START<br />

Is control panel field<br />

breaker CB21 ON?<br />

no<br />

A<br />

and check continuity with<br />

ohmmeter. Is breaker open?<br />

ti0<br />

I<br />

Replace defective<br />

field breaker.<br />

v<br />

I 1 4 I I<br />

I<br />

t -t-l<br />

Push to reset breaker. Does generator<br />

If voltage is unstable, high or low, or<br />

causes breaker to trip, see Flow Charts<br />

AC output voltage build up?<br />

B. C, D. or E<br />

P I I I I<br />

I - 1 t<br />

no<br />

Is residual voltage across 1621-62 and 63<br />

5 to 10 VAC or more?<br />

Check reactor L21 and transformer T21 per<br />

TESTS [B] and [E].<br />

Is exciter field voltage<br />

across VR21-5 & 6 5 VDC<br />

Check exciter field wiring<br />

for opens per TEST [MI.<br />

Replace bad wiring.<br />

Check exciter field winding<br />

per TEST [HI. Replace<br />

if bad.<br />

Do not replace the printed circuit board<br />

until the trouble not on the PC board has<br />

been located and corrected to avoid damage lo new PC board.<br />

Check diodes and SCR's on<br />

bridge assembly CR21 per<br />

TEST [C].<br />

Check fuses F2 and F3 for<br />

continuity on VR21 regu-<br />

Check exciter field wiring<br />

for shorts per TEST [MI.<br />

Replace bad wiring.<br />

v<br />

Replace voltage regulator<br />

PC board per procedure IF].<br />

' 22<br />

Flash exciter field per TEST [D]. Does<br />

generator output voltage build up?<br />

Disconnect stator leads 7 and 8 from TB21-62<br />

and 63. Is residual voltage across leads 5<br />

to 10 VAC or more now?<br />

I<br />

Check lead continuity between<br />

VR21-12 & l7 on generator,<br />

I<br />

Check diodes CR1 through CR6<br />

on rotor per TEST [GI. Re-<br />

I<br />

Check exciter rotor winding<br />

per TEST [J]. Replace if bad.<br />