06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

FIGURE 3.6.8 Impulse-test setup.<br />

seen at the tested terminals of the transformer, causing a deviation in the test waveforms compared with<br />

the reference waveforms. The act of comparing the reduced full-wave records and the full-wave records<br />

is sometimes called “matching” the waves. If they are identical, the waves are said to be matched. Any<br />

differences in the waves, judged to be significant, are said to be mismatches. If there are mismatches,<br />

something is not correct, either in the test setup or in the dielectric system of the transformer. Various<br />

waveforms of voltages and currents associated with different types of defects are presented in great detail<br />

in the IEEE impulse guide [4]. When digital recorders are employed, methods of waveform analysis using<br />

the frequency dependence of the transformer impedance, transformer transfer function, and other digital<br />

waveform-analysis tools are now being developed and used to aid failure detection. Measurements of the<br />

voltages and currents in various parts of the transformer under test can aid in location of dielectric<br />

defects. These schemes are summarized in Figure 3.6.9.<br />

3.6.5.1.3 Switching-Impulse Test<br />

Man-made transients, as opposed to nature-made transients, are often the result of switching operations<br />

in power systems. Switching surges are relatively slow impulses. They are characterized by a wave that:<br />

1. Rises to peak value in no less than 100 s<br />

2. Falls to zero voltage in no less than 1000 s<br />

3. Remains above 90% of peak value, before and after time of crest, for no less than 200 s<br />

This is shown in Figure 3.6.10. Generally, the crest value of the switching-impulse voltage is approximately<br />

83% of the BIL.<br />

Voltages of significant magnitude are induced in all windings due to core-flux buildup that results<br />

from the relatively long duration of the impressed voltage during the switching-impulse test. The induced<br />

voltages are approximately proportional to the turns ratios between windings. Depending upon the<br />

transformer construction, shell-form versus core-form, three-leg versus five-leg construction, etc., many<br />

connections for tests are possible. Test voltages at the required levels can be applied directly to the winding<br />

under test, or they can be induced in the winding under test by application of switching impulse voltage<br />

of suitable magnitude across another winding, taking into consideration the turns ratio between the two<br />

FIGURE 3.6.9 Impulse-current measurement locations.<br />

windings. The magnitudes of voltages between windings and between different phases depend on the<br />

connections. This is discussed in great detail in the IEEE impulse guide [4].<br />

Because of its long duration and high peak-voltage magnitude, application of switching impulses on<br />

windings can result in saturation of the transformer core. When saturation of the core occurs, the resulting<br />

waves exhibit faster-falling, shorter-duration tails. By reversing polarity of the applied voltages between<br />

successive shots, the effects of core saturation can be reduced. Failures during switching-impulse tests<br />

are readily visible on voltage wave oscillograms and are often accompanied by loud noises and external<br />

flashover.<br />

Switching-impulse tests are generally carried out with impulse generators having adequate energy<br />

capacity and appropriate wave-shaping resistors and loading capacitors.<br />

3.6.5.2 Low-Frequency Dielectric Tests<br />

3.6.5.2.1 Purpose of Low-Frequency Dielectric Tests<br />

When high-frequency impulse voltages are applied to transformer terminals, the stress distributions<br />

within the windings are not linear but depend on the inductances and capacitances of the windings. Also,<br />

the effects of oscillations penetrating the windings produce complex and changing voltage distributions.<br />

Low-frequency stresses that result from power-frequency overvoltage, on the other hand, result in stresses<br />

with a linear distribution along the winding. Because the insulation system is stressed differently at low<br />

frequency, a second set of tests is required to demonstrate dielectric withstand under power-frequency<br />

conditions. The low-frequency dielectric tests demonstrate that the power transformer insulation system<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!