Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

a) All side wall supply registers are to be the double deflection type with<br />

opposed blade d<strong>amp</strong>ers<br />

b) All return and exhaust registers are to be the single deflection type with<br />

opposed blade d<strong>amp</strong>ers<br />

c) Ceiling diffusers in public areas are to be linear<br />

d) The inside of supply and return ducts and plenums in public areas are to<br />

painted matt black for any portion visible through the grill<br />

e) Registers and diffusers are to be factory prime coated.<br />

Sound levels due to air conditioning and ventilation equipment, pipes, ducts, etc are to<br />

be designed to not exceed the following criteria:<br />

a) Guestrooms and suites - NC 30 with FCU on low speed<br />

b) Ballrooms, conference rooms, executive offices and massage rooms - NC<br />

30<br />

c) Public spaces, general offices, lobby lounge, main dining and general<br />

office - NC 35<br />

d) Staff cafeteria, swimming pool and health club – NC 40<br />

e) Kitchen and laundry – NC 50.<br />

Neoprene or vinyl coated fiberglass of 1 ½ pounds density acoustic duct lining of at<br />

least 1” thickness is to provided and installed to the following areas:<br />

a) Discharge and intake ducts of every low pressure handling unit for a<br />

minimum distance of 15’0” (4.6 m)<br />

Insulating materials shall be provided and installed to all piping,<br />

mechanical equipment, ductwork, etc.<br />

REV. MARCH 2006 198<br />