Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

a) Supply grills<br />

b) Return grills<br />

c) Thermostats<br />

d) Guest bathroom exhaust grills.<br />

Electric motors are to be designed and specified to meet the following criteria:<br />

a) Motors and controls driving heating, ventilating and air conditioning<br />

equipment are to be supplied and installed by the Mechanical Contractor.<br />

The wiring for this equipment is to be supplied and installed by the<br />

Electrical Contractor<br />

b) All motors are to be of the quiet operating type and preferably should be<br />

from one manufacturer<br />

c) All motors and accessories are to comply in all aspects with NEMA<br />

standards, are to include a service factor and to be energy efficient<br />

d) Exhaust fans for guestroom dishwashers are to be wired so that the fan<br />

only works when the dishwasher is in operation.<br />

Ducts are to be designed and specified to meet the following criteria:<br />

a) Kitchen range hood exhaust ducts are to be manufactured from 16 gauge<br />

black iron and are to be provided with clean-outs are each bend, every 10<br />

(3 m) feet horizontally and every 20 feet (6 m) vertically<br />

b) Dishwashers and laundry flat ironers are to be manufactured from<br />

stainless steel for a minimum distance of 25 feet (7.6 m) from the<br />

equipment.<br />

c) Horizontal ducts from dishwashers are to pitch toward the equipment at<br />

one inch per ten feet<br />

d) Swimming pool supply air ducts are to be manufactured from aluminum,<br />

while exhaust ducts are to be manufactured from stainless steel<br />

e) Laundry dryer exhaust ducts are to be manufactured from galvanized<br />

steel with water tight joints and the interiors are to be smooth and free<br />

from any intrusions<br />

f) Fire d<strong>amp</strong>ers are to be installed in all ducts piercing shaft walls and shall<br />

have suitable eyes and standard fusible links as well an exterior device,<br />

which will visibly show the position of the d<strong>amp</strong>er.<br />

Grilles, registers and diffusers are to be designed and specified to meet the following<br />

criteria:<br />

REV. MARCH 2006 197<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.