SERVICES AND SYSTEMS<br />

Electrical/General Requirements (continued)<br />

a) Public restrooms<br />

b) Each ballroom and pre-function section<br />

c) Meeting rooms<br />

d) Spa/Fitness Center<br />

f) Flood, sump and sewage pumps<br />

g) Automatic transfer equipment to bring all elevators to main lobby level,<br />

each one at a time, while at the same time keeping the fireman’s elevator<br />

continually operational<br />

h) Telephone systems<br />

i) Freezers, refrigerators and circulation pumps for refrigeration cooling<br />

j) All computer equipment and computer room HVAC equipment<br />

k) Fire protection and life safety<br />

l) HVAC equipment used for smoke control, stairwell and elevator shaft<br />

pressurization<br />

m) Uninterrupted power supply<br />

n) Oil heaters for chillers<br />

o) All paging systems<br />

p) Security systems including CCTV<br />

q) Automatic door.<br />

The main distribution system using at least two transformers, secondary and/or primary<br />

tie or transfer switches, standby cable or equivalent, is to be designed and specified to<br />

prevent total loss of power in the event of maintenance or a failure of any single piece<br />

of equipment, bus or cable in the primary and main secondary distribution.<br />

An automatic load limiting system is to be designed and specified to shut down the<br />

following loads when the loads exceeds the predetermined limit:<br />

a) Toilet exhaust fans<br />

b) Miscellaneous general ventilation systems<br />

c) Public space air-conditioning systems (provide over-ride)<br />

d) Chillers (only as a last resort)<br />

e) Electric water heating.<br />

Panel boards are to be designed and specified to meet the following general criteria:<br />

REV. MARCH 2006 202<br />