<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

PUBLIC AREAS<br />

3.8. Wet Treatment Rooms<br />

The interior walls and floor of the wet treatment rooms (approximately 150 ft 2 – 14 m 2 )<br />

should be finished with stone. Concealed cove lighting with independent dimmer switch<br />

and temperature thermostat. All walls are to be soundproofed to achieve a rating of STC<br />

54. The room is also to have a 2’0” wide x 4’0” (0.6 x 1.2m) long counter with sink and<br />

storage cabinets above and below. Duplex electrical outlets and telephone outlet. Robe<br />

hooks and towel bars.<br />

In addition the rooms are to have the following features:<br />

a) Vichy shower and table<br />

b) 4” (10 cm) Diameter stainless steel floor drain<br />

c) Shower cubicle (as per guestroom shower requirements).<br />

3.9. Sauna Room<br />

The interior of the sauna (approximately 120 ft 2 – 11.1m 2 ) should be finished<br />

throughout in selected cedar, including the floor with three tiers of seating, each 2’0”<br />

(0.6 m) wide. The double glazed entry door with a wooden handle both sides, is to open<br />

out. Adjacent to the outside of the entry door will be the temperature control (set to a<br />

maximum of 180 F – 82 C), rob hooks and the emergency buzzer (connected to the<br />

reception desk).<br />

3.10. Steam Room<br />

The walls and ceiling (sloped) of the steam room (approximately 120 ft 2 – 11.1 m 2 ) is to<br />

be constructed in sand and cement plaster and finished with ceramic tiles. The floor and<br />

seating areas are to have non-slip stone finish. A tempered glass entry door with<br />

wooden handle both sides, is to open out. Adjacent to the outside of the entry door will<br />

be the temperature control, rob hooks and the emergency buzzer (connected to the<br />

reception desk). The floor is to incorporate a floor drain and the steam source requires<br />

access for regular maintenance.<br />

3.11. Janitor’s Closet<br />

A janitor’s closet (approximately 120 ft 2 – 11.1 m 2 ) will have the following features:<br />

a) Floor sink with hot and cold service sink faucet, with ceramic tile<br />

surround<br />

b) Adjustable shelving 16” wide by 4’0” (04. x 1.2 m) (minimum of<br />

four shelves)<br />

c) Mop rack<br />

d) Vinyl floor and vinyl baseboard<br />

e) Wall mounted telephone.<br />

REV. MARCH 2006 67<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.