[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Since C S in the case of tertiary-winding-connected shunt reactor is relatively smaller than C S for a<br />
shunt reactor directly connected to the high-voltage bus, tertiary-connected reactors normally experience<br />
overvoltages of lower magnitude.<br />
Vacuum circuit breakers have a constant I ch , which is weakly affected by the capacitance seen across<br />
its terminal. To obtain current chopping characteristics of a vacuum breaker, the breaker manufacturer<br />
should be consulted.<br />
IEEE C37.015-1993 provides helpful information for evaluating overvoltages caused by circuit breaker<br />
current chopping. [7]<br />
Current chopping can be mitigated by employing an opening resistor with the circuit breaker. The<br />
shunt reactor can also be protected against current-chopping overvoltages by a surge arrester installed<br />
across the reactor terminals.<br />
FIGURE 2.9.34 Single-phase equivalent circuit for a star-connected and solidly grounded shunt-reactor bank.<br />
C b = equivalent capacitance across the breaker terminals, F<br />
C S = system equivalent capacitance, F<br />
u L–G = system line-to-ground voltage, kV<br />
The parameter k a in Equation 2.9.37 provides a relative indication of the magnitude of the overvoltage<br />
for this type of reactor connection. Circuit damping effects are neglected.<br />
(2.9.37)<br />
where<br />
k a = per-unit parameter that indicates the relative magnitude of the overvoltage due to current<br />
chopping<br />
V reactor_chopping = maximum peak of the overvoltage across the reactor terminals after current chopping, kV<br />
V L–G = maximum peak line-to-ground system voltage, kV<br />
I ch = magnitude of current chopped, A<br />
C 1 = total capacitance on the reactor side, µF<br />
= angular power frequency, rad/s<br />
Q = shunt-reactor-bank three-phase MVAR<br />
For SF 6 , bulk-oil, and air-blast circuit breakers, I ch is a function of the high-frequency stray and grading<br />
capacitances in parallel with the circuit-breaker terminals [12]. Equation 2.9.38 shows this relationship.<br />
where<br />
k<br />
a<br />
2<br />
3.<br />
I<br />
V<br />
ch<br />
1 ka<br />
<br />
2. . CQ .<br />
1<br />
I<br />
ch<br />
.<br />
C<br />
reactor _ chopping<br />
VL<br />
G<br />
(2.9.38)<br />
= chopping number (AF –0.5 ), which depends on the circuit breaker construction and arcextinguishing<br />
media<br />
C CB = equivalent capacitance across the circuit breaker terminals for circuit represented in<br />
Figure 2.9.34, F<br />
C<br />
CB<br />
CB<br />
CS.<br />
CL<br />
Cb<br />
<br />
C C<br />
S<br />
L<br />
(2.9.39)<br />
2.9.4.2 Restrike<br />
When interrupting small inductive current just before the natural current zero, in a circuit with a critical<br />
combination of source-side and load-side capacitances and inductances, the voltage across the circuit<br />
breaker terminals may exceed its transient-recovery-voltage (TRV) capability and lead to circuit breaker<br />
restrikes. This process can repeat several times until the gap between the circuit breaker contacts becomes<br />
sufficiently large so that its dielectric withstand exceeds the voltage across the circuit breaker terminals.<br />
Each time the circuit breaker restrikes, a transient overvoltage is imposed on the reactor. This type of<br />
overvoltage has a very fast rate of rise of voltage that can distribute nonlinearly across the reactor winding<br />
turns. Current chopping can also increase the magnitude of transient overvoltages produced by restrike.<br />
Multiple restrikes can excite a resonant oscillation in the reactor winding. This can lead to highfrequency<br />
overvoltages between some coil winding turns. Equation 2.9.40 approximates the relative<br />
magnitude of the first restrike overvoltage for the reactor shown in Figure 2.9.34.<br />
<br />
k1<br />
k 1<br />
a<br />
<br />
CS<br />
C <br />
L<br />
<br />
CS<br />
C<br />
<br />
L<br />
V<br />
k <br />
V<br />
reactor _ restrike<br />
LG<br />
(2.9.40)<br />
When reactors are not solidly grounded, higher restrike voltages can occur. IEEE C37.015-1993 [7]<br />
provides detailed information for evaluating this type of overvoltage for reactors with different types of<br />
grounding.<br />
Restrike can be mitigated by the use of a surge arrester across the circuit-breaker terminals or by the<br />
use of a synchronous opening device with the circuit breaker. Overvoltages caused by restrike can be<br />
limited by adding a surge arrester across the reactor terminals. If multiple restrikes excite the natural<br />
frequency of the reactor winding, employment of an RC circuit can change the resonant frequency of<br />
the circuit and avert high-frequency overvoltages between coil winding turns.<br />
2.9.5 Current-Limiting Reactors and Switching Transients<br />
2.9.5.1 Definitions<br />
Transient-recovery voltage (TRV) is the voltage that appears across the contacts of a circuit-breaker pole<br />
upon interruption of a fault current. The first time that the short-circuit current passes through zero<br />
after the circuit breaker contacts part, the arc extinguishes and the voltage across the circuit breaker<br />
contacts rapidly increases. If the dielectric strength between the circuit breaker contacts does not recover<br />
as fast as the recovery voltage across the contacts, the circuit breaker will restrike and continue to conduct.<br />
There are various sources of the high rate of rise of transient-recovery voltage, which can potentially<br />
cause the circuit breaker to restrike, e.g., transformer impedance, short-line fault, or distant-fault reflected<br />
waves. In cases where the fault current is limited by the inductance of a current-limiting reactor, a high<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC