06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Voltage and current symmetry with respect to the three lines is obtained only in the delta and zigzag<br />

connections. Delta-connected transformers do not introduce third harmonics or their multiples into the<br />

power lines. The third-harmonic-induced voltage components are 360 apart. They are therefore all in<br />

phase and cause a third-harmonic current to flow within the delta winding. This third-harmonic current<br />

acts as exciting current and causes a third-harmonic voltage to be induced in each winding that is in<br />

opposition to the third-harmonic component of voltage that was originally induced by the sinusoidal<br />

exciting current from the lines. As a result, the third harmonic is eliminated from the secondary voltage.<br />

Another advantage of the delta–delta connection, if composed of three single-phase transformers, is<br />

that one transformer can be removed and the remaining two phases operated at 86.6% of their rating<br />

in the open delta connection.<br />

The principle disadvantage of the delta–delta connection is that the neutral is not available. As a result,<br />

the phases cannot be grounded except at the corners. The insulation design is more costly because this<br />

type of three-phase transformer connection has higher ground voltages during system fault or transient<br />

voltages. Supplying an artificial neutral to the system with a grounding transformer can help to control<br />

these voltages. The delta-connection insulation costs increase with increasing voltage. Consequently, this<br />

type of connection is commonly limited to a maximum system voltage of 345 kV.<br />

Differences in the voltage ratio of the individual phases causes a circulating current in both the primary<br />

and secondary deltas that is limited only by the impedance of the units. Differences in the impedances<br />

of the individual phases also causes unequal load division among the phases. When a current is drawn<br />

from the terminals of one phase of the secondary, it flows in the windings of all three phases. The current<br />

among the phases divides inversely with the impedance of the parallel paths between the terminals.<br />

3.5.4.1.3 Delta–Wye and Wye–Delta Connections<br />

The delta–wye or wye–delta connections have fewer objectionable features than any other connections.<br />

In general, these combine most of the advantages of the wye–wye and delta–delta connections. Complete<br />

voltage and current symmetry is maintained by the presence of the delta. The exciting third-harmonic<br />

current circulates within the delta winding, and no third-harmonic voltage appears in the phase voltages<br />

on the wye side. The high-voltage windings can be connected wye, and the neutral can be brought out<br />

for grounding to minimize the cost of the insulation.<br />

Differences in magnetizing current, voltage ratio, or impedance between the single-phase units are<br />

adjusted by a small circulating current in the delta. All of these factors result in unbalanced phase voltages<br />

on the delta, which causes a current to circulate within the delta.<br />

If the primary windings of a four-wire, wye-connected secondary that is supplying unbalanced loads<br />

are connected in delta, the unbalanced loading can be readily accommodated. There will be unbalanced<br />

secondary voltages caused by the difference in the regulation in each phase, but this is usually insignificant.<br />

Although the delta–wye connection has most of the advantages of the wye–wye and delta–delta, it still<br />

has several disadvantages. This connection introduces a 30 phase shift between the primary and secondary<br />

windings that has to be matched for paralleling. A delta–wye bank cannot be operated with only<br />

two phases in an emergency. If the delta is on the primary side and should accidentally open, the unexcited<br />

leg on the wye side can resonate with the line capacitance.<br />

3.5.4.2 Multiwinding <strong>Transformer</strong>s<br />

<strong>Transformer</strong>s having more than two windings coupled to the same core are frequently used in power<br />

and distribution systems to interconnect three or more circuits with different voltages or to electrically<br />

isolate two or more secondary circuits. For these purposes, a multiwinding transformer is less costly and<br />

more efficient than an equivalent number of two winding transformers. The arrangement of windings<br />

can be varied to change the leakage reactance between winding pairs. In this way, the voltage regulation<br />

and the short-circuit requirements are optimized. The application of multiwinding transformers permits:<br />

• Interconnection of several power systems operating at different voltages<br />

• Use of a delta-connected stabilizing winding, which can also be used to supply external loads<br />

• Control of voltage regulation and reactive power<br />

• <strong>Electric</strong>al isolation of secondary circuits<br />

• Duplication of supply to a critical load<br />

• Connection for harmonic-filtering equipment<br />

• A source for auxiliary power at a substation<br />

Some of the problems with the use of multiwinding transformers are associated with the effect leakage<br />

impedance has on voltage regulation, short-circuit currents, and the division of load among the different<br />

circuits. All the windings are magnetically coupled to the leakage flux and are affected by the loading of<br />

the other windings. It is therefore essential to understand the leakage impedance behavior of this type<br />

of transformer to be able to calculate the voltage regulation of each winding and load sharing among<br />

the windings. For three-winding transformers, the leakage reactance between each pair of windings must<br />

be converted into a star-equivalent circuit. The impedance of each branch of the star circuit is calculated<br />

as follows:<br />

Z a = 0.5(Z ab + Z ca – Z bc ) (3.5.1)<br />

Z b = 0.5(Z bc + Z ab – Z ca ) (3.5.2)<br />

and<br />

Z c = 0.5(Z ca + Z bc – Z ab ) (3.5.3)<br />

where Z a , Z b , and Z c are the star-equivalent impedances in each branch, and Z ab , Z bc , and Z ca are the<br />

impedances as seen from the terminals between each pair of windings with the remaining winding left<br />

open circuit. The equivalent star-circuit reactances and resistances are determined in the same manner.<br />

The four-winding transformer coupled to the same core is not commonly used because of the interdependence<br />

of the voltage regulation of each winding to the loading on the other windings. The equivalent<br />

circuit for a four-winding transformer is much more complicated, involving a complex circuit of six<br />

different impedances.<br />

After the loading of each winding is determined, the voltage regulation and load sharing can be<br />

calculated for each impedance branch and between terminals of different windings. The currents in each<br />

winding during a system fault can also be calculated in a similar fashion.<br />

3.5.4.3 Autotransformers Connections<br />

It makes no difference whether the secondary voltage is obtained from another coil or from the primary<br />

turns. The same transformation ratio is obtained in either case. When the primary and secondary voltages<br />

are obtained from the same coil, schematically, the transformer is called an autotransformer. The performance<br />

of autotransformers is governed by the same fundamental considerations as for transformers<br />

with separate windings. The autotransformer not only requires less turns than the two-winding transformer;<br />

it also requires less conductor cross section in the common winding because it has to carry only<br />

the differential current between the primary and secondary. As a result, autotransformers deliver more<br />

external load than the internal-winding kVA ratings, depending on the voltage ratios of the primary and<br />

secondary voltages, as shown in Figure 3.5.3 and the following formula:<br />

Output/internal rating = V 1 /(V 1 – V 2 ) (3.5.4)<br />

where<br />

V 1 = voltage of the higher-voltage winding<br />

V 2 = voltage of the lower-voltage winding<br />

The internal rating, size, cost, excitation current, and efficiency of autotransformers are higher than<br />

in double-wound transformers. The greatest benefit of the autotransformer is achieved when the primary<br />

and secondary voltages are close to each other.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!