Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

• Local channels<br />

•<br />

• English speaking channel (NBC)<br />

• CNN<br />

• Movie channel<br />

• In-house safety movie<br />

Have TV outlets been located in the following locations:<br />

• All guest bedrooms and living rooms<br />

• All public area bars and entertainment rooms<br />

• Staff dining<br />

• Ballrooms and meeting rooms in the “AV” baseboard provision<br />

• Health Club exercise room adjacent to each piece of equipment<br />

• Staff boardroom and training room<br />

• In TV storage room and TV repair area<br />

Miscellaneous Communication Systems<br />

Have the following communication systems been provided under the<br />

general contract?<br />

• Portable handheld radios including repeater station, microphone<br />

control console and transmission line. (Approximate quantity of<br />

11 for city hotels and 20 for resorts).<br />

• Portable pagers including transmitter, base station and<br />

transmission line. (Approximate quantity of 20 keynote and 10<br />

Bravo for city hotels; 32 keynote and 15 Bravo for resorts).<br />

• Wireless remote sound system for the hearing impaired in the<br />

large ballroom as per Local Code requirements.<br />

Power Distribution System and Electric Service<br />

The power distribution system design shall comply with the applicable<br />

Local Code, however, the following minimum requirements should be<br />

provided:<br />

• Two (2) main power transformers with secondary switchboard<br />

interconnections with a tie breaker. Ideal design is each<br />

transformer loaded 50% with full redundancy, however, 66%<br />

loading with generator in the event of transformer failure is<br />

acceptable. 100% loading of transformers is acceptable only if<br />

transformers are utility-owned with rapid replacement in the<br />

event of failure.<br />

• Power factor correction capacitors for main switchboard.<br />

• Distribution panels and motor control centers located adjacent to<br />

large loads such as kitchens, laundry, function rooms,<br />

mechanical plant, etc.<br />

• Separate automatic transfer switch for fire pumps as per North<br />

American Standards.<br />

YES<br />

NO<br />

REV. MARCH 2006 280<br />