06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

voltage of the excited winding, readings are taken of the rms current, the rms voltage, and the no-load<br />

power. The ratio of the measured rms current to the rated load current of the excited winding, expressed<br />

in percent, is commonly referred to as the percent excitation current. The measured no-load loss is<br />

corrected to a sine-wave basis by a formula given in the IEEE test code [2], using the readings of the two<br />

voltmeters. The correction is shown below. The corrected value is reported as the no-load loss of the<br />

transformer.<br />

Pm<br />

Pc<br />

<br />

Vr<br />

P 2<br />

<br />

1 P<br />

V<br />

2<br />

<br />

(3.6.1)<br />

where<br />

P c is the corrected (reported) value of no-load loss<br />

P m is the measured value of no-load loss<br />

V a is the reading of the average-responding, rms-calibrated voltmeter<br />

V r is the reading of the true-rms-responding voltmeter<br />

P1 and P2 are the per-unit hysteresis and per-unit eddy-current losses, respectively<br />

According to the IEEE test code [2], if the actual values of P1 and P2 are not available, it is suggested<br />

that the two loss components be assumed equal in value, assigning each a value of 0.5 p.u.<br />

3.6.6.2 Load Loss and Impedance Measurements<br />

3.6.6.2.1 Purpose of Load Loss Measurements<br />

A transformer dissipates a load loss that depends upon the transformer load current. Load loss is a cost<br />

to the user during the lifetime of the transformer. Maximum values of the load loss of transformers at<br />

rated current are specified and often guaranteed by the manufacturer. Load-loss measurements are made<br />

to verify that the load loss does not exceed the specified or guaranteed value.<br />

3.6.6.2.2 Nature of the Quantity Being Measured<br />

The magnitude of the load loss is a function of the transformer load current. Its magnitude is zero when<br />

there is no load on the transformer. Load loss is always given for a specified transformer load, usually at<br />

rated load. <strong>Transformer</strong> load loss, often called copper loss or winding loss, includes I 2 R losses due to<br />

load current in the winding conductors and stray losses in various metallic transformer parts due to eddy<br />

currents induced by leakage fields. Stray losses are produced in the winding conductors, in core clamps,<br />

in metallic structural parts, in magnetic shields, and in tank walls due to the presence of leakage fields.<br />

Stray losses also include power loss due to circulating currents in parallel windings and in parallel<br />

conductors within windings.<br />

Because winding resistance varies with conductor temperature, and because the resistivities of the<br />

structural parts producing stray losses vary with temperature, the transformer load losses are a function<br />

of temperature. For this reason, a standard reference temperature (usually 85C) for reporting the load<br />

loss is established in ANSI and IEEE standards [1]. To correct the load-loss measurements from the<br />

temperature at which they are measured to the standard reference temperature, a correction formula is<br />

provided in the IEEE test code [2]. This correction involves the calculation of winding I 2 R losses, where<br />

I is the rated current of the winding in amperes, and R is the measured dc resistance of the winding. The<br />

I 2 R losses and the stray losses are separately corrected and combined in the formula given in the standard.<br />

The measurement of the dc winding resistance, R, is covered in Section 3.6.6.3. Stray losses are determined<br />

by subtracting the I 2 R losses from the measured total load losses. All of this is covered in detail in the<br />

IEEE test code [2]. The formula for this conversion is stated in general in Equation 3.6.2:<br />

W<br />

LL<br />

2 2 2 2<br />

( I<br />

pRp IsRs)( Tk Tr)<br />

( WmI pRp IsRs)( Tk Tm)<br />

<br />

<br />

( T T )<br />

( T T )<br />

k<br />

m<br />

a<br />

k<br />

r<br />

(3.6.2)<br />

where<br />

T r is the reference temperature (C)<br />

T m is the temperature at which the load loss is measured (C)<br />

W m is the load loss (W) as measured at temperature T m (C)<br />

W LL is the load loss (W) corrected to a reference temperature T r (C)<br />

T k is a winding material constant: 234.5 for copper, 225 for aluminum<br />

R p and R s are, respectively, the primary and secondary resistances ()<br />

I p and I s are the primary and secondary rated currents (A)<br />

It can be seen from Equation 3.6.2 that the measurement of load losses and correction to the reference<br />

temperature involves the measurement of five separate quantities:<br />

1. <strong>Electric</strong> power (the load loss as measured)<br />

2. Temperature (the temperature at time of test)<br />

3. Resistance of the primary winding (at a known temperature)<br />

4. Resistance of the secondary winding (at a known temperature)<br />

5. <strong>Electric</strong> current (needed to adjust the current to the required values)<br />

Another characteristic of transformer load loss is its low power factor. Most often, when considering<br />

electric-power measurement applications, the power factor of the load being measured is relatively high,<br />

usually exceeding 80%. For large modern power transformers, the power factor can be very low, in the<br />

range from 1 to 5%. The measurement of electric power at very low power factor requires special<br />

consideration, as discussed in the next section.<br />

3.6.6.2.3 How Load Loss Is Measured<br />

Load losses are normally measured by connecting one winding, usually the low-voltage winding, to a<br />

short circuit with adequately sized shorting bars and connecting the other winding, usually the highvoltage<br />

winding, to a power-frequency voltage source. The source voltage is adjusted until the impressed<br />

voltage causes rated current to flow in both windings. Input rms voltage, rms current, and electric power<br />

are then measured. Figure 3.6.15 shows a circuit commonly used for measurement of load losses of a<br />

single-phase transformer. Three-phase measurement is carried out in the same way but with three sets<br />

of instruments and instrument transformers. Precision scaling devices are usually required because of<br />

the high magnitudes of current, voltage, and power involved.<br />

The applied test voltage when the transformer is connected as in Figure 3.6.15, with rated currents in<br />

the windings, is equal to the impedance voltage of the transformer. Hence impedance, or impedance<br />

voltage, is also measured during the load-loss test. The ratio of the measured voltage to the rated voltage<br />

of the winding, multiplied by 100, is the percent impedance voltage of the transformer. This quantity is<br />

commonly called “percent impedance” or, simply, “impedance.”<br />

3.6.6.2.4 Discussion of the Measurement Process<br />

The equivalent circuit of the transformer being tested in the load-loss test and the phasor diagram of<br />

test voltage and current during the test are shown in Figure 3.6.16. The load-loss power factor for the<br />

load-loss test is cos = E R /E Z . Because the transformer leakage impedance, consisting of R and X in<br />

Figure 3.6.16, is mainly reactive, and more so the larger the transformer, the power factor during the<br />

load-loss test is very low. In addition, there is a trend in modern transformers to create designs with<br />

lower losses due to increased demands for improved efficiency and transformer load-loss evaluations for<br />

optimal life-cycle costs. <strong>Transformer</strong> designs for low values of load loss lead to reductions in the equivalent<br />

resistance shown in Figure 3.6.16, and hence to low values for the quantity, E R , which translates to lower<br />

values for the load-loss power factor in modern transformers. In fact the load-loss power factors for large<br />

modern transformers are often very low, in the range from 0.01 to 0.05 per unit. Under circuit conditions<br />

with very low power factor, the accurate measurement of electric power requires special scaling devices<br />

having very low phase-angle error and power measuring instruments having high accuracy at low power<br />

factor. In addition to the IEEE test code [2], a <strong>Transformer</strong> Loss Measurement Guide, C57.123, has<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!