Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

7. TECHNOLOGY SERVICES – PRODUCT SPECIFICATIONS<br />

7.1. Cabling Overview<br />

Enhanced Category 5 UTP specifications<br />

a) The UTP-based cabling system shall have a 160 MHz channel bandwidth over a<br />

maximum distance of 100m (328 ft) and a channel power sum attenuation-tocrosstalk<br />

ratio (PSACR) of 9.6 dB @ 100 MHz using an interconnect or BIX cross<br />

connect configuration.<br />

b) The UTP-based cabling system shall use matched components from a single<br />

manufacturer, certified to deliver system performance over the lifetime of the<br />

applications that the cabling system was originally designed to support.<br />

c) All components used in the UTP-based cabling system shall be warranted for a<br />

period of 25 years from date of installation against defects in materials and<br />

workmanship.<br />

d) The UTP-based cabling system shall comply with the following standards:<br />

Enhanced Category 5 - TIA/EIA Addendum<br />

Category 5 - ANSI/TIA/EIA-568, TIA/EIA TSB67<br />

Class D - CENELEC EN50173<br />

Class D - ISO/IEC 11801<br />

Optical Fiber Cabling System<br />

a) The optical fiber-based cabling system shall provide a 160 MHz-km bandwidth @<br />

850 nm and 500 MHz-km bandwidth @ 1300 nm using 50/125 micron 6 strand<br />

multimode optical fiber.<br />

b) The optical fiber-based cabling system shall use matched components from a single<br />

manufacturer, certified to deliver system performance over the lifetime of the<br />

applications that the cabling system was originally designed to support.<br />

c) All components used in the optical fiber-based cabling system shall be warranted<br />

for a period of 25 years from date of installation against defects in materials and<br />

workmanship.<br />

d) The optical fiber-based cabling system shall comply with the following standards:<br />

ANSI/TIA/EIA-568<br />

CENELEC EN50173<br />

ISO/IEC 11801<br />

e) The optical fiber-based cabling system shall be capable of supporting the following<br />

native fiber-based applications as well as environments where native copper-based<br />

electrical signals are converted to an optical stream:<br />

Gigabit Ethernet (1000BASE-SX and LX)<br />

Fast Ethernet (100BASE-FX)<br />

REV. MARCH 2006 233<br />