resistance, the change in temperature can be deduced. This measurement is employed to determine<br />

average winding temperatures at the end of heat run tests. Taking resistance measurements after<br />

a heat run test is discussed in section 3.6.6.4.<br />

Resistance measurements across the transformer terminals provide an assessment of the quality of<br />

internal connections made to the transformer windings. Loose or defective connections are indicated<br />

by unusually high or unstable resistance readings.<br />

3.6.6.3.2 Nature of the Quantity Being Measured<br />

The dc winding resistance differs from the value of resistance indicated for the resistor shown in Figure<br />

3.6.16 or the resistors that appear in textbook illustrations of the PI or T equivalent circuits of transformers<br />

to represent the resistance of the windings. The resistors in the equivalent circuits include the effects of<br />

winding I 2 R loss, eddy loss in the windings, stray losses in structural parts, and circulating currents in<br />

parallel conductors — namely, they represent the resistive components of the load loss. The resistors<br />

shown in the equivalent circuits can be thought of as representing an equivalent ac resistance of the<br />

windings. The dc resistance of the windings is a different quantity, one that is relevant for calculating<br />

I 2 R, for determining average winding temperature, and for evaluating electrical connections.<br />

3.6.6.3.3 How Winding-Resistance Measurements Are Made<br />

The measurement of power transformer winding resistance is normally done using the voltmeter-ammeter<br />

method or using a ratiometric method to display the voltage–current ratio directly. A circuit for the<br />

measurement of winding resistance is shown in Figure 3.6.17. A dc source is used to establish the flow<br />

of steady direct current in the transformer winding to be measured. After the R-L transient has subsided,<br />

simultaneous readings are taken of the voltage across the winding and the current through the winding.<br />

The resistance of the winding is determined from these readings based on Ohm’s law.<br />

3.6.6.3.4 Discussion of the Measurement Process<br />

If a dc voltage is applied as a step to a series R-L circuit, the current will rise exponentially with a time<br />

constant of L/R. This is familiar for the case where both resistance and inductance remain constant<br />

during the transient period. For a transformer winding, however, it is possible for the true resistance,<br />

the apparent resistance, and the inductance of the winding to change with time. The true resistance may<br />

change if the direct current is of high-enough magnitude and is applied long enough to heat the winding<br />

substantially, thereby changing its resistance during the measurement. The inductance changes with time<br />

because of the nonlinear B-H curve of the core steel and varies in accordance with the slope of the coresteel<br />

saturation curve. In addition, there is an apparent resistance, Ra, during the transient period.<br />

V<br />

Ra R<br />

L dI<br />

<br />

(3.6.3)<br />

I I dt<br />

Note that the apparent resistance, Ra, is higher than the true resistance, R, during the transient period<br />

and that the apparent resistance derived from the voltmeter and ammeter readings equals the true<br />

resistance only after the transient has subsided.<br />

Resistance measurement error due to heating of the winding conductor is usually not a problem in<br />

testing transformers, but the possibility of this effect should be taken into consideration, especially for<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!