[James_H._Harlow]_Electric_Power_Transformer_Engin(BookSee.org)
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
FIGURE 2.9.10 Two generator arrangements where a reactor can be used as a neutral-grounding device: unit system<br />
(left) and three-wire system (right).<br />
chapter 19 of the Westinghouse <strong>Electric</strong>al Transmission and Distribution Reference Book [2] can<br />
be employed for this case.<br />
3. The rated short-circuit duration for the grounding reactor shall also be specified. When reactors<br />
are used for a single isolated generator or in a unit system, a 10-sec rating is usually employed.<br />
When grounding reactors are used in systems having feeders at generator voltage, a 1-min rating<br />
is usually employed to accommodate for repetitive feeder faults.<br />
4. The rated continuous current of the grounding reactor should be specified considering the allowable<br />
unbalance current and third-harmonic current. In the absence of this information, 3% of the<br />
reactor short-circuit rating can be specified as the continuous-current rating when the duration<br />
of the rated short-circuit current is 10 sec. In cases when the rated short-circuit duration is 1 min,<br />
7% of rated short-circuit current is recommended as the rated continuous current. See IEEE Std.<br />
32-1972 for more information. [3]<br />
5. Insulation class and associated BIL (basic impulse insulation level) rating should be specified based<br />
on (1) the reactor voltage drop during a single line-to-ground fault and (2) the nominal system<br />
voltage. Refer to Table 4 of IEEE Std. 32-1972. [3]<br />
Transient overvoltages are another important consideration in the application of generator neutralgrounding<br />
reactors. When the neutral of a generator is not solidly grounded, transient overvoltages can<br />
be expected. These overvoltages are usually caused by phase-to-ground arcing faults in air or by a<br />
switching operation followed by one or more restrikes in the breaker. When a grounding reactor is used<br />
for generator neutral grounding, the X 0 /X 1 ratio at the generator terminals shall be less than three to<br />
keep transient overvoltages within an acceptable level. (X 0 and X 1 are the resultant of the generator and<br />
system zero- and positive-sequence reactances, respectively.) When a neutral-reactor installation is<br />
intended only for reduction of a single line-to-ground fault to the three-phase fault level, X 0 /X 1 is equal<br />
to unity, which is a safe ratio in terms of imposed transient overvoltages.<br />
2.9.2.2.4 Arc-Suppression Reactors (Petersen Coils)<br />
An arc-suppression coil is a single-phase, variable-inductance, oil-immersed, iron-core reactor that is<br />
connected between the neutral of a transformer and ground for the purpose of achieving a resonant<br />
neutral ground. The zero-sequence impedance of the transformer is taken into consideration in rating<br />
the inductance of the arc-suppression coil. The adjustment of inductance is achieved in steps by means<br />
of taps on the winding, or inductance can be continuously adjusted by varying the reluctance of the<br />
magnetic circuit. The length of an air gap is adjusted by means of a central moveable portion of the core<br />
(usually motor driven). See Figure 2.9.11. The inductance is adjusted, in particular during nongroundfault<br />
conditions, to achieve cancellation of the capacitive ground-fault current, so that in the case of a<br />
single line-to-ground fault, cancellation of the capacitive fault current is achieved with an inductive<br />
current of equal magnitude. Current injection by an active component (power converter) into the neutral,<br />
usually through an auxiliary winding of the arc-suppression coil, can also provide cancellation of the<br />
resistance component of the fault current. See Figure 2.9.12 and Figure 2.9.13, which illustrate this<br />
FIGURE 2.9.11 Arc-suppression reactor.<br />
FIGURE 2.9.12 Single line-to-ground fault in nongrounded system.<br />
principle for nongrounded and resonant-grounded systems, respectively. Resonant grounding is used in<br />
distribution systems in Europe, parts of Asia and in a few areas of the U.S. The type of system ground<br />
employed is a complex function of system design, safety considerations, contingency (fault) operating<br />
practices, and legislation. Arc-suppression reactors are typically used to the best advantage on distribution<br />
systems with overhead lines to reduce the intermittent arcing-type single line-to-ground faults that may<br />
otherwise occur on ungrounded systems.<br />
© 2004 by CRC Press LLC<br />
© 2004 by CRC Press LLC