Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Administration Specifications<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit. Where conduit is not provided in existing hotels, cable shall be<br />

plenum rated where regulation require.<br />

a) Voice<br />

b) Data<br />

Each telephone line will be run with Cat 5 e cable (see section 7.1, distance<br />

applies to Data only), as well all jacks must terminated on RJ-11 jacks and<br />

installed onto a quad jack faceplate. Voice RJ-11 jacks must be terminated with a<br />

BLACK Connector/Jack.<br />

Each workstation area shall have:<br />

Two RJ-11C terminations.<br />

Each data line will be run with Cat 5 e cable (see section 7.1), terminated on an 8<br />

wire, 8-position jack. Each RJ-45 Data connection will be terminated with a<br />

BLUE Data jack.<br />

Each workstation area shall have:<br />

Two RJ-45 terminations.<br />

Meeting and Ballrooms Specifications<br />

All cable shall be 4-pair enhanced category 5, unshielded twisted pair cable. All cabling shall<br />

be in a metal or PVC conduit. Where conduit is not provided in existing hotels, cable shall be<br />

plenum rated where regulation require.<br />

Each meeting room and divisible section of meeting rooms or ballrooms shall have at least, one<br />

quad jack faceplate with two RJ-11C terminations and two RJ-45 terminations for data. Each<br />

voice and data line will be run with Cat 5 e cable (see section 7.1, distance applies to Data<br />

only). This jack shall be mounted in an appropriate A/V niche to provide maximum service to<br />

the space, usually at the front or side of the room. Voice RJ-11 jacks must be terminated with a<br />

BLACK Connector/Jack.<br />

Each divisible section of a large meeting rooms and all sections of ballrooms shall have one 6-<br />

plex jack with each jack terminated as RJ-11 C for voice. In addition it shall also have at least,<br />

one quad jack faceplate with two RJ-45 terminations for data. Each voice and data line will be<br />

run with Cat 5 e cable (see section 7.1, distance applies to Data only). These jacks shall be<br />

mounted in an appropriate A/V niche to provide maximum service to the space, usually at the<br />

front or side of the room.<br />

REV. MARCH 2006 225<br />