AC .AMMETERS<br />
WATER TEMPERATURE GAU EMOTE HEATER WITCH<br />
Cranking Limiter: Some systems have a thermally<br />
activated device that limitscranking 45 to 90seconds<br />
depending on ambient temperature. A red pushbut-<br />
ton popsout and cannot be reset until one minute has<br />
elapsed. Other solid state systems (DTA) limit crank-<br />
Ing to 45-75 seconds before energizing a fault relay.<br />
The relay stops the cranking function and turns on a<br />
red Overcrank lamp.<br />
Running Time Metec Registers the total number of<br />
hours, to I/lOth that the unit has run. Use it to keep a<br />
record for periodic servicing. Time is accumulative;<br />
meter cannot be reset.<br />
Frequency Meter: Indicates the frequency of the<br />
generator output in hertz. It can be used to check<br />
engine speed. (Each hertz equals 30 rpm.)<br />
Wzrning Lights: Indicator lights are used on some<br />
controls to give warning of:<br />
UN-STOP SWITCH<br />
FIGURE 71. TYPlCAL RAMATOR-COOLED SET CONTROL PANEL<br />
56<br />
set failed to start<br />
Overspeed<br />
Low oil pressure<br />
Pre low oil pressure<br />
Low engine temperature<br />
High engine temperature<br />
Pre high engine temperature<br />
Overcrank<br />
Start switch in Off position<br />
Reset pushbuttons orswitches permit restarting after<br />
,trouble is corrected.<br />
Line Circuit Breaker: Protects generator from line<br />
overloads.<br />
Water Temperature Gauge: Indicates temperature of<br />
circulating coolant in engine. (Wired to a sensor unit<br />
located on the engine.)<br />
.)