WIRING CONNECTIONS, 15-25 kW<br />
SINGLE PHASE ALTERNATORS<br />
The most popular single phase connection is the<br />
120/240combination. With this connection either 120<br />
or 240 volts can be used alone or at the same time<br />
(Figure 41).<br />
Refer to <strong>page</strong> 8for wiring connections of 30 kW units<br />
using the UR control.<br />
EXCITER<br />
WINDING<br />
VOLTMETER<br />
LINE I<br />
CIRCUIT c85<br />
BREA KE R<br />
VOLTAGE<br />
&:<br />
REGULATOR '<br />
F;Gi?F -'-<br />
,e3 to. 1<br />
FIELD BREAKER<br />
GI( I ) ALTERNATOR<br />
?I<br />
CBi CB2<br />
1,-q<br />
RECEPTACLE<br />
POWER<br />
CAB LE<br />
RECEPTACLE<br />
240 v.<br />
RECEPTACLE<br />
& GROUND<br />
r<br />
FIGURE 41.120/240 VOLT, SINGLE PHASE CONNECTION<br />
40<br />
THREE PHASE ALTERNATORS<br />
Three phase alternators are connected as shown in<br />
Figure 42. The three load wires are connected to T1,<br />
T2 and T3. Single phase (240 volts) can be obtained<br />
between any two three-phase terminals. Single phase<br />
(120volts) can be obtained between T1 and TO or T2<br />
and TO. TO is the grounded terminal for 120 volts.<br />
EXCITER<br />
WINDING<br />
OUTPUT<br />
LEADS<br />
VOLTAGE REGULATOR<br />
T4<br />
ALTERNATOR<br />
FIELD BREA .KER<br />
w<br />
I20 v.<br />
RECEPTACLE<br />
POWER<br />
CABLE<br />
RECEPTACLE<br />
240 V.<br />
RECEPTACLE<br />
FIGURE 42 THREE PHASE 240 VOLT DELTA CONNECTIONS<br />