Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

TYPICAL OCCUPANCY REQUIREMENTS & LIGHTING/EQUIPMENT LOAD<br />

ESTIMATES<br />

Areas Serviced<br />

Recommended Load<br />

Occupancy Lighting/Equipment Notes<br />

Range<br />

Bedrooms 2P 1250 w Refer to (A)<br />

Restaurant 1P/15 ft 2 45-65 w/10 ft 2<br />

Banquet Hall 1 P/9 ft 2 108-135 w/10 ft 2<br />

Bar 1 P/11 ft 2 30-55 w/10 ft 2<br />

Meeting Rooms < 700 ft 2 1 P/22 ft 2 55-75 w/10 ft 2<br />

Meeting Rooms > 700 ft 2 1 P/11 ft 2<br />

Shops 1 P/55 ft 2 30-55 w/10 ft 2<br />

Offices 1 P/110 ft 2 30-55 w/10 ft 2 Refer to (B)<br />

Lobby 1 P/38 ft 2 55-65 w/10 ft 2<br />

Reception Hall 1 P/18 ft 2 55-65 w/10 ft 2<br />

Spa/Fitness Center 1 P/55 ft 2 30-55 w/10 ft 2 Refer to (C)<br />

Computer Center<br />

Review with FHR<br />

Autocom<br />

Review with FHR<br />

Personal Dining Room 1 P/15 ft 2 30-55 w/10 ft 2<br />

Note:<br />

A) The following occupancy rates should be followed for the areas listed below:<br />

• Presidential Suites living/dining area: 15 - 20 ft 2 per person<br />

• Two bedroom suite living/dining area: 15 - 20 ft 2 per person<br />

• One bedroom suite living/dining area: 4 persons<br />

The preliminary lighting and power load estimate used in corridor areas typically range between<br />

35 – 45 w/10 ft 2 .<br />

B) The lighting and power loads in office areas typically range between 30-55<br />

w/10 ft 2 for lighting with electronic ballasts and 55-75 w/10 ft 2 for lighting with standard<br />

ballasts.<br />

C) The cooling load for Fitness Center exercise rooms should be calculated based on a fully<br />

occupied room with guests doing a vigorous workout. The Spa and Fitness Center lighting and<br />

power loads should range between 30-55 w/10 ft 2 . However, for the exercise rooms located<br />

within the Fitness Center, lighting and power loads typically range between 100-160 w/10 ft 2 .<br />

This is primarily due to the heat generated from the number of exercise machines located in<br />

these rooms.<br />

D) The activity level for each person is a function of the usage for the specific area served. A<br />

substantially greater quantity of heat is dissipated in activities like dancing or exercising as<br />

opposed to sedentary type of activities. ASHRAE Standard 55-1992 should be followed.<br />

REV. MARCH 2006 274<br />