<strong>FAIRMONT</strong> <strong>HOTELS</strong> & <strong>RESORTS</strong> · <strong>DESIGN</strong> <strong>STANDARDS</strong><br />

BACK-OF-HOUSE<br />

1.6. Standard Lighting Fixtures<br />

Back-of-house lighting in areas with exposed ceiling and/or T-bar ceilings shall be energy<br />

efficient recessed fluorescent fixtures complete with hinged acrylic lens. Fixture sizes shall be<br />

standardized to l<strong>amp</strong> sizes with a preference for 1’0” x 4’ 0” (0.3 x 1.2m) or 2’0” x 4’0’<br />

(0.6 x 1.2m) light fixtures. Fixtures in kitchens, laundry or other d<strong>amp</strong> locations shall be<br />

gasketted. Fixtures in service and storage rooms may be strip lights complete with wire guards.<br />

a) All fluorescent fixtures throughout the hotel shall be warm white<br />

with rapid start premium electric type for T-8 l<strong>amp</strong>s.<br />

b) Standardize lengths of fluorescent light fixtures where possible<br />

c) All storerooms and offices shall have room lighting controlled by<br />

local switches located inside the room and adjacent to the entrance<br />

door. Where a room has more than one entrance, three way<br />

switching shall be provided. The switches in storerooms shall<br />

incorporate a power outlet for housekeeping purposes<br />

d) In mechanical rooms, a fluorescent light fixture shall be mounted<br />

at each motor control centre and shall be on emergency power<br />

supply<br />

e) Exit lighting to have the minimum wattage l<strong>amp</strong>s permitted by<br />

code.<br />

f) Public area exits shall have thin line exit fixtures with bronze<br />

finish and fitted with a long life electronic circuit.<br />

g) Back-of-house exits shall have standard width exit fixtures with a<br />

paint finish and fitted with a long life electronic circuit.<br />

h) Fixtures in fire escape stairs shall be mounted on main landings<br />

only unless otherwise stated by local code.<br />

1.7. Other Offices<br />

Coffee/Tea Room to include the following features:<br />

a) A built in counter 2’0” wide and 3’0” (0.6 x 0.9 m) AFFL<br />

(incorporating a stainless steel sink with adjustable shelving<br />

below counter and lockable cabinets above<br />

b) One 110V 15 <strong>amp</strong> duplex outlet (refrigerator)<br />

c) Three 110V 15 <strong>amp</strong> duplex outlets (both of separate circuits) at<br />

4’0” (1.2 m) to centre line AFFL (kettle and coffee maker).<br />

REV. MARCH 2006 148<br />

© 2002, Fairmont Hotels and Resorts. All Rights Reserved.