Fairmont Hotels & Resorts · Design Standards<br />

SERVICES AND SYSTEMS<br />

Mechanical/General Requirements (continued)<br />

a) Kitchen to have a required temperature of 80 F (27 C) dry bulb at 60%<br />

b) Bake shop, pastry shop, laundry and valet to have a required temperature<br />

of 80 F (27 C)<br />

c) Garde manger, chocolate shop, butcher shop and beverage stores to have<br />

a required temperature of 65 F (18 C)<br />

d) Computer room to have a required temperature of 72 F (22 C)<br />

e) Telephone equipment room to have a required temperature of 78 F (26).<br />

The VAV systems are to be designed using the following criteria:<br />

a) Maintain absolute minimum total system static<br />

b) Maintain absolute minimum duct velocities commensurate with economic<br />

and space limitations:<br />

i) Hotel bedroom and general offices – 1000 FPM<br />

ii) Boardrooms – 1200 FPM<br />

iii) Meeting rooms, ballrooms and pre-function areas – 800 FPM<br />

iv) Restaurants – 1500 FPM.<br />

c) Ducting should avoid components such as mitred elbows, conventional<br />

and acoustical turning valves, bullhead tees, etc in order to ensure that<br />

noise is kept to a minimum<br />

d) The air distribution ductwork must be sized on the basis of the Static<br />

Regain Method (SRM)<br />

e) Pressure-independent low-pressure VAV regulators must be selected to<br />

serve each occupied space<br />

f) Supply duct connection must be either galvanized metal or a maximum of<br />

five feet of bonded aluminum flex with no more than a 45° bend<br />

g) Terminal ceiling diffusers or booted-plenum slots specifically designed<br />

for VAV air distribution from the standpoint of minimum “dumping”<br />

action at reduced air volumes and from the standpoint of sound levels at<br />

maximum cfm delivery is to be selected.<br />

Quiet operating centrifugal fans are to be designed following:<br />

a) Rated in accordance with AMCA procedure and shall bear the AMCA<br />

seal<br />

b) Class I, II or II as recommended by AMCA based upon both operating<br />

pressures and maximum tip speed<br />

REV. MARCH 2006 194<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.