1.6 cm. This means that most of the current will flow in the region from the outer portion of the conductor<br />

and radially inward to a depth of the skin depth . Second, the losses generated within a conductor will be:<br />

P loss = I 2 R = I 2 L/A = 4I 2 L/(D 12 – D 02 ) (3.2.3)<br />

where<br />

I = rated current<br />

= resistivity of the conductor material, ohmm<br />

= 1.7241 10 –3 ohmm for copper with 100% IACS (international annealed copper standard)<br />

= 3.1347 10 –3 ohmm for electrical aluminum alloy with 55% IACS<br />

L = length of conductor, m<br />

A = cross section of conductor = (D 12 – D 02 )/4<br />

D 1 = outside diameter of conductor, m<br />

D 0 = D 1 – , m<br />

skin depth of the conductor in the case that a tubular conductor is used<br />

0.0127 m for copper, 0.0159 m for aluminum, both at 60-Hz frequency<br />

It can be seen from Equation 3.2.3 that P loss decreases as D 1 increases. Hence, design practice is to<br />

increase the outside diameter of the conductor for higher current ratings and to limit the wall thickness<br />

to near the skin depth. There are other technical advantages to increasing the outside conductor diameter:<br />

First, from Equation 3.2.2, observe that electric-field stress reduces as d = D 1 increases. Therefore, a larger<br />

diameter conductor will have higher partial-discharge inception and withstand voltages. Second, the<br />

mechanical strength of the conductor is dependent on the total cross-sectional area of the conductor, so<br />

that a larger diameter is sometimes used to achieve higher withstand forces in the conductor.<br />

FIGURE 3.2.4 Pressurized SF 6 gas bushing.<br />

rated through 345-kV system voltage, and partial-discharge limits as well as limits for power factor<br />

and capacitance change from before to after the standard electrical tests.<br />

3. IEEE Std. C57.19.03, Standard Requirements, Terminology and Test Procedures for Bushings for<br />

DC Applications [7]. This standard gives the same type of information as ANSI/IEEE Std.<br />

C57.19.00 for bushings for direct-current equipment, including oil-filled converter transformers<br />

and smoothing reactors. It also covers air-to-air dc bushings.<br />

4. IEEE Std. C57.19.100, Guide for Application of <strong>Power</strong> Apparatus Bushings [8]. This guide recommends<br />

practices to be used (1) for thermal loading above nameplate rating for bushings applied<br />

on power transformers and circuit breakers and (2) for bushings connected to isolated-phase bus.<br />

It also recommends practices for allowable cantilever loading caused by the pull of the line<br />

connected to the bushing, applications for contaminated environments and high altitudes, and<br />

maintenance practices.<br />

5. IEC Publication 137 [9], Bushings for Alternating Voltages above 1000 V. This standard is the IEC<br />

equivalent to the first standard listed above and is used widely in European and Asian countries.<br />

3.2.4 Important Design Parameters<br />

3.2.4.1 Conductor Size and Material<br />

The conductor diameter is determined primarily by the current rating. There are two factors at work<br />

here. First, the skin depth of copper material at 60 Hz is about 1.3 cm and that of aluminum is about<br />

3.2.4.2 Insulators<br />

Insulators must have sufficient length to withstand the steady-state and transient voltages that the bushing<br />

will experience. Adequate lengths depend on the insulating media in which the insulator is used and on<br />

whether the bushing is capacitively graded. In cases where there are two different insulating media on<br />

either side of an insulator, the medium with the inferior dielectric characteristics determines the length<br />

of the insulator.<br />

3.2.4.2.1 Air Insulators<br />

Primary factors that determine the required length of insulators used in air at atmospheric pressure are<br />

lightning-impulse voltage under dry conditions and power-frequency and switching-impulse voltages<br />

under wet conditions. Standard dry conditions are based on 760-mm (Hg) atmospheric pressure and<br />

20C, and wet conditions are discussed in Section 3.2.6.1, High-Altitude Applications.<br />

Bushings are normally designed to be adequate for altitudes up to 1000 m. Beyond 1000 m, longer<br />

insulators must be used to accommodate the lower air density at higher altitudes. Under clean conditions,<br />

air insulators for capacitively graded bushings are normally shorter in length than insulator housings<br />

without grading elements within them. However, as the insulator becomes more contaminated, the effects<br />

of grading elements disappear, and the withstand characteristics of graded and nongraded insulators<br />

become the same over the long term (15 to 30 min) [10]. Further guidance on this subject is given in<br />

Section 3.2.6.2, Highly Contaminated Environments.<br />

3.2.4.2.2 Oil Insulators<br />

Since mineral oil is dielectrically stronger than air, the length of insulators immersed in oil is typically<br />

30 to 40% the length of air insulators. In equipment having oil with low contamination levels, no sheds<br />

are required on oil-immersed insulators. In situations where some contamination exists in the oil, such<br />

as carbon particles in oil-insulated circuit breakers, small ripples are generally cast on the outer insulator<br />

surface exposed to the oil.<br />