[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
FIGURE 2.9.13 Single line-to-ground fault in resonant-grounded system.<br />
FIGURE 2.9.15 Typical capacitor inrush/outrush reactor connection.<br />
Capacitor inrush/outrush reactors (Figure 2.9.15) are used to reduce the severity of some of the<br />
transients listed above in order to minimize dielectric stresses on breakers, capacitors, transformers, surge<br />
arresters, and associated station electrical equipment. High-frequency-transient interference in nearby<br />
control and communication equipment is also reduced.<br />
Reactors are effective in reducing all transients associated with capacitor switching, since they limit<br />
the magnitude of the transient current (Equation 2.9.5), in kA, and significantly reduce the transient<br />
frequency (Equation 2.9.6), in Hz.<br />
FIGURE 2.9.14 Typical duplex-reactor connection.<br />
I V * ( C / L )<br />
peak LL eq. eq.<br />
(2.9.5)<br />
2.9.2.2.5 Duplex Reactors<br />
Duplex reactors are usually installed at the point where a large source of power is split into two simultaneously<br />
and equally loaded buses (Figure 2.9.14). They are designed to provide low-rated reactance<br />
under normal operating conditions and full-rated or higher reactance under fault conditions. A duplex<br />
reactor consists of two magnetically coupled coils per phase. This magnetic coupling, which is dependent<br />
upon the geometric proximity of the two coils, determines the properties of a duplex reactor under<br />
steady-state and short-circuit operating conditions. During steady-state operation, the magnetic fields<br />
produced by the two windings are in opposition, and the effective reactance between the power source<br />
and each bus is a minimum. Under short-circuit condition, the linking magnetic flux between the two<br />
coils becomes unbalanced, resulting in higher impedance on the faulted bus, thus restricting the fault<br />
current. The voltage on the unfaulted bus is supported significantly until the fault is cleared, both by the<br />
effect of the reactor impedance between the faulted and unfaulted bus and also by the “voltage boosting”<br />
effect caused by the coupling of the faulted leg with the unfaulted leg of duplex reactors.<br />
The impedance of a duplex reactor can be calculated using Equation 2.9.1 and Equation 2.9.2, the<br />
same as those used for phase reactors.<br />
f 1/ 2<br />
Leq<br />
C<br />
<br />
. eq<br />
<br />
<br />
(2.9.6)<br />
where<br />
C eq = equivalent capacitance of the circuit, F<br />
L eq = equivalent inductance of the circuit, H<br />
V LL = system line-to-line voltage, kV<br />
Therefore, reflecting the information presented in the preceding discussion, IEEE Std. 1036-1992,<br />
Guide for Application of Shunt <strong>Power</strong> Capacitors, calls for the installation of reactors in series with each<br />
capacitor bank, especially when switching back-to-back capacitor banks.<br />
Figure 2.9.16 shows a typical EHV shunt-capacitor installation utilizing reactors rated at 550 kV/1550<br />
kV BIL, 600 A, and 3.0 mH. <br />
2.9.2.3 Capacitor Inrush/Outrush Reactors<br />
Capacitor switching can cause significant transients at both the switched capacitor and remote locations.<br />
The most common transients are:<br />
• Overvoltage on the switched capacitor during energization<br />
• Voltage magnification at lower-voltage capacitors<br />
• <strong>Transformer</strong> phase-to-phase overvoltages at line termination<br />
• Inrush current from another capacitor during back-to-back switching<br />
• Current outrush from a capacitor into a nearby fault<br />
• Dynamic overvoltage when switching a capacitor and transformer simultaneously<br />
FIGURE 2.9.16 550-kV capacitor inrush/outrush reactors.<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC