Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Electrical/General Requirements (continued)<br />

Mechanical, electrical equipment areas<br />

20 (215 lm/m2)<br />

w/task lighting at each<br />

motor control center and<br />

electical switchboard<br />

Housekeeping and Laundry 50 (538 lm/m 2 )<br />

Maintenance Areas 50 (538 lm/m 2 )<br />

with 75 (810 lm/m 2 )<br />

on all work surfaces<br />

Kitchen Areas 50 (538 lm/m 2 )<br />

Meeting Rooms 50 (538 lm/m 2 )<br />

Ballroom Foyers 35 (376 lm/m 2 )<br />

Main Lobby and Employee lockers 30 (322 lm/m 2 )<br />

Assembly and Circulation 25 (269 lm/m 2 )<br />

Food and Beverage outlets and Porte Cochere 20 (215 lm/m 2 )<br />

Mechanical, electrical general areas 20 (215 lm/m 2 )<br />

Elevator foyer and guest corridors 10-20 (108 – 215 lm/m 2 )<br />

Lighting fixtures in public areas are to be recessed and/or surface mounted<br />

incandescent. The exception to this will be coved or display cases and where specialist<br />

millwork requires individual lighting treatment. The recessed lighting fixtures for<br />

general illumination in the public areas is to be, in general, of the low brightness type,<br />

parabolic aperture cones, open apertures with ellipsoidal reflectors, baffle aperture<br />

down lights, etc., supplemented with adjustable accent lights, decorative chandeliers,<br />

etc.<br />

Recessed fluorescent fixtures are to be installed in all the Administrations Offices,<br />

except the General Manager’s and any other BOH areas that have windows overlooking<br />

public areas. These are to have incandescent lighting fixtures.<br />

Outdoor parking, garden and street lighting are to be super metal halide or low pressure<br />

sodium.<br />

All fluorescent lighting fixtures are to be warm white with rapid start ballast.<br />

In mechanical rooms, a fluorescent light fixture is to be mounted at each motor control<br />

center and is to be on emergency power.<br />

3.2. Dimming Equipment<br />

Dimming equipment is to be Lutron. Similar equipment manufactured by other<br />

dimming equipment companies are acceptable, subject to approval by Fairmont Hotels<br />

& Resorts.<br />