Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Electrical and LAN Closet:<br />

• Separate room for LAN equipment<br />

Typical Guestroom Provisions:<br />

• Power, telephone, lighting and TV outlets as per interior<br />

designer<br />

• Confirm if 120 volt (US) outlet is required at desk<br />

• Handicapped provisions such as strobes, vibrating pillow, etc. as<br />

per local code<br />

Special Guestrooms Sound System:<br />

• Residential stereo conduit rough-in for Two-Bedroom and<br />

Presidential Suites. Includes two systems with two speakers in<br />

master bedroom and four speakers in living room and dining<br />

room. Homerun location is armoire unit in each room.<br />

SPECIFICATIONS<br />

Power Distribution<br />

Have copper conductors and bus been specified?<br />

Has electrical equipment been suitably dearated for temperature in areas<br />

where ambient temperatures are in the range of 105 F ?<br />

Have concealed conduit and devices been specified in all front-of-house<br />

areas and back-of-house areas except storage and service rooms?<br />

Have lamacoid nameplates been specified for all equipment?<br />

Is the interrupting capacity of all distribution panels and switchgear been<br />

specified to ensure that the equipment can safely withstand the available<br />

fault current?<br />

Have one or all of the following wiring methods been described?<br />

• Enclosed bus duct for main transformers<br />

• Multi-core armored cables or cables in conduit for large feeders<br />

to distribution pads, motor control centers and branch<br />

panelboards<br />

• Small branch circuit wiring in conduit or unarmored double<br />

insulated cable in tray for devices in ceiling space or in hollow<br />

cavity walls<br />

Emergency Power<br />

Does the generator specification include a statement for “the generator to<br />

handle a 100% load step”?<br />

Does the transfer switch specification include bypass provisions in order to<br />

avoid shutting down the load or maintenance?<br />

YES<br />

NO<br />

REV. MARCH 2006 288<br />

©2002 Fairmont Hotels & Resorts. All Rights Reserved