06.08.2018 Views

[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

I S2 = K I S1 (I S2 assumed I S1 , K 1), kA<br />

I bt = I L , the rated current of the bus-tie reactor, kA<br />

number of feeders on the section of the bus with the highest number of feeders<br />

Therefore, the required reactor impedance, in Ohms, in each configuration, their ratio, and the ratio of<br />

the rated power of the reactors are given by Equations 2.9.15a–d:<br />

FIGURE 2.9.31 Simplified radial system.<br />

X<br />

bt<br />

<br />

VLL<br />

3 I<br />

S2<br />

K ( 1)<br />

1<br />

<br />

K 1<br />

<br />

<br />

(2.9.15a)<br />

X<br />

fd<br />

<br />

VLL<br />

3 <br />

S2<br />

K ( 1)<br />

1<br />

<br />

( 1<br />

K)<br />

<br />

<br />

(2.9.15b)<br />

X<br />

X<br />

bt<br />

fd<br />

MVAbt<br />

Total MVA<br />

( 1<br />

K)<br />

<br />

K 1<br />

fd<br />

2<br />

( 1<br />

K)<br />

<br />

<br />

n<br />

<br />

K 1<br />

<br />

<br />

(2.9.15c)<br />

(2.9.15d)<br />

From the above, it is apparent that bus-tie reactors are a good solution where a relatively small reduction<br />

in fault level is required on a number of downstream feeders. However, bus-tie reactors increase rapidly<br />

in size and cost when (1) the fault contributions on either side of the reactor are significantly different<br />

(i.e., as K moves away from 1.0) and (2) when the largest fault contribution (I S1 ) approaches the breaker<br />

rating I b . Conversely, bus-tie reactors decrease rapidly in size and cost when the reactor can be given a<br />

low continuous rating due to low normal power transfer across the tie.<br />

FIGURE 2.9.32 <strong>Power</strong>-line-balance phasor diagram.<br />

2.9.3.3 <strong>Power</strong>-Line Balance<br />

Consider the radial system shown in Figure 2.9.31, in which the sending-end bus is fed from an infinite<br />

power source. By inspection of Figure 2.9.32, the following equations can be written:<br />

V = V 1 – V 2 (2.9.16)<br />

V = Z I (2.9.17)<br />

FIGURE 2.9.29 Bus-tie-reactor connection.<br />

V = [(R I cos ) + (X I sin )] + j [(X I cos ) – (RI sin )] (2.9.18)<br />

where<br />

= tan –1 (Q/P)<br />

V 1 = sending end voltage, kV<br />

V 2 = receiving end voltage, kV<br />

V = line voltage drop, kV<br />

R = line resistance, <br />

X = line reactance, <br />

I = line current, kA<br />

P = real power, kW<br />

Q = reactive power kVA<br />

= transmission angle, deg.<br />

= current phase angle, deg.<br />

Since P = V 2 I cos and Q = V 2 I sin , then<br />

V = [(P R + Q X) + j (P X – Q R)]/V 2 (2.9.19)<br />

FIGURE 2.9.30 Phase-reactor connection.<br />

where<br />

V f = in phase component of V, kV<br />

V q = quadrature component of V, kV<br />

V = V f + j V q (2.9.20)<br />

© 2004 by CRC Press LLC<br />

© 2004 by CRC Press LLC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!