<strong>SPARK</strong> <strong>GAPS</strong><br />

<strong>DEHN</strong> (<strong>UK</strong>) LTD<br />

DS179<strong>UK</strong>/08/10


<strong>DEHN</strong> - Isolating Spark Gaps<br />

Process plants such as refineries, oil, gas and product pipelines belong to the largest and most sophisticated building<br />

structures. They form the lifelines for regions and entire countries. Reliability, quality and efficiency are important<br />

factors for the oil and gas industry to establish themselves on the market. Therefore safe operation of all electrical<br />

and electronic installations and systems is the most important aspect.<br />

Due to the large size, location and construction as well as the use of modern measuring and control technology, the<br />

reliability of these installations is threatened by surges due to lightning or switching operations. The repair costs for<br />

replacing damaged systems are considerably higher than the costs of installing lightning protection systems and<br />

surge protective devices, not to mention the revenue lost due to operational downtime.<br />

<strong>DEHN</strong> also offers practical protection against lightning and surges for the cathodic corrosion protection system.<br />

Decades of .. experience in lightning and surge protection for petrochemical systems as well as intensive research by<br />

<strong>DEHN</strong> + SOHNE have led to the development of comprehensive protection solutions. This allows a substantial<br />

reduction of lightning damage e.g. at isolating pipe flanges, CP installations and control rooms. More importantly,<br />

consequential production failures and operational downtime due to lightning are reduced to a minimum.<br />

..<br />

<strong>DEHN</strong> + SOHNE offers ATEX and IEC/Ex approved isolating spark gap products for use in EX Zones 1, 2, 21 and 22.<br />

Latest certificates available to download on www.dehn.co.uk


EXFS 100 / EXFS 100 KU LIGHTNING EQUIPOTENTIAL BONDING<br />

For explosion-hazard areas ISOLATING <strong>SPARK</strong> <strong>GAPS</strong> (Zones 1, 2, 21, 22)<br />

ATEX-certified isolating spark gap for lightning<br />

equipotential bonding according to IEC 62305 with<br />

low sparkover voltage.<br />

EXFS 100: Isolating spark gap for use in explosion-hazard areas with plastic coating and M10 connecting nut.<br />

EXFS 100 KU: Isolating spark gap for use in explosion-hazard areas with 2m connection cable for above / underground installation.<br />

The Ex isolating spark gaps of the EXFS 100 / EXFS 100 KU product family are used<br />

when conductive installation components situated in explosion-hazard areas<br />

cannot be connected directly with each other. The spark gaps with low<br />

sparkover voltage are especially efficient for isolated installation components<br />

with little insulation resistance. No special regulations have to be observed for<br />

safe application in zone 1 with gases or zone 21 with dusts. With a maximum<br />

lightning impulse current of 100 kA (10/350 us), EXFS 100 and EXFS 100 KU meet<br />

class H according to EN 50164-3 “Lightning Protection Components (LPC) - Part 3:<br />

Requirements for isolating spark gaps”. The ATEX-certified spark gaps EXFS 100<br />

and EXFS 100 KU provide approved safety according to harmonised European<br />

standards. For connecting EXFS 100 spark gaps, prewired connecting cables with<br />

different lengths are available as accessories. Flat and angled connection<br />

brackets make it easier to connect the spark gaps to pipe flanges. EXFS 100 KU<br />

types are enclosed by a damp-proof plastic coating and are ideally suited for<br />

underground installation at insulation couplings.<br />

EXFS 100 EXFS 100 KU<br />

Lightning impulse current (10/350 us) Iimp 100 kA 100 kA<br />

Class of lightning current carrying capability acc. to EN<br />

50164-3<br />

H H<br />

Nominal discharge current (8/20 us) In 100 kA 100 kA<br />

Rated power-frequency withstand voltage (50 Hz) Uw/<br />

ac<br />

250 V 250 V<br />

100% Lightning impulse sparkover voltage Urimp ≤1.25 kV ≤1.25 kV<br />

Power-frequency sparkover voltage (50 Hz) Uaw ≤0.5 kV ≤0.5 kV<br />

Rated discharge current (50 Hz) Imax 500 A/0.5 sec. (Tu: 45 C) 500 A/0.5 sec. (Tu 45 C)<br />

