Standard Number<br />

<strong>2012</strong> <strong>Hilton</strong> <strong>Garden</strong> <strong>Inn</strong><br />

<strong>Summary</strong> <strong>of</strong> <strong>Changes</strong><br />

Below is a list <strong>of</strong> items you will not want to miss!<br />

Standard Type Location<br />

Effective August 1, <strong>2012</strong>, all new builds must comply with all Operations (Sections 100-1700) and Design & Construction<br />

standards (Section 2500). Beginning October 1, <strong>2012</strong>, all existing hotels must comply with the following Operation standards<br />

changes. Non-compliance <strong>of</strong> the following items will result in point deductions during quality assurance evaluations unless an<br />

alternative compliance date is indicated. All properties that choose to voluntarily renovate, or do so as required by a PIP must<br />

comply with the Design & Construction standards upon renovation. (updated 8/1/12)<br />

2515.04 Top Surfaces (entire section) Addition<br />

2515.05 Art (entire section) Addition<br />

2515.06 Mirrors (entire section) Revision<br />

2516.03.B.5<br />

2516.03.E.1<br />

2516.03.E.1.a<br />

2516.03.E.1.b<br />

2516.03.E.1.c<br />

2516.03.E.1.d<br />

2516.03.E.1.e<br />

2516.03.E.1.f<br />

2516.03.E.1.g<br />

2516.03.E.2<br />

Concealed sprinkler heads are required in the Pavilion. All<br />

other public areas must be concealed or recessed.<br />

Concealed or recessed (ceiling or sidewall) sprinkler<br />

heads must be used in guestrooms.<br />

Where a kitchen hood exhaust system is used to control<br />

grease-laden vapors, the following fire protection systems<br />

and hood/duct construction criteria must be verified as<br />

being installed:<br />

A fire suppression system designed for the installation in a<br />

kitchen hood to protect kitchen appliances and the kitchen<br />

hood exhaust system. The suppression system must<br />

provide protection <strong>of</strong> the kitchen cooking appliances, the<br />

kitchen exhaust hood, and the exhaust plenum portion <strong>of</strong><br />

the hood connection to the exhaust duct.<br />

The kitchen exhaust hood and the exhaust ducting must<br />

be solely dedicated to the exhaust <strong>of</strong> grease laden vapors<br />

and must be separated from all other exhaust systems.<br />

The kitchen hood and exhaust ducting must not be<br />

constructed <strong>of</strong> any material that is subject to corrosion or<br />

heat degradation. No galvanized metal is allowed.<br />

Kitchen exhaust duct system must be constructed and<br />

installed so that grease cannot collect or leak from any<br />

joint in any portion <strong>of</strong> the exhaust system.<br />

Grease duct cleanout access panels must be provided to<br />

allow inspection and cleaning <strong>of</strong> all sections <strong>of</strong> the duct<br />

system. Acecss hatches must not be spaced more than<br />

19'-8"/6 m apart.<br />

All sections <strong>of</strong> the exhaust duct must have a two-hour fireresistive<br />

rating from the point <strong>of</strong> duct penetration <strong>of</strong> a<br />

ceiling, wall or floor to its exterior termination.<br />

Clearance <strong>of</strong> the kitchen exhaust duct to the interior<br />

surface <strong>of</strong> combustible materials must be not less than 15-<br />

3/4" / 400 mm, or from noncombustible material must not<br />

be less than 6"/150 mm.<br />

New and replacement kitchen hood suppression systems<br />

referred to in 2516.03.E.1.a must be pre-engineered wetchemical<br />

fire extinguishing systems rated compliant with<br />

UL 300 (www.ul.com) or GB 50016-2006 Clause 8.5.8 and<br />

provided with connection to the hotel’s automatic sprinkler<br />

system or reliable water supply.<br />

Revision<br />

Revision<br />

Addition<br />

Addition<br />

Addition<br />

Addition<br />

Addition<br />

Addition<br />

Addition<br />

Revision<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

United States, Canada, South<br />

America, Central America,<br />

Mexico, Caribbean<br />

10 <strong>of</strong> 11