SERVICES AND SYSTEMS<br />

Computer Room<br />

a) A main central computer shall be provided in the accounting offices area to house<br />

all network servers. The Systems Manager’s office should be located next to the<br />

computer room with glazed partition between.<br />

b) The floor finish should be anti-static VAT, ceiling w/suspended acoustic tiles.<br />

c) All cabling to be installed in ceiling mounted open cable trays.<br />

d) The room should be air conditioned with an independent unit hooked up to the<br />

emergency power supply to maintain the room at 20°C (± 3°C) and 50% RH.<br />

e) Ventilation and AC system to be provided with high efficiency filters.<br />

f) Provide temperature sensors connected to the EMS to enable low/high temperature<br />

alarm.<br />

g) No pipes or equipment containing liquid are to be installed above the computer<br />

room except for sprinkler pipes where they are required by local bylaws or building<br />

code.<br />

h) Smoke detector and fire extinguisher to be provided in computer room.<br />

i) Lighting to be recessed fluorescent fixtures on emergency power supply.<br />

j) Electrical supply to on dedicated circuits from the hotel’s main distribution panel.<br />

k) A minimum of 10 KVA power supply is required.<br />

l) UPS (Uninterruptible Power Supply) must be provided (10 KVA, 3 phase, 208/120<br />

VAC with non-evaporative type battery back-up).<br />

m) Number of outlets varies depending on equipment provided by FHR. Generally one<br />

duplex 120 VAC, 15A outlet will be required for each Server, and one outlet for<br />

each PC, Monitor, printer, modem and network hub. A typical 400-room hotel will<br />

require approximately 16 duplex outlets in the computer room. Exact number of<br />

outlet will be confirmed with FHR prior to completing construction documents and<br />

specifications.<br />

n) The computer equipment shall be mounted on a shelving system; this system will<br />

allow equipment to be plugged in.<br />

REV. MARCH 2006 241<br />