(Ex) marking acc. To EN 60079 (gases) II 2G Ex d IIC T6 II 2G ExdIIC T6<br />

(Ex) marking acc. To EN 61241 (dusts) II 2D Ex tD A21 lP67 T 80 C II 2D Ex tD A21 lP67 T 80 C<br />

Operating temperature range Tu -20 C…+60 C -20 C…+60 C<br />

Degree of protection IP 67 IP 67<br />

Approvals, Certifications BVS 06 ATEX E 099, IECEx KEM<br />

09.0051...<br />

BVS 06 ATEX E 099, IECEx KEM<br />

09.0051...<br />

Length of enclosure 100 mm 123 mm<br />

Diameter of enclosure 45.5 mm 34 mm<br />

Enclosure material Plastic coating Plastic coating; water-proof coating<br />

Connection of enclosure Thread nut M10, 2x M10x25 mm,<br />

2 x spring washer<br />

NYY-J-1 x 25 mm ,<br />

approx. 2 m long<br />

Type EXFS 100 EXFS 100 KU<br />

Part No. 923 100 923 101<br />

Packing unit 1 pc(s) 1 pc(s)<br />

For indirect connection/earthing of functionally isolated installation components when<br />

being affected by lightning.<br />

Device for lightning equipotential bonding according to IEC 62305 in explosion-hazard<br />

areas (1, 2, 21, 22).<br />

For bridging insulation pieces, insulation flanges etc. in cathodically corrosion-protected<br />

pipe sections.<br />

For safe installation in explosion protected zone 1, 2, 21, 22 (Gas, Dust according to ATEX<br />

Directives)<br />

Particularly low sparkover voltage.<br />

Especially high a.c. current withstand capability. 100 kA (according to EN 50164-3)<br />

Extremely heavy duty device IP 67.<br />

Installation of EXFS 100 EXFS 100 Installation of EXFS 100 KU<br />

EXFS 100 KU<br />

o<br />

o<br />

o<br />

o<br />

2<br />

o<br />

o<br />

Accessory Parts for EXFS 100 / EXFS 100 KU<br />

EXFS 100: Connection cable, Cu 25 mm<br />

Connecting cable for EXFS 100;2 cable lugs 010.5<br />

mm hexagon screw and nut (M10), StSt spring &<br />

washer<br />

Type Cable lug<br />

material<br />

Cross<br />

section<br />

Cable<br />

length<br />

Pair of angled connection brackets - IF 1 -<br />

Pair of angled connection brackets for EXFS ..;<br />

diameter corresponds to bolt diameter of the<br />

bolted flange joint (d1 up to max. 60mm, please<br />

indicate the diameter required when placing your<br />

order)<br />

Pair of flat connection brackets - IF 3 -<br />

Pair of flat connection brackets for EXFS ..;<br />

diameter corresponds to bolt diameter of the<br />

bolted flange joint (d1 up to max. 60mm, please<br />

indicate the diameter required when placing your<br />

order)<br />

2<br />

Pu<br />

pc(s)<br />

Part No<br />

2<br />

AL EXFS L100 KS Cu/gal Sn 25mm 100mm 1 *923 025<br />

2<br />

AL EXFS L200 KS Cu/gal Sn 25mm 200mm 1 *923 035<br />

2<br />

AL EXFS L300 KS Cu/gal Sn 25mm 300mm 1 *923 045<br />

Type Material Pu pc(s). Part No.<br />

IF1 St/t/Zn 1<br />

*923 011<br />

Type Material Pu pc(s). Part No.<br />

IF3 St/t/Zn 1<br />

*923 016<br />

*None sparking approved accessories eliminate the possibility of<br />

sparking in explosion-hazard areas


EXFS L / EXFS KU LIGHTNING EQUIPOTENTIAL BONDING<br />

For use in explosion-hazard areas ISOLATING <strong>SPARK</strong> <strong>GAPS</strong> (Zones 2)<br />

ATEX-certified isolating spark gap for lightning equipotential<br />

bonding according to IEC 62305, approved device with flexible<br />

conductor connection.<br />

EXFS L..: Isolating spark gap for use in explosion-hazard areas with flexible connecting cable<br />

EXFS KU: Isolating spark gap for use in explosion-hazard areas with 1.5m connecting cable for above/underground installation<br />

Installation of EXFS L... EXFS L... EXFS KU<br />

EXFS L100,200,300 EXFS KU<br />

Lightning impulse current (10/350 us) Iimp 50 kA 50 kA<br />

Class of lightning current carrying capability acc. to EN<br />

50164-3<br />

N N<br />

Nominal discharge current (8/20 us) Iin 100 kA 100 kA<br />

Rated power-frequency withstand voltage (50 Hz) Uw/<br />

ac<br />

300 V 300 V<br />

100% Lightning impulse sparkover voltage Urimp ≤2.5 kV ≤2.5 kV<br />

Power-frequency sparkover voltage (50 Hz) Uaw ≤1.2 kV ≤1.2 kV<br />

Type of protection acc. EN 50014, EN 50021 II 3 G EEx nC II T4 II 3 G EEx nC II T4<br />

Operating temperature range Tu -20 C…+80 C -20 C…+80 C<br />

Degree of protection IP 54 IP 67<br />

Approvals, Certifications ZELM 03 ATEX 3192X ZELM 03 ATEX 3192X<br />

Length of enclosure 90 mm 90 mm<br />

Diameter of enclosure 63 mm 63 mm<br />

Enclosure material Zinc diecasting, plastic Zinc diecasting, plastic<br />

Connection cable<br />

2<br />

H01N2-D 25mm with cable lug and<br />

screw/nut (M10)<br />

2<br />

NYY-J-1x25 mm<br />

Cable length* 100, 200, 300 mm * 2 x approx. 1500mm<br />

Suitable for flange size 20-130, 120-230, 220-320 mm<br />

Type EXFS L100, 200, 300 EXFS KU<br />

Part No. 923 060, 923 061, 923 062 923 019<br />

Packing unit 1 pc(s) 1 pc(s)<br />

*Cable length for EXFS L100 - 100mm, L200 - 200mm, L300 - 300mm. Custom lengths also available.<br />

For indirect connection/earthing of functionally isolated installation<br />

components when being affected by lightning.<br />

Device for lightning equipotential bonding acc. to IEC 62305 in<br />

explosion-hazard areas (Zone 2).<br />

According to “ATEX Directive” 94/9/EC.<br />

Corrosion-resistant zinc diecasting enclosure with plastic cover and<br />

flexible conductor connection.<br />

For bridging insulating pieces, insulation flanges etc. in cathodically<br />

corrosion protected pipe sections.<br />

Heavy-duty device.<br />

Ex isolating spark gaps of the EXFS L / EXFS KU product family are used when the direct interconnection of electrically conductive<br />

installation components in Ex areas is not acceptable. As, for example, in the case of cathodically corrosion protected pipeline sections.<br />

ATEX-certified EXFS L and EXFS KU spark gaps provide approved and tested safety in accordance with harmonised European standards.<br />

The arc-resistant tungsten-copper electrodes ensure a long service life of the Ex spark gaps. The approved type EXFS L with flexible<br />

conductor connection quickly adapts to any application environment. The prewired spark gaps provide connecting cables with different<br />

lengths with cable lugs, screws and M10 nut. The flat or angled connection brackets allow for easy connection of the spark gap to<br />

pipeline flanges. The EXFS KU type is enclosed in a damp-proof PVC enclosure and is ideal for underground installation at insulating<br />

couplings.<br />

o<br />

o<br />

Accessory Parts for EXFS L / EXFS KU<br />

Pair of angled connection brackets - IF 1 -<br />

Pair of angled connection brackets for EXFS …;<br />

diameter corresponds to bolt diameter of the<br />

bolted flange joint (d1 up to max. 60 mm, please<br />

indicate the diameter required when placing your<br />

order)<br />

Type Material Pu pc(s). Part No.<br />

IF1 St/t/Zn 1<br />

*923 011<br />

Pair of flat connection brackets - IF 3 -<br />

Pair of flat connection brackets for EXFS ..; diameter<br />

corresponds to bolt diameter of the bolted<br />

flange joint (d1 up to max. 60mm, please indicate<br />

the diameter required when placing your order)<br />

Type Material Pu pc(s). Part No.<br />

IF3 St/t/Zn 1<br />

*923 016<br />

*None sparking approved accessories eliminate the possibility of<br />

sparking in explosion-hazard areas


1<br />

2<br />

3<br />

LIGHTNING AND SURGE PROTECTION FOR PIPELINE STATIONS<br />

<strong>DEHN</strong>ventil M TNC 255 (FM)<br />

951 300 (305)<br />

<strong>DEHN</strong>ventil M TNS 255 (FM)<br />

951 400 (405)<br />

<strong>DEHN</strong>ventil M TT 255 (FM)<br />

951 310 (315)<br />

Multipole modular lightning current<br />

and surge arrester for protection of<br />

the power supply in low voltage<br />

distribution systems<br />

BLITZDUCTOR BXT ML4 BD 180 + BXT BAS.<br />

920 347 + 920 300<br />

Universal, pluggable lightning current and<br />

surge arrester for telecommunication and<br />

telecontrol systems with integrated LifeCheck<br />

BLITZDUCTOR BXT ML4 BD EX 24 + BXT BAS<br />

EX. 920 381 + 920 301<br />

Universal, pluggable surge arrester for 2<br />

isolated intrinsically safe measuring circuits<br />

with integrated LifeCheck<br />

EXFS 100. 923 100<br />

ATEX certified spark gap for use<br />

in hazardous areas (Zone 1, 2, 21,<br />

22) for protection against over<br />

voltages and lightning currents<br />

<strong>DEHN</strong>pipe DPI MD EX 24 M 2.<br />

929 960<br />

Surge arrester for protection of<br />

intrinsically safe measuring<br />

circuits made of stainless steel for<br />

outdoor areas (IP 67) for screwing<br />

into 2-wire filed devices<br />

Pipe clamps for hazardous areas.<br />

e.g. 540 803<br />

Pipe clamp for connecting pipes of<br />

different materials and diameters which<br />

allows for discharging lightning currents<br />

in hazardous areas (Zone 1, 2, 21, 22)<br />

without ignition sparks<br />

Schematic diagram: Lightning and Surge protection for a pipeline station<br />

For more information refer to www.dehn.co.uk or the <strong>DEHN</strong> <strong>UK</strong> main catalogue<br />

4<br />

5<br />

6


1 BLITZDUCTOR VT KKS BVT KKS ALD 75.<br />

918 420<br />

Lightning current and surge arrester<br />

for protection of active corrosion<br />

protection installations (anode<br />

electrical circuit) with integrated<br />

remote signalling contact. Installation<br />

in steel plate enclosure recommended<br />

2<br />

<strong>DEHN</strong> PROTECTS CATHODIC PROTECTION (CP) SYSTEMS<br />

3 ITAK KKS. 989 406/S;<br />

4 EXFS L 100. 923 060<br />

4<br />

Aluminium connection box,<br />

ATEX certified spark gap<br />

IP 65, for protection of CP<br />

for use in hazardous<br />

installations, completely<br />

areas (Zone 2) for<br />

equipped with lightning<br />

protection against over<br />

current and surge arrester<br />

voltages and lightning<br />

type BVT KKS ALD 75 + BVT<br />

KKS APD 36<br />

currents<br />

BLITZDUCTOR VT KKS BVT KKS APD 36.<br />

918 421<br />

Lightning current and surge arrester for<br />

protection of active corrosion protection<br />

installations (sensor measuring circuit) with<br />

integrated remote signalling contact.<br />

Installation into steel plate enclosure<br />

recommended<br />

EXFS 100. 923 100<br />

ATEX certified spark gap for<br />

use in hazardous areas (Zone<br />

1, 2, 21, 22) for protection<br />

against over voltages and<br />

lightning currents<br />

Each cable going out of the CP rectifier (measuring and anode electrical circuit) is led via a lightning current and surge<br />

arrester especially adjusted to CP installations. Thus, the partial lightning currents coming from the pipeline as well as<br />

surges caused by switching operations can be controlled safely. It is recommended to install the lightning current and<br />

surge arresters into a separate steel enclosure in order to prevent any threats to the CP installation due to overloads<br />

e.g. via overhead lines.<br />

Schematic diagram: Lightning and Surge protection for CP systems<br />

For more information refer to www.dehn.co.uk or the <strong>DEHN</strong> <strong>UK</strong> main catalogue


Notes


Lightning Protection<br />

Surge Protection<br />

Safety Protection<br />

<strong>DEHN</strong> (<strong>UK</strong>) LTD<br />

Unit N8B Meltham Mills<br />

Meltham<br />

Holmfirth<br />

West Yorkshire<br />

HD9 4DS<br />

Tel: 01484 859111<br />

Fax: 01484 859222<br />

Email: info@dehn.co.uk<br />

Web: www.dehn.co.uk