RCB-1.3 TESTING<br />

RCB-1.31 STANDARD TEST<br />

• The exchanger shall be hydrostatically tested with water.<br />

• The test pressure shall be held for at least 30 minutes.<br />

• The shell side and the tube side are to be tested separately in such a<br />

manner that leaks at the tube joints can be detected from at least one<br />

side.<br />

When the tube side design pressure is the higher pressure, the tube bundle<br />

shall be tested outside of the shell only if specified by the purchaser and the<br />

construction permits. Welded joints are to be sufficiently cleaned prior to<br />

testing the exchanger to permit proper inspection during the test.<br />

• The minimum hydrostatic test pressure at room temperature shall be in<br />

accordance with the Code.<br />

RCB-1.311 OTHER UQUID TESTS<br />

Liquids other than water may be used as a testing medium if agreed upon<br />

between the purchaser and the manufacturer.<br />