[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
I S2 = K I S1 (I S2 assumed I S1 , K 1), kA<br />
I bt = I L , the rated current of the bus-tie reactor, kA<br />
number of feeders on the section of the bus with the highest number of feeders<br />
Therefore, the required reactor impedance, in Ohms, in each configuration, their ratio, and the ratio of<br />
the rated power of the reactors are given by Equations 2.9.15a–d:<br />
FIGURE 2.9.31 Simplified radial system.<br />
X<br />
bt<br />
<br />
VLL<br />
3 I<br />
S2<br />
K ( 1)<br />
1<br />
<br />
K 1<br />
<br />
<br />
(2.9.15a)<br />
X<br />
fd<br />
<br />
VLL<br />
3 <br />
S2<br />
K ( 1)<br />
1<br />
<br />
( 1<br />
K)<br />
<br />
<br />
(2.9.15b)<br />
X<br />
X<br />
bt<br />
fd<br />
MVAbt<br />
Total MVA<br />
( 1<br />
K)<br />
<br />
K 1<br />
fd<br />
2<br />
( 1<br />
K)<br />
<br />
<br />
n<br />
<br />
K 1<br />
<br />
<br />
(2.9.15c)<br />
(2.9.15d)<br />
From the above, it is apparent that bus-tie reactors are a good solution where a relatively small reduction<br />
in fault level is required on a number of downstream feeders. However, bus-tie reactors increase rapidly<br />
in size and cost when (1) the fault contributions on either side of the reactor are significantly different<br />
(i.e., as K moves away from 1.0) and (2) when the largest fault contribution (I S1 ) approaches the breaker<br />
rating I b . Conversely, bus-tie reactors decrease rapidly in size and cost when the reactor can be given a<br />
low continuous rating due to low normal power transfer across the tie.<br />
FIGURE 2.9.32 <strong>Power</strong>-line-balance phasor diagram.<br />
2.9.3.3 <strong>Power</strong>-Line Balance<br />
Consider the radial system shown in Figure 2.9.31, in which the sending-end bus is fed from an infinite<br />
power source. By inspection of Figure 2.9.32, the following equations can be written:<br />
V = V 1 – V 2 (2.9.16)<br />
V = Z I (2.9.17)<br />
FIGURE 2.9.29 Bus-tie-reactor connection.<br />
V = [(R I cos ) + (X I sin )] + j [(X I cos ) – (RI sin )] (2.9.18)<br />
where<br />
= tan –1 (Q/P)<br />
V 1 = sending end voltage, kV<br />
V 2 = receiving end voltage, kV<br />
V = line voltage drop, kV<br />
R = line resistance, <br />
X = line reactance, <br />
I = line current, kA<br />
P = real power, kW<br />
Q = reactive power kVA<br />
= transmission angle, deg.<br />
= current phase angle, deg.<br />
Since P = V 2 I cos and Q = V 2 I sin , then<br />
V = [(P R + Q X) + j (P X – Q R)]/V 2 (2.9.19)<br />
FIGURE 2.9.30 Phase-reactor connection.<br />
where<br />
V f = in phase component of V, kV<br />
V q = quadrature component of V, kV<br />
V = V f + j V q (2.9.20)<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC