[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
V<br />
90<br />
( X X )<br />
s<br />
T<br />
(2.9.10a)<br />
where, I SC = short circuit current, p.u.<br />
Since (X S + X T ) is small, the short-circuit current (I SC ) can become very large. The total transmitted<br />
power then equals the available power from the source (MVA SC ),<br />
S = V S I SC (2.9.11)<br />
FIGURE 2.9.28 Radial system.<br />
V ( V)<br />
s<br />
S 90<br />
( X X )<br />
s<br />
T<br />
(2.9.11a)<br />
where<br />
V S = sending end voltage, p.u.<br />
V R = receiving end voltage, p.u.<br />
V = bus voltage drop, p.u.<br />
I = bus current, p.u.<br />
Z S = source impedance, p.u.<br />
Z T = transformer impedance, p.u.<br />
Z L = load impedance, p.u.<br />
Under steady state, the load impedance 4 Z L essentially controls the current I, since both Z S and Z T are<br />
small. Also, typically X S R S , X T X S , and the load P L Q L . Therefore,<br />
V = V S – V R [PR S + Q(X S + X T )] (2.9.9)<br />
where<br />
P= real power, p.u.<br />
Q = reactive power, p.u.<br />
R S = source resistance, p.u.<br />
X S = source reactance, p.u.<br />
X T = transformer reactance, p.u.<br />
V = voltage drop, p.u.<br />
and V, per unit, is small<br />
When a short circuit occurs (closing the switch SW), V R 0 and Z L = 0 (bolted fault), and Equation<br />
2.9.8 can be rewritten as<br />
I SC = V/[R S + j (X S + X T )] (2.9.10)<br />
4<br />
The load may, in fact, be a rotating machine, in which case the back electromotive force (EMF) generated by the<br />
motor is the controlling factor in limiting the current. Nevertheless, this EMF may be related to an impedance, which<br />
is essentially reactive in nature.<br />
where, S = transmitted power, p.u.<br />
Therefore, as voltage drops, the system voltage is shared between the system impedance (transmission<br />
lines) and the transformer impedance:<br />
V S = V Q S (X S + X T ) (2.9.12)<br />
where, Q S = transmitted reactive power, p.u.<br />
Since X T is typically much larger than X S , the voltage drop across the transformer almost equals the<br />
system voltage. Two major concerns arise from this scenario:<br />
1. Mechanical stresses in the transformer, with the windings experiencing a force proportional to<br />
the square of the current<br />
2. Ability of the circuit breaker to successfully interrupt the fault current<br />
Therefore, it is imperative to limit the short-circuit current so that it will not exceed the ratings of<br />
equipment exposed to it. Basic formulas are as follows:<br />
Three-phase fault:<br />
1-to-ground fault:<br />
I 3 , kA = 100 [MVA]/[ 3 V LL Z 1 ] (2.9.13)<br />
I SLG , kA = 3 100 [MVA]/[ 3 V LL Z T ] (2.9.14)<br />
Z T = Z 1 + Z 2 + Z 0 + 3Z N<br />
(2.9.14a)<br />
where<br />
V LL = line-to-line base voltage, kV<br />
Z T = total equivalent system impedance seen from the fault, p.u.<br />
Z 1 , Z 2 , and Z 0 = equivalent system positive-, negative-, and zero-sequence impedance<br />
seen from the fault (in p.u. @ 100-MVA base)<br />
Z N = any impedance intentionally connected to ground in the path of the fault current, p.u.<br />
2.9.3.2 Phase Reactors vs. Bus-Tie Reactors<br />
A method to evaluate the merits of using phase reactors vs. bus-tie reactors is presented here. Refer to<br />
Figure 2.9.29 and Figure 2.9.30 and the following definitions:<br />
I S1 and I S2 = available fault contribution from the sources, kA.<br />
I L = rated current of each feeder, kA.<br />
n = total number of feeders in the complete bus (assuming all feeders are identical)<br />
I b = I S2 , the interrupting rating of the feeder circuit breakers, > 1, kA<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC