OHMMETER RESISTANCE BETWEEN<br />

Fl AND F2 SHOULD BE<br />

13.05 TO 15.95 OHMS AT 7'F (25°C)<br />

FIGURE 27. TESTING EXCITER FIELD<br />

IJI<br />

TESTING EXCITER ROTOR<br />

Test the exciter rotor (Figure 28) for open or shorted<br />

windings or grounds as follows:<br />

Testing for Open or Shorted Windings:<br />

Use a Wheatstone Bridge for this test. Disconnect<br />

main rotor field leads which connect to rotating recti-<br />

fier assemblies at F1+ and F2-. Disconnect lead wires<br />

from diodes CR1, CR2, CRq, CR4, CR5and CR6.Test<br />

between exciter lead pairs Tl-T2, T2-T3 and Tl-T3.<br />

Resistance should be 0.6 to 0.7 ohms at 68" F (2OOC).<br />

Testing for Grounds:<br />

Connect leads of ohmmeter between each CR lead<br />

and exciter rotor laminations; use RX 100 scale on<br />

ohmmeter. An ohmmeter reading less than infinity<br />

(.) indicates defective ground insulation.<br />

FI<br />

CRS<br />

FIGURE 28. TESTING EXCITER ROTOR<br />

29<br />

TESTING GENERATOR STATOR<br />

Using proper test equipment, check the stator for<br />

grounds, opens, and shorts in the windings.<br />

Testing for Grounds:<br />

Some generatots have ground connections to the frame. Check<br />

wiring diagram.<br />

Using an ohmmeter set at RX 100, test each stator<br />

winding for shorts to laminations. A reading lessthan<br />

one megohm indicates a ground.<br />

Testing for Open or Shorted Windings:<br />

Test for continuity between coil leads shown in Fig-<br />

ure 29; all pairs should have equal resistance. Use an<br />

accurate instrument for this test such as a Kelvin<br />

Bridge. Resistance valuesat 77' F (25OC) are given in<br />

Table 6.<br />

If any windings are shorted, open or grounded,<br />

replace the stator assembly. Before replacing the<br />

assembly, check the leads for broken wires or insula-<br />

tion.<br />

kW RATING<br />

60 Hertz<br />

DTAIMDTA 25.0 kW<br />

SK 30.0 kW<br />

PTO 30.0 kW<br />

THREE PHASE MODELS<br />

TEST BETWEEN WIRE PAIRS<br />

VOLTAGE CODE<br />

75 3c<br />

-066 to .081 .031 to -038<br />

Ohms Ohms<br />

.a99 to -121 -027 to -033<br />

Ohms<br />

Code 50<br />

Ohms<br />

Tl-T2, T2-T3, -032 to .039<br />

T3-Tl .149to<br />

.183 Ohms<br />

Ohms