06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

3.6.6.1.2 Nature of the Quantity Being Measured<br />

<strong>Transformer</strong> no-load loss, often called core loss or iron loss, is the power loss in a transformer excited<br />

at rated voltage and frequency but not supplying load. The no-load loss comprises three components:<br />

1. Core loss in the core material<br />

2. Dielectric loss in the insulation system<br />

3. I 2 R loss due to excitation current in the energized winding<br />

FIGURE 3.6.13 Test circuit for partial-discharge measurement during the induced-voltage test.<br />

• The magnitude of partial discharge activity does not exceed 100 V (500 pC).<br />

• After the PD level has stabilized, any increase in partial discharge activity does not exceed 30 V<br />

(150 pC).<br />

• The partial discharge levels during the 1-h period do not show an increasing trend.<br />

• There is no sustained increase in partial discharge level during the last 20 min of the test.<br />

The test circuit for PD measurement during the induced-voltage test is shown in Figure 3.6.13. The<br />

bushing capacitance tap is connected to a coupling impedance unit, which provides PD signals to the<br />

PD detection unit. Methods for measurement and calibration are described in detail in the IEEE test<br />

code [2] and in the IEEE partial discharge measurement guide [5].<br />

If there is significant level of PD activity during the test, it is desirable to identify the location of the<br />

PD source inside the transformer so that the problem can be corrected. This will ensure PD-free operation.<br />

Methods for location of PD sources inside the transformer often are based on triangulation. Ultrasonic<br />

acoustic waves arriving at transformer tank surfaces due to PD activity are monitored at various locations<br />

on the tank walls. Knowing wave propagation velocities and travel paths, it is possible to locate sources<br />

of PD activity with reasonable accuracy.<br />

The no-load loss of a transformer is primarily caused by losses in the core steel (item 1, above).<br />

The remaining two sources are sometimes ignored. As a result, the terms no-load loss, core loss, and<br />

iron loss are often used interchangeably. Core loss and iron loss, strictly speaking, refer only to the<br />

power loss that appears within the core material. The following discussion on no-load loss, or core<br />

loss, will explain why the average-voltage voltmeter method, to be described later, is recommended.<br />

The magnitude of no-load loss is a function of the magnitude, frequency, and waveform of the<br />

impressed voltage. These variables affect the magnitude and shape of the core magnetic flux waveform<br />

and hence affect the value of the core loss. It has been verified through measurements on power and<br />

distribution transformers that core loss also depends, to some extent, upon the temperature of the<br />

core. According to the IEEE test code [2], the approximate rate of change of no-load loss with core<br />

temperature is 0.00065 per-unit core loss increase for each C reduction in core temperature. The two<br />

main components of the core loss are hysteresis loss and eddy-current loss. The change in eddy-current<br />

loss, due to a change in the resistivity of the core steel as temperature changes, appears to be one factor<br />

that contributes to the observed core-loss temperature effect. The hysteresis loss magnitude is a<br />

function of the peak flux density in the core-flux waveform. When the impressed voltage waveform is<br />

distorted (not a pure sine wave), the resulting peak flux density in the flux waveform depends on the<br />

average absolute value of the impressed voltage wave. Eddy-current loss is a function of the frequency<br />

of the power source and the thickness of the core-steel laminations. Eddy loss is strongly influenced<br />

by harmonics in the impressed voltage. The IEEE transformer test code [2] recommends the averagevoltage<br />

voltmeter method, to be described below, for measuring no-load loss.<br />

3.6.6.1.3 How No-Load Loss Is Measured<br />

The measurement of no-load loss, according to the average-voltage voltmeter method, is illustrated in<br />

Figure 3.6.14. Voltage and current transformers are required to scale the inputs for voltmeters, ammeters,<br />

and wattmeters. Three-phase no-load-loss measurements are carried out the same way, except that three<br />

sets of instruments and instrument transformers are utilized. The test involves raising voltage on one<br />

winding, usually the low-voltage winding, to its rated voltage while the other windings are in open circuit.<br />

Two voltmeters connected in parallel are employed. The voltmeter labeled V a in Figure 3.6.14 represents<br />

an average-responding, rms-calibrated voltmeter. The voltmeter labeled V r represents a true rms-responding<br />

voltmeter. Harmonics in the impressed voltage will cause the rms value of the waveform to be different<br />

from the average-absolute (rms-scaled) value, and the two voltmeter readings will differ. When the voltage<br />

reading, as measured by the average-responding voltmeter, reaches a value corresponding to the rated<br />

3.6.6 Performance Characteristics<br />

3.6.6.1 No-Load Loss and Excitation-Current Measurements<br />

3.6.6.1.1 Purpose of No-Load Loss Measurements<br />

A transformer dissipates a constant no-load loss as long as it is energized at constant voltage, 24 hours<br />

a day, for all conditions of loading. This power loss represents a cost to the user during the lifetime of<br />

the transformer. Maximum values of the no-load loss of transformers are specified and often guaranteed<br />

by the manufacturer. No-load-loss measurements are made to verify that the no-load loss does not exceed<br />

the specified or guaranteed value.<br />

FIGURE 3.6.14 Test circuit for no-load-loss measurement.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!