06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3.2.5.2 Bushing Current <strong>Transformer</strong> Pockets<br />

The bushing flange creates a very convenient site to locate bushing current transformers (BCTs). The<br />

flange is extended on its inner end, and the BCTs, having 500 to 5000 turns in the windings, are placed<br />

around the flange. This location is called the BCT pocket and is shown in Figure 3.2.2. In this case, the<br />

bushing central conductor forms the single-turn primary of the BCT, and the turns in the windings form<br />

the secondary. Bushings built with standard dimensions have standard lengths for the BCT pocket [6].<br />

3.2.5.3 Lower Support/Lower Terminal<br />

Bushings that do not use draw-through leads, described in Section 3.2.7.3, must have a lower terminal<br />

in order to connect to the transformer winding or the circuit-breaker internal mechanism. This terminal<br />

can be one of any number of shapes, e.g., a smooth stud, threaded stud, spade, tang, or simply a flat<br />

surface with tapped holes for an additional terminal to be attached. Standards [6] prescribe several of<br />

these for various sizes of bushings.<br />

One lower terminal specified by standards for bushings with voltage ratings 115 through 230 kV<br />

incorporates the lower-support function of the bushing with the lower terminal. The lower support is<br />

an integral part of the second type of clamping system (compression) described above, and in this<br />

function, it helps create the required forces for compressing the seals. The lower surface of the flat support<br />

has tapped holes in it so that the desired lower terminal can be attached. Two lower terminals specified<br />

by standards have a spherical radius of 102 mm (4.0 in.) machined into their bottom surfaces. This<br />

spherical radius enables the use of an additional lower terminal with a suitably shaped matching surface<br />

to be attached via the tapped holes, but at a small angle with the bottom of the bushing. This feature is<br />

useful for attaching rigid leads that are not always perfectly true with respect to the placement of the<br />

bushing, or when bushings are mounted at a small angle from vertical.<br />

3.2.5.4 Lower-End Shield<br />

It can be seen from Figure 3.2.3 that all regions of the lower end of air-to-oil bushings experience high<br />

dielectric stresses. In particular, the areas near the corners of the lower support and terminal are very<br />

highly stressed. Therefore, electrostatic shields with large radii, such as the one shown in Figure 3.2.2<br />

and Figure 3.2.7, are attached to the lower end of these bushings in order to reduce the electric fields<br />

that appear in this area. Shields also serve the purpose of shielding the bolted connections used to connect<br />

the leads to the bushing. Since shields with a thin dielectric barrier are somewhat stronger dielectrically,<br />

crepe paper is wrapped, or molded pressboard is placed on, the outer surfaces of the shield.<br />

3.2.6 Bushings for Special Applications<br />

3.2.6.1 High-Altitude Applications<br />

Bushings intended for application at altitudes higher than 1000 m suffer from lower air density along<br />

the outer insulator. Standards [1] specify that, when indicated, the minimum insulation necessary at the<br />

required altitude can be determined by dividing the standard insulation length at 1000 m by the correction<br />

factor given in Table 3.2.2. For instance, suppose that the required length of the air insulator on a bushing<br />

is 2.5 m at 1000-m altitude. Further, suppose that this bushing is to be applied at 3000 m. Hence, the<br />

air insulator must be at least 2.5/0.8 = 3.125 m in length. The air insulator on the bushing designed for<br />

1000 m must be replaced with a 3.125-m-long insulator, but the remainder of the bushing, i.e., the central<br />

core and the oil insulator, will remain the same as the standard bushing because these parts are not<br />

affected by air insulation. These rules do not apply to altitudes higher than 4500 m.<br />

3.2.6.2 Highly Contaminated Environments<br />

Insulators exposed to pollution must have adequate creep distance, measured along the external contour<br />

of the insulator, to withstand the detrimental insulating effects of contamination on the insulator surface.<br />

Figure 3.2.2 shows the undulations on the weather sheds, and additional creep distance is obtained by<br />

adding undulations or increasing their depth. Recommendations for creep distance [8] are shown in<br />

Table 3.2.3 according to four different classifications of contamination.<br />

For example, a 345-kV bushing has a maximum line-to-ground voltage of 220 kV, so that the<br />

minimum creep is 220 28 = 6160 mm for a light contamination level and 220 44 = 9680 mm for<br />

a heavy contamination level. The term ESDD (equivalent salt-density deposit) used in Table 3.2.3 is<br />

TABLE 3.2.2 Dielectric-Strength Correction Factors for Altitudes<br />

Greater than 1000 m<br />

Altitude, m<br />

Altitude Correction Factor for Dielectric Strength<br />

1000 1.00<br />

1200 0.98<br />

1500 0.95<br />

1800 0.92<br />

2100 0.89<br />

2400 0.86<br />

2700 0.83<br />

3000 0.80<br />

3600 0.75<br />

4200 0.70<br />

4500 0.67<br />

Source: ANSI/IEEE, 1997 [1]. With permission.<br />

TABLE 3.2.3 Recommended Creep Distances for Four Contamination Levels<br />

Contamination Level<br />

Equivalent Salt-Deposit<br />

Density (ESDD), mg/cm 2<br />

Recommended Minimum Creep<br />

Distance, mm/kV<br />

Light 0.03–0.08 28<br />

Medium 0.08–0.25 35<br />

Heavy 0.25–0.6 44<br />

Extra heavy above 0.6 54<br />

FIGURE 3.2.7 Lower-end shield.<br />

Source: IEEE Std. C57.19.100-1995 (R1997) [8]. With permission.<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!