Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

7.2. Horizontal Cabling<br />

HC<br />

Horizontal<br />

Cabling<br />

a) The intended use is to provide a 100 ohm UTP signalling path between the Horizontal<br />

Cross-connect in the Telecommunications Closet and the Telecommunications<br />

Outlet/Connector serving the Work Area(s).<br />

b) The horizontal UTP cable shall meet or exceed the enhanced Category 5 transmission<br />

characteristics per the latest issue of ANSI/TIA/EIA-568.<br />

c) The plenum version of the horizontal UTP cable shall be ETL or UL Listed and CSA<br />

Certified as Type CMP, in accordance with the Bi-national Standard for Communications<br />

Cable, UL 444/C22.2 No. 214-94.<br />

d) The non-plenum version of the horizontal UTP cable shall be ETL or UL Listed and CSA<br />

Certified as Type CMR or CM, in accordance with the Bi-national Standard for<br />

Communications Cable, UL 444/C22.2 No. 214-94.<br />

e) The horizontal UTP cable shall comply with Class A limits of FCC Part 15, Subpart J for<br />

computing devices for electromagnetic radiation when tested with appropriate<br />

networking protocols.<br />

REV. MARCH 2006 234<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.