Photo 18: The draw<strong>in</strong>g of PA fan is seen here. The <strong>in</strong>let box seemed to be small as compared to<br />

fan impeller size. Moreover IGV comes <strong>in</strong> the p<strong>at</strong>h of air flow <strong>at</strong> high velocity zones. The IGV<br />

could block the air flow <strong>in</strong>stead of swirl<strong>in</strong>g it.<br />

700x1800<br />

700x1530<br />

125<br />

400<br />

6<br />

400<br />

355x800<br />

225<br />

158<br />

255<br />

365<br />

350<br />

850<br />

Ø950<br />

1,700<br />

Ø810<br />

Ø1,428.5<br />

175<br />

750<br />

425<br />

350<br />

865.5<br />

400<br />

Figure 1: The PA fan <strong>in</strong>let box was found to be too small <strong>in</strong> comparison with a better<br />

perform<strong>in</strong>g PA fan of almost same design parameters. Small suction box with IGV would work<br />

as sharp ell duct <strong>in</strong>stead of uniformly distribut<strong>in</strong>g suction box.