Fairmont Hotels & Resorts · Design Standards<br />

APPENDICES<br />

Plumbing<br />

Does the domestic hot water load for the suites reflect the following:<br />

10 gal. - storage per bedroom<br />

15 gal. - recovery rate per bedroom<br />

Has additional domestic hot water tanks been provided for the Laundry,<br />

Kitchen, Suites and Public space areas respectively?<br />

Do the temperatures for domestic hot water correspond to the following:<br />

120 F - for bedrooms, public areas<br />

140 F - for kitchens<br />

160 F - for laundry<br />

Has cold water storage been provided where the water source is unreliable<br />

or required by local authorities?<br />

Has adequate water softening been provided?<br />

Has adequate water treatment been provided as required by world health<br />

organization standards?<br />

Has the domestic hot water system been provided with a recirculation<br />

system to maintain temperature throughout the system during low usage<br />

periods?<br />

Have dedicated isolation valves for DHW and DCW been provided within<br />

each hotel suite for the respective suite?<br />

Do the types of plumbing fixtures conform to the FHR Standards?<br />

Have lavatories and water closets been provided as indicated in FHR’s<br />

Standards?<br />

Have steeping bathtubs been provided in each of the guestrooms?<br />

Have showerheads been provided with a minimum flow rate of 5 USGPM?<br />

Have pressure balancing mixing valves been provided for showers?<br />

Is the water pressure provided in each hotel suite as required by the<br />

showerhead manufacturer?<br />

Have DCW and drainage piping been provided for ice machines?<br />

Has the can wash equipment been specified?<br />

Is the drainage piping for the hotel guestrooms cast iron?<br />

Has at least one drain been provided for each public or back-of-house<br />

washroom area?<br />

Has the maintenance work shop and the paint shop areas each been<br />

provided with a sink?<br />

Has the loading dock and porte cochere been provided with a hose bibb to<br />

serve a power spray wash?<br />

Hotel Guestrooms<br />

Are the fan coil units serving the guest suites capable of three-speed<br />

operation and temperature control as per FHR’s Standards?<br />

Are the fan coil unit sizes for guest suites based on medium speed, with<br />

NC levels of 35 for daytime operation, and low speed, with NC levels of<br />

30 for nighttime operation? (High speed must be provided for quick cool<br />

down)<br />

YES<br />

NO<br />

REV. MARCH 2006 270<br />