Fairmont Hotels & Resorts · Design Standards<br />
SERVICES AND SYSTEMS<br />
Electrical/General Requirements (continued)<br />
Mechanical, electrical equipment areas<br />
20 (215 lm/m2)<br />
w/task lighting at each<br />
motor control center and<br />
electical switchboard<br />
Housekeeping and Laundry 50 (538 lm/m 2 )<br />
Maintenance Areas 50 (538 lm/m 2 )<br />
with 75 (810 lm/m 2 )<br />
on all work surfaces<br />
Kitchen Areas 50 (538 lm/m 2 )<br />
Meeting Rooms 50 (538 lm/m 2 )<br />
Ballroom Foyers 35 (376 lm/m 2 )<br />
Main Lobby and Employee lockers 30 (322 lm/m 2 )<br />
Assembly and Circulation 25 (269 lm/m 2 )<br />
Food and Beverage outlets and Porte Cochere 20 (215 lm/m 2 )<br />
Mechanical, electrical general areas 20 (215 lm/m 2 )<br />
Elevator foyer and guest corridors 10-20 (108 – 215 lm/m 2 )<br />
Lighting fixtures in public areas are to be recessed and/or surface mounted<br />
incandescent. The exception to this will be coved or display cases and where specialist<br />
millwork requires individual lighting treatment. The recessed lighting fixtures for<br />
general illumination in the public areas is to be, in general, of the low brightness type,<br />
parabolic aperture cones, open apertures with ellipsoidal reflectors, baffle aperture<br />
down lights, etc., supplemented with adjustable accent lights, decorative chandeliers,<br />
etc.<br />
Recessed fluorescent fixtures are to be installed in all the Administrations Offices,<br />
except the General Manager’s and any other BOH areas that have windows overlooking<br />
public areas. These are to have incandescent lighting fixtures.<br />
Outdoor parking, garden and street lighting are to be super metal halide or low pressure<br />
sodium.<br />
All fluorescent lighting fixtures are to be warm white with rapid start ballast.<br />
In mechanical rooms, a fluorescent light fixture is to be mounted at each motor control<br />
center and is to be on emergency power.<br />
3.2. Dimming Equipment<br />
Dimming equipment is to be Lutron. Similar equipment manufactured by other<br />
dimming equipment companies are acceptable, subject to approval by Fairmont Hotels<br />
& Resorts.<br />
REV. MARCH 2006 204<br />
© 2002, Fairmont Hotels and Resorts. All Rights Reserved